Discover energy-saving solutions for private offices with Rayzeek’s occupancy sensor design guide. Learn how to meet energy code requirements while optimizing lighting control for efficiency and comfort.

Optimize Energy Use in Private Offices with Smart Lighting Control

Private offices are individual workspaces, often enclosed by walls and a door, providing a quiet and focused environment for tasks that require concentration. These spaces are typically equipped with overhead lighting and task lighting, which can contribute significantly to the overall energy consumption of a commercial building.

Despite their benefits, private offices often face the issue of lights being left on when the space is unoccupied, leading to unnecessary energy waste. This is particularly problematic given that private offices are not continuously occupied throughout the day, with occupants often leaving for meetings, breaks, or other tasks.

To address this issue, occupancy sensors offer an effective solution. These devices can automatically turn off lights when the office is vacant, significantly reducing energy consumption. By integrating occupancy sensors into private offices, businesses can not only meet energy code requirements but also achieve substantial energy savings and improve their sustainability efforts.

Splnění energetických předpisů

International Energy Conservation Code (IECC) je vzorový předpis vyvinutý organizací International Code Council (ICC) za účelem stanovení minimálních požadavků na návrh a konstrukci z hlediska energetické účinnosti budov. Předpis IECC je aktualizován každé tři roky, aby zohledňoval nejnovější postupy a technologie v oblasti úspory energie.

IECC a proč by vás měl zajímat

Předpis IECC je široce přijímán jednotlivými státy i samosprávami po celých Spojených státech. IECC pokrývá různé oblasti využití energie, včetně obálky budovy (stěny, střechy a okna), systémů vytápění a chlazení a osvětlovacích soustav.

Předpis IECC vyžaduje specifické prvky řízení osvětlení, jako jsou senzory přítomnosti, které minimalizují plytvání energií v neobsazených prostorech v různých oblastech.

Standard ANSI/ASHRAE/IES 90.1, Energy Standard for Sites and Buildings Except Low-Rise Residential Buildings, je široce uznávaný energetický standard vydávaný Americkou společností inženýrů pro vytápění, chlazení a klimatizaci (ASHRAE).

ASHRAE 90.1 a proč by vás měl zajímat

Standard ASHRAE 90.1 se používá jako srovnávací základna pro energetické předpisy budov po celých Spojených státech a slouží jako cesta k prokázání shody v rámci IECC. Definujeme minimální požadavky na energetickou účinnost prvků komerčních budov, včetně obálek budov, systémů HVAC, systémů ohřevu vody a osvětlovacích soustav.

Standard ASHRAE 90.1 stanovuje maximální povolenou hustotu příkonu osvětlení a minimální požadavky na řízení osvětlení, včetně použití senzorů přítomnosti v konkrétních prostorech.

Title 24, část 6 předpisu California Building Standards Code, oficiálně známá jako Building Energy Efficiency Standards for Residential and Nonresidential Buildings, je spravována orgánem California Energy Commission a pravidelně aktualizována s ohledem na nové technologie a metody energetické účinnosti.

Title 24 a proč by vás měl zajímat

Title 24 je známý svými přísnými požadavky, které jsou často považovány za náročnější než požadavky obsažené v mnoha jiných energetických předpisech napříč Spojenými státy. Title 24 vyžaduje přísné standardy energetické náročnosti pro všechny aspekty výstavby budov, což zahrnuje vytápění, větrání, klimatizaci (HVAC), ohřev vody a osvětlení.

Title 24 vyžaduje instalaci senzorů přítomnosti, které upravují osvětlení na základě obsazenosti místností v konkrétních prostorech komerčních budov, aby nedocházelo k plytvání energií.

Míra přijetí energetických předpisů podle států

Rozbalte pro zobrazení podrobné tabulky ↓

StátPlatný komerční předpisKategorie účinnosti komerčního předpisu
Alabama90.1-201390.1-2013
AljaškaŽádný celostátníŽádný celostátní předpis
ArizonaMístní samospráva (Home rule)<90.1-2007
Arkansas2009 IECC a 90.1-200790.1-2007
KalifornieNormy energetické účinnosti budov z roku 202290.1-2019
ColoradoMístní samospráva (Home rule)Žádný celostátní předpis
Connecticut2021 IECC a 90.1-201990.1-2019
Delaware2018 IECC a 90.1-201690.1-2013
District of Columbia90.1-2013^90.1-2019
Florida2021 IECC a 90.1-2019^90.1-2016
Georgia2015 IECC a 90.1-2013^90.1-2013
HavajMístní samospráva (Home rule)90.1-2013
Idaho2018 IECC a 90.1-201690.1-2013
Illinois2021 IECC a 90.1-201990.1-2019
Indiana90.1-200790.1-2007
Iowa2012 IECC and 90.1-201090.1-2007
KansasMístní samospráva (Home rule)Žádný celostátní předpis
Kentucky2012 IECC and 90.1-201090.1-2007
Louisiana2021 IECC a 90.1-2019^90.1-2016
Maine2015 IECC and 90.1-201390.1-2013
Maryland2021 IECC a 90.1-2019^90.1-2019
Massachusetts2018 IECC and 90.1-2016^90.1-2019
Michigan2015 IECC a 90.1-2013^90.1-2013
Minnesota90.1-2019^90.1-2019
MississippiŽádný celostátníŽádný celostátní předpis
MissouriMístní samospráva (Home rule)Žádný celostátní předpis
Montana2021 IECC a 90.1-201990.1-2019
Nebraska2018 IECC a 90.1-201690.1-2013
Nevada2018 IECC a 90.1-201690.1-2013
New Hampshire2018 IECC and 90.1-2016^90.1-2013
New Jersey90.1-201990.1-2019
Nové Mexiko2021 IECC a 90.1-2019^90.1-2019
New York2018 IECC and 90.1-2016^90.1-2016
Severní Karolína2015 IECC a 90.1-2013^90.1-2010
Severní DakotaMístní samospráva (Home rule)Žádný celostátní předpis
Ohio2021 IECC a 90.1-2019^90.1-2016
Oklahoma2006 IECC a 90.1-2004<90.1-2007
Oregon90.1-201990.1-2019
Pensylvánie2018 IECC a 90.1-201690.1-2013
Rhode Island2018 IECC and 90.1-2016^90.1-2013
Jižní Karolína2009 IECC a 90.1-200790.1-2007
Jižní DakotaMístní samospráva (Home rule)Žádný celostátní předpis
Tennessee2021 IECC a 90.1-201390.1-2007
Texas2015 IECC and 90.1-201390.1-2013
Utah2021 IECC a 90.1-2019^90.1-2019
Vermont2021 IECC a 90.1-2019^90.1-2019
Virginie2021 IECC a 90.1-2019^90.1-2019
WashingtonEnergetický kodex státu Washington z roku 201890.1-2019
Tennessee2012 IECC and 90.1-201090.1-2007
Texas2015 IECC and 90.1-201390.1-2013
Utah2021 IECC a 90.1-2019^90.1-2019
Vermont2018 IECC and 90.1-2016^90.1-2019
Virginie2021 IECC a 90.1-2019^90.1-2019
WashingtonEnergetický kodex státu Washington z roku 201890.1-2019
Západní Virginie90.1-201390.1-2013
Wisconsin2015 IECC a 90.1-2013^90.1-2010
WyomingMístní samospráva (Home rule)Žádný celostátní předpis
  • ^ Pokud lze změnu s dopadem na energetickou účinnost kvantifikovat pomocí prototypových modelů budov DOE, byla do analýzy zahrnuta.
  • U států přijímajících normy IECC i 90.1 je v této studii norma IECC obvykle analyzována jako aktuální státní kodex, s výjimkou států s rozsáhlými změnami normy IECC.

Senzorová řešení

Zjistěte, jak může Rayzeek vyřešit vaše výzvy v oblasti úspory energie.

Zobrazit všechny nabídky

Klíčové koncepty návrhové příručky pro samostatné kanceláře

Návrh energeticky úsporného řešení řízení osvětlení pro samostatné kanceláře vyžaduje strategické umístění snímačů přítomnosti, které zajistí kompletní pokrytí daného prostoru.

  • Umístění snímače: Position the sensor to cover the main areas of activity, such as the desk and the entrance. The sensor should have a clear line of sight to these areas, unobstructed by furniture or other objects. For private offices, wall-mounted sensors or ceiling-mounted sensors can be effective, depending on the room layout and furniture arrangement.
  • Coverage of Minor Movements: Ensure that the desk area falls within the minor motion coverage area of the sensor. This means that even small movements, such as typing or turning pages in a book, should be detected by the sensor to prevent the lights from turning off while the space is occupied.
  • Avoidance of Obstructions: If using wall-mounted sensors, ensure that tall furniture like bookcases does not block the sensor’s view of the room. Similarly, the sensor’s view should not be blocked by the door when it’s open.
  • Entrance Coverage: The sensor should have a clear view of the entrance to detect occupancy as soon as someone enters the room. If the door blocks the sensor’s view when open, consider using an additional sensor to cover the entrance.
  • Avoidance of Interference: Sensors should not be mounted close to air vents, as the vibration and air flow can reduce their effectiveness.
  • Manual Control: Incorporate manual controls for occupants to turn the lights ON/OFF as needed. These controls should be conveniently located, often near the entrance.

Wall Sensor Switches

RZ020/021 Motion Sensor Switches

  • 2-wire, 3-wire, 4-wires wiring options
  • Occupancy, Vacancy, Manual ON/OFF
  • Adjustive time delay and ambient light control

Multi-Location Wireless Wall Sensors

RZ020A/021A + RZ022W Kits

  • Hardwired RZ021A/022A occupancy sensor switch
  • Wireless companion switch (RZ022W) for multi-location control

Ceiling Occupancy Sensors

RZ036

  • Hardwired occupancy sensors
  • Auto ON, auto OFF
  • Line voltage and Low voltage available

Core features included:

  • Integrated manual ON/OFF control for all lighting
  • Vacancy sensors (Manual ON only): Lights must be turned on manually only
  • Adjustable time-delay, lighting is automatically turned full OFF after 15mins
  • Additional: multi-location wireless kits to expand the control range without re-wring
  • Additional: multiple wiring options available for both new constructions and retrofit projects.

Meets the Mandatory Provisions

IECC – 2011

C405.2.1 Occupant sensor controls

Occupant sensor controls shall be installed to control lights in the space.

For private/small offices <300 sq. ft:

C405.2.1.1 Occupant sensor control functions

  • Manual on or partial on to no more than 50% power.
  • Full off within 20 minutes after all occupants have left the space
  • A manual control to turn off the lights.

ASHRAE 90.1 – 2022

For private/small/enclosed offices <300 sq. ft:

9.4.1.1 a Local control

There shall be one or more manual lighting control device that provides ON and OFF control
of all lighting in the space.

9.4.1.1 b Restricted to manual ON

None of the lighting shall be automatically turned on

9.4.1.1 c Restricted to partial automatic ON

No more than 50% of the lighting power for the general lighting shall be allowed to be automatically turned on

** NOTE: At least one 9.4.1.1 b or 9.4.1.1 c shall be implemented.

9.4.1.1 H Automatic full OFF control

All lighting in the space shall be automatically shut off within 20 minutes of all occupants leaving the space

Title 24 – 2022

For private/small offices <250 sq. ft:

130.1 (a) Manual area controls.

Each area enclosed by ceiling-height partitions shall provide lighting controls that allow the lighting in that area to be manually turned on and off.

130.1 (c) Shut-OFF Controls.

Lighting shall be controlled with occupant sensing controls to automatically shut OFF all of the lighting in 20 minutes or less after the control zone is unoccupied that shall function either as:

  • A. Occupant sensing controls (if 130.1(b) not required to have multi-level lighting controls); or
  • B. Partial-ON occupant sensing controls, or
  • C. Vacancy sensing controls, where all lighting responds to a manual ON input only