Classrooms

Discover the energy-saving potential of classrooms with Rayzeek’s occupancy sensor design guide. Learn how to meet energy code requirements while creating a more efficient learning environment.

Transforming Classrooms into Energy-Efficient Learning Spaces

Classrooms are dynamic spaces that serve as the foundation for learning and development. They are often filled with a variety of lighting fixtures, from overhead lights to task lighting, all of which contribute to a significant amount of energy consumption. The lighting in these spaces is typically left on for extended periods, even when the room is unoccupied, leading to unnecessary energy waste.

In a typical classroom, the lighting needs can vary greatly depending on the time of day, the activities taking place, and the number of occupants. This variability makes it challenging to manage lighting effectively and efficiently. As a result, there is a pressing need for solutions that can automatically control lighting based on occupancy, thereby reducing unnecessary energy consumption.

The need for energy conservation in classrooms is clear, and one of the most effective solutions is the use of occupancy sensors. These devices can automatically turn off lights when a room is vacant, significantly reducing energy consumption. With Rayzeek’s range of occupancy sensors, classrooms can become more energy-efficient, meeting the requirements of energy codes while also reducing operational costs.

עמידה בתקני האנרגיה

התקן הבינלאומי לשימור אנרגיה (IECC) הוא תקן מודל שפותח על ידי מועצת התקנים הבינלאומית (ICC) כדי לקבוע דרישות תכנון ובנייה מינימליות ליעילות אנרגטית במבנים. ה-IECC מתעדכן מדי שלוש שנים כדי לשלב את שיטות העבודה והטכנולוגיות העדכניות ביותר בתחום שימור האנרגיה.

IECC, מדוע זה צריך לעניין אותך

תקן IECC מאומץ במידה רבה על ידי מדינות ורשויות מקומיות ברחבי ארצות הברית. IECC מכסה היבטים שונים של שימוש באנרגיה, לרבות מעטפת הבניין (קירות, גגות וחלונות), מערכות חימום וקירור, ומערכות תאורה.

תקן IECC מחייב בקרות תאורה ספציפיות, כגון חיישני תפוסה, כדי למזער בזבוז אנרגיה בחללים לא מאוכלסים באזורים שונים.

תקן ANSI/ASHRAE/IES 90.1, תקן אנרגיה לאתרים ולמבנים למעט מבני מגורים נמוכים, הוא תקן אנרגיה מוכר גלובלית המפורסם על ידי האגודה האמריקאית למהנדסי חימום, קירור ומזוג אוויר (ASHRAE).

ASHRAE 90.1, מדוע זה צריך לעניין אותך

תקן ASHRAE 90.1 משמש כנקודת התייחסות (מדד) לתקני אנרגיה בבנייה ברחבי ארצות הברית ומשמש כמסלול ציות במסגרת ה-IECC, המתווה דרישות מינימום לביצועים יעילים באנרגיה של רכיבי מבנים מסחריים, כולל מעטפת הבניין, מערכות מיזוג אוויר (HVAC), מערכות חימום מים ומערכות תאורה.

תקן ASHRAE 90.1 מגדיר צפיפות הספק תאורה מרבית מותרת ודרישות מינימום לבקרת תאורה, כולל שימוש בחיישני תפוסה באזורים ספציפיים.

Title 24, חלק 6 של קוד תקני הבנייה של קליפורניה, הידוע רשמית כתקני יעילות אנרגטית בבנייה למבני מגורים ושאינם למגורים, מנוהל על ידי נציבות האנרגיה של קליפורניה (CEC) ומתעדכן תקופתית כדי לשקף טכנולוגיות ושיטות חדשות ליעילות אנרגטית.

Title 24, מדוע זה צריך לעניין אותך

תקן Title 24 ידוע בדרישות המחמירות שלו, הנחשבות לרוב למחמירות יותר מאלו שנמצאות בתקני אנרגיה רבים אחרים ברחבי ארצות הברית. Title 24 מחייב תקני ביצועים אנרגטיים קפדניים לכל היבטי הבנייה, הכוללים חימום, אוורור, מיזוג אוויר (HVAC), חימום מים ותאורה.

תקן Title 24 מחייב התקנת חיישני תפוסה המתאימים את התאורה בהתבסס על תפוסת החדר באזורים ספציפיים של מבנים מסחריים כדי להבטיח שאנרגיה לא תתבזבז.

אימוץ תקני אנרגיה לפי מדינה

התרחבו כדי לצפות בטבלה המפורטת ↓

מדינהתקן מסחרי נוכחיקטגוריית יעילות תקן מסחרי
אלבמה90.1-201390.1-2013
אלסקהאין תקן כלל-מדינתיאין תקן כלל-מדינתי
אריזונהשלטון מקומי (Home rule)<90.1-2007
ארקנסו2009 IECC ו-90.1-200790.1-2007
קליפורניהתקני יעילות אנרגטית לבנייה 202290.1-2019
קולורדושלטון מקומי (Home rule)אין תקן כלל-מדינתי
קונטיקט2021 IECC ו-90.1-201990.1-2019
דלאוור2018 IECC ו-90.1-201690.1-2013
מחוז קולומביה90.1-2013^90.1-2019
פלורידה2021 IECC ו-90.1-2019^90.1-2016
ג'ורג'יה2015 IECC ו-90.1-2013^90.1-2013
הוואישלטון מקומי (Home rule)90.1-2013
איידהו2018 IECC ו-90.1-201690.1-2013
אילינוי2021 IECC ו-90.1-201990.1-2019
אינדיאנה90.1-200790.1-2007
איווה2012 IECC ו-90.1-201090.1-2007
קנזסשלטון מקומי (Home rule)אין תקן כלל-מדינתי
קנטקי2012 IECC ו-90.1-201090.1-2007
לואיזיאנה2021 IECC ו-90.1-2019^90.1-2016
מיין2015 IECC ו-90.1-201390.1-2013
מרילנד2021 IECC ו-90.1-2019^90.1-2019
מסצ'וסטס2018 IECC ו-90.1-2016^90.1-2019
מישיגן2015 IECC ו-90.1-2013^90.1-2013
מינסוטה90.1-2019^90.1-2019
מיסיסיפיאין תקן כלל-מדינתיאין תקן כלל-מדינתי
מיזורישלטון מקומי (Home rule)אין תקן כלל-מדינתי
מונטנה2021 IECC ו-90.1-201990.1-2019
נברסקה2018 IECC ו-90.1-201690.1-2013
נבאדה2018 IECC ו-90.1-201690.1-2013
ניו המפשייר2018 IECC ו-90.1-2016^90.1-2013
ניו ג'רזי90.1-201990.1-2019
ניו מקסיקו2021 IECC ו-90.1-2019^90.1-2019
ניו יורק2018 IECC ו-90.1-2016^90.1-2016
צפון קרוליינה2015 IECC ו-90.1-2013^90.1-2010
צפון דקוטהשלטון מקומי (Home rule)אין תקן כלל-מדינתי
אוהיו2021 IECC ו-90.1-2019^90.1-2016
אוקלהומה2006 IECC and 90.1-2004<90.1-2007
Oregon90.1-201990.1-2019
Pennsylvania2018 IECC ו-90.1-201690.1-2013
Rhode Island2018 IECC ו-90.1-2016^90.1-2013
South Carolina2009 IECC ו-90.1-200790.1-2007
South Dakotaשלטון מקומי (Home rule)אין תקן כלל-מדינתי
Tennessee2021 IECC and 90.1-201390.1-2007
Texas2015 IECC ו-90.1-201390.1-2013
Utah2021 IECC ו-90.1-2019^90.1-2019
Vermont2021 IECC ו-90.1-2019^90.1-2019
Virginia2021 IECC ו-90.1-2019^90.1-2019
Washington2018 Washington State Energy Code90.1-2019
Tennessee2012 IECC ו-90.1-201090.1-2007
Texas2015 IECC ו-90.1-201390.1-2013
Utah2021 IECC ו-90.1-2019^90.1-2019
Vermont2018 IECC ו-90.1-2016^90.1-2019
Virginia2021 IECC ו-90.1-2019^90.1-2019
Washington2018 Washington State Energy Code90.1-2019
West Virginia90.1-201390.1-2013
Wisconsin2015 IECC ו-90.1-2013^90.1-2010
Wyomingשלטון מקומי (Home rule)אין תקן כלל-מדינתי
  • ^ When an amendment impacting energy efficiency can be quantified using DOE Prototype Building Models, they were captured in the analysis.
  • For states adopting both IECC and 90.1, the IECC code is usually analyzed as the state current code in this study except for states with extensive amendments to the IECC.

Sensor Solutions

Find out how Rayzeek can solve your energy saving challenges.

הצג את כל ההצעות

Design Guide Key Concepts for Classrooms

Designing an energy-efficient lighting control solution for classrooms involves strategic placement of occupancy sensors to ensure comprehensive coverage of the space.

Designing an energy-efficient classroom with occupancy sensors involves careful planning and strategic placement of sensors:

  • Wall Occupancy/Vacancy Sensors: Install these sensors near the main entrance of the classroom. These sensors can detect when someone enters or leaves the room, and can automatically turn the lights on or off accordingly. They can also be manually controlled to turn all lights on or off.
  • Ceiling Occupancy Sensors: These sensors should be installed in the center of the classroom, ensuring they have a clear view of the entire room to cover key areas such as the teacher’s desk, student desks, and any separate learning areas. They can detect any movement in the room, including minor movements such as students writing at their desks. When no movement is detected for a set period, the lights will automatically turn off.
  • Additional Sensors for Specific Areas: If the classroom has specific areas such as a reading corner or a lab area, additional sensors may be needed. These sensors can control the lighting in these specific areas based on occupancy, ensuring that lights are not left on unnecessarily.
  • Sensor Placement Considerations: Avoid placing sensors near air vents or other sources of movement that could trigger the sensor falsely. Also, ensure the sensors’ view is not obstructed by tall furniture or fixtures.
  • Consideration of Natural Light: If the classroom has windows, the sensors should be programmed to consider the natural light coming into the room. This can help to further reduce energy consumption by utilizing natural light whenever possible.
  • Integration with Manual Control: All occupancy/vacancy sensors should be integrated with manual controls. This allows teachers to manually turn off the lights during activities like video presentations, even if the room is occupied.

Wall Sensor Switches

RZ020/021 Motion Sensor Switches

  • 2-wire, 3-wire, 4-wires wiring options
  • Occupancy, Vacancy, Manual ON/OFF
  • Adjustive time delay and ambient light control

Multi-Location Wireless Wall Sensors

RZ020A/021A + RZ022W Kits

  • Hardwired RZ021A/022A occupancy sensor switch
  • Wireless companion switch (RZ022W) for multi-location control

Ceiling Occupancy Sensors

RZ036

  • Hardwired occupancy sensors
  • Auto ON, auto OFF
  • Line voltage and Low voltage available

Core features included:

  • Integrated manual ON/OFF control for all lighting
  • Vacancy sensors (Manual ON only): Lights must be turned on manually only
  • Adjustable time-delay, lighting is automatically turned full OFF after 15mins
  • Additional: multi-location wireless kits to expand the control range without re-wring
  • Additional: multiple wiring options available for both new constructions and retrofit projects.

Meets the Mandatory Provisions

IECC – 2011

C405.2.1 Occupant sensor controls

Occupant sensor controls shall be installed to control lights in the space.

C405.2.1.1 Occupant sensor control functions

  • Manual on or partial on to no more than 50% power.
  • Full off within 20 minutes after all occupants have left the space
  • A manual control to turn off the lights.

ASHRAE 90.1 – 2022

9.4.1.1 a Local control

There shall be one or more manual lighting control device that provides ON and OFF control
of all lighting in the space.

9.4.1.1 b Restricted to manual ON

None of the lighting shall be automatically turned on

9.4.1.1 c Restricted to partial automatic ON

No more than 50% of the lighting power for the general lighting shall be allowed to be automatically turned on

** NOTE: At least one 9.4.1.1 b or 9.4.1.1 c shall be implemented.

For classrooms except shop classrooms (all other classrooms/lecture halls/training rooms):

9.4.1.1 h Automatic full OFF control

All lighting in the space shall be automatically shut off within 20 minutes of all occupants leaving the space

Title 24 – 2022

130.1 (a) Manual area controls.

Each area enclosed by ceiling-height partitions shall provide lighting controls that allow the lighting in that area to be manually turned on and off.

130.1 (c) Shut-OFF Controls.

Lighting shall be controlled with occupant sensing controls to automatically shut OFF all of the lighting in 20 minutes or less after the control zone is unoccupied that shall function either as:

  • A. Occupant sensing controls (if 130.1(b) not required to have multi-level lighting controls); or
  • B. Partial-ON occupant sensing controls, or
  • C. Vacancy sensing controls, where all lighting responds to a manual ON input only

Let us hear you.

Let Rayzeek help design and deliver a bespoke energy-saving lighting solution for you.

    Hebrew