Classrooms

Discover the energy-saving potential of classrooms with Rayzeek’s occupancy sensor design guide. Learn how to meet energy code requirements while creating a more efficient learning environment.

Transforming Classrooms into Energy-Efficient Learning Spaces

Classrooms are dynamic spaces that serve as the foundation for learning and development. They are often filled with a variety of lighting fixtures, from overhead lights to task lighting, all of which contribute to a significant amount of energy consumption. The lighting in these spaces is typically left on for extended periods, even when the room is unoccupied, leading to unnecessary energy waste.

In a typical classroom, the lighting needs can vary greatly depending on the time of day, the activities taking place, and the number of occupants. This variability makes it challenging to manage lighting effectively and efficiently. As a result, there is a pressing need for solutions that can automatically control lighting based on occupancy, thereby reducing unnecessary energy consumption.

The need for energy conservation in classrooms is clear, and one of the most effective solutions is the use of occupancy sensors. These devices can automatically turn off lights when a room is vacant, significantly reducing energy consumption. With Rayzeek’s range of occupancy sensors, classrooms can become more energy-efficient, meeting the requirements of energy codes while also reducing operational costs.

Memenuhi Kode Energi

International Energy Conservation Code (IECC) adalah model kode yang dikembangkan oleh International Code Council (ICC) untuk menetapkan persyaratan desain dan konstruksi minimum untuk efisiensi energi pada bangunan. IECC diperbarui setiap tiga tahun untuk menggabungkan praktik dan teknologi konservasi energi terbaru.

IECC, Mengapa Anda Harus Peduli

IECC diadopsi secara luas oleh negara bagian dan kotamadya di seluruh Amerika Serikat. IECC mencakup berbagai aspek penggunaan energi, termasuk selubung bangunan (dinding, atap, dan jendela), sistem pemanas dan pendingin, serta sistem pencahayaan.

IECC mewajibkan kontrol pencahayaan khusus, seperti sensor hunian, untuk meminimalkan pemborosan energi di area yang tidak terisi di berbagai lokasi.

Standar ANSI/ASHRAE/IES 90.1, Standar Energi untuk Tapak dan Bangunan Kecuali Bangunan Hunian Rendah, adalah standar energi yang diakui secara luas yang diterbitkan oleh American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).

ASHRAE 90.1, Mengapa Anda Harus Peduli

ASHRAE 90.1 digunakan sebagai tolok ukur untuk kode energi bangunan di seluruh Amerika Serikat dan berfungsi sebagai jalur kepatuhan dalam IECC yang menguraikan persyaratan minimum untuk kinerja efisiensi energi komponen bangunan komersial termasuk selubung bangunan, sistem HVAC, sistem pemanas air, dan sistem pencahayaan.

Standar ASHRAE 90.1 menentukan kepadatan daya pencahayaan maksimum yang diizinkan dan persyaratan kontrol pencahayaan minimum, termasuk penggunaan sensor hunian di area tertentu.

Title 24, bagian 6 dari Kode Standar Bangunan California, yang secara resmi dikenal sebagai Standar Efisiensi Energi Bangunan untuk Bangunan Hunian dan Non-hunian, Title 24 dikelola oleh California Energy Commission dan diperbarui secara berkala untuk mencerminkan teknologi dan metode efisiensi energi baru.

Title 24, Mengapa Anda Harus Peduli

Title 24 dikenal dengan persyaratannya yang ketat, yang sering kali dianggap lebih ketat daripada yang ditemukan di banyak kode energi lainnya di seluruh Amerika Serikat. Title 24 mewajibkan standar kinerja energi yang ketat untuk semua aspek konstruksi bangunan, yang mencakup pemanas, ventilasi, pengondisian udara (HVAC), pemanas air, dan pencahayaan.

Title 24 mewajibkan pemasangan sensor hunian yang menyesuaikan pencahayaan berdasarkan tingkat hunian ruangan di area tertentu di bangunan komersial untuk memastikan bahwa energi tidak terbuang sia-sia.

Penerapan Kode Energi Berdasarkan Negara Bagian

Expand to see the detailed table ↓

StateCurrent Commercial CodeCommercial Code Efficiency Category
Alabama90.1-201390.1-2013
AlaskaNone statewideNo statewide code
ArizonaHome rule<90.1-2007
Arkansas2009 IECC and 90.1-200790.1-2007
California2022 Building Energy Efficiency Standards90.1-2019
ColoradoHome ruleNo statewide code
Connecticut2021 IECC and 90.1-201990.1-2019
Delaware2018 IECC and 90.1-201690.1-2013
District of Columbia90.1-2013^90.1-2019
Florida2021 IECC and 90.1-2019^90.1-2016
Georgia2015 IECC and 90.1-2013^90.1-2013
HawaiiHome rule90.1-2013
Idaho2018 IECC and 90.1-201690.1-2013
Illinois2021 IECC and 90.1-201990.1-2019
Indiana90.1-200790.1-2007
Iowa2012 IECC and 90.1-201090.1-2007
KansasHome ruleNo statewide code
Kentucky2012 IECC and 90.1-201090.1-2007
Louisiana2021 IECC and 90.1-2019^90.1-2016
Maine2015 IECC and 90.1-201390.1-2013
Maryland2021 IECC and 90.1-2019^90.1-2019
Massachusetts2018 IECC and 90.1-2016^90.1-2019
Michigan2015 IECC and 90.1-2013^90.1-2013
Minnesota90.1-2019^90.1-2019
MississippiNone statewideNo statewide code
MissouriHome ruleNo statewide code
Montana2021 IECC and 90.1-201990.1-2019
Nebraska2018 IECC and 90.1-201690.1-2013
Nevada2018 IECC and 90.1-201690.1-2013
New Hampshire2018 IECC and 90.1-2016^90.1-2013
New Jersey90.1-201990.1-2019
New Mexico2021 IECC and 90.1-2019^90.1-2019
New York2018 IECC and 90.1-2016^90.1-2016
North Carolina2015 IECC and 90.1-2013^90.1-2010
North DakotaHome ruleNo statewide code
Ohio2021 IECC and 90.1-2019^90.1-2016
Oklahoma2006 IECC and 90.1-2004<90.1-2007
Oregon90.1-201990.1-2019
Pennsylvania2018 IECC and 90.1-201690.1-2013
Rhode Island2018 IECC and 90.1-2016^90.1-2013
South Carolina2009 IECC and 90.1-200790.1-2007
South DakotaHome ruleNo statewide code
Tennessee2021 IECC and 90.1-201390.1-2007
Texas2015 IECC and 90.1-201390.1-2013
Utah2021 IECC and 90.1-2019^90.1-2019
Vermont2021 IECC and 90.1-2019^90.1-2019
Virginia2021 IECC and 90.1-2019^90.1-2019
Washington2018 Washington State Energy Code90.1-2019
Tennessee2012 IECC and 90.1-201090.1-2007
Texas2015 IECC and 90.1-201390.1-2013
Utah2021 IECC and 90.1-2019^90.1-2019
Vermont2018 IECC and 90.1-2016^90.1-2019
Virginia2021 IECC and 90.1-2019^90.1-2019
Washington2018 Washington State Energy Code90.1-2019
West Virginia90.1-201390.1-2013
Wisconsin2015 IECC and 90.1-2013^90.1-2010
WyomingHome ruleNo statewide code
  • ^ When an amendment impacting energy efficiency can be quantified using DOE Prototype Building Models, they were captured in the analysis.
  • For states adopting both IECC and 90.1, the IECC code is usually analyzed as the state current code in this study except for states with extensive amendments to the IECC.

Sensor Solutions

Find out how Rayzeek can solve your energy saving challenges.

View All Offerings

Design Guide Key Concepts for Classrooms

Designing an energy-efficient lighting control solution for classrooms involves strategic placement of occupancy sensors to ensure comprehensive coverage of the space.

Designing an energy-efficient classroom with occupancy sensors involves careful planning and strategic placement of sensors:

  • Wall Occupancy/Vacancy Sensors: Install these sensors near the main entrance of the classroom. These sensors can detect when someone enters or leaves the room, and can automatically turn the lights on or off accordingly. They can also be manually controlled to turn all lights on or off.
  • Ceiling Occupancy Sensors: These sensors should be installed in the center of the classroom, ensuring they have a clear view of the entire room to cover key areas such as the teacher’s desk, student desks, and any separate learning areas. They can detect any movement in the room, including minor movements such as students writing at their desks. When no movement is detected for a set period, the lights will automatically turn off.
  • Additional Sensors for Specific Areas: If the classroom has specific areas such as a reading corner or a lab area, additional sensors may be needed. These sensors can control the lighting in these specific areas based on occupancy, ensuring that lights are not left on unnecessarily.
  • Sensor Placement Considerations: Avoid placing sensors near air vents or other sources of movement that could trigger the sensor falsely. Also, ensure the sensors’ view is not obstructed by tall furniture or fixtures.
  • Consideration of Natural Light: If the classroom has windows, the sensors should be programmed to consider the natural light coming into the room. This can help to further reduce energy consumption by utilizing natural light whenever possible.
  • Integration with Manual Control: All occupancy/vacancy sensors should be integrated with manual controls. This allows teachers to manually turn off the lights during activities like video presentations, even if the room is occupied.

Wall Sensor Switches

RZ020/021 Motion Sensor Switches

  • 2-wire, 3-wire, 4-wires wiring options
  • Occupancy, Vacancy, Manual ON/OFF
  • Adjustive time delay and ambient light control

Multi-Location Wireless Wall Sensors

RZ020A/021A + RZ022W Kits

  • Hardwired RZ021A/022A occupancy sensor switch
  • Wireless companion switch (RZ022W) for multi-location control

Ceiling Occupancy Sensors

RZ036

  • Hardwired occupancy sensors
  • Auto ON, auto OFF
  • Line voltage and Low voltage available

Core features included:

  • Integrated manual ON/OFF control for all lighting
  • Vacancy sensors (Manual ON only): Lights must be turned on manually only
  • Adjustable time-delay, lighting is automatically turned full OFF after 15mins
  • Additional: multi-location wireless kits to expand the control range without re-wring
  • Additional: multiple wiring options available for both new constructions and retrofit projects.

Meets the Mandatory Provisions

IECC – 2011

C405.2.1 Occupant sensor controls

Occupant sensor controls shall be installed to control lights in the space.

C405.2.1.1 Occupant sensor control functions

  • Manual on or partial on to no more than 50% power.
  • Full off within 20 minutes after all occupants have left the space
  • A manual control to turn off the lights.

ASHRAE 90.1 – 2022

9.4.1.1 a Local control

There shall be one or more manual lighting control device that provides ON and OFF control
of all lighting in the space.

9.4.1.1 b Restricted to manual ON

None of the lighting shall be automatically turned on

9.4.1.1 c Restricted to partial automatic ON

No more than 50% of the lighting power for the general lighting shall be allowed to be automatically turned on

** NOTE: At least one 9.4.1.1 b or 9.4.1.1 c shall be implemented.

For classrooms except shop classrooms (all other classrooms/lecture halls/training rooms):

9.4.1.1 h Automatic full OFF control

All lighting in the space shall be automatically shut off within 20 minutes of all occupants leaving the space

Title 24 – 2022

130.1 (a) Manual area controls.

Each area enclosed by ceiling-height partitions shall provide lighting controls that allow the lighting in that area to be manually turned on and off.

130.1 (c) Shut-OFF Controls.

Lighting shall be controlled with occupant sensing controls to automatically shut OFF all of the lighting in 20 minutes or less after the control zone is unoccupied that shall function either as:

  • A. Occupant sensing controls (if 130.1(b) not required to have multi-level lighting controls); or
  • B. Partial-ON occupant sensing controls, or
  • C. Vacancy sensing controls, where all lighting responds to a manual ON input only

Let us hear you.

Let Rayzeek help design and deliver a bespoke energy-saving lighting solution for you.