Private Offices
Discover energy-saving solutions for private offices with Rayzeek’s occupancy sensor design guide. Learn how to meet energy code requirements while optimizing lighting control for efficiency and comfort.

Optimize Energy Use in Private Offices with Smart Lighting Control
Private offices are individual workspaces, often enclosed by walls and a door, providing a quiet and focused environment for tasks that require concentration. These spaces are typically equipped with overhead lighting and task lighting, which can contribute significantly to the overall energy consumption of a commercial building.
Despite their benefits, private offices often face the issue of lights being left on when the space is unoccupied, leading to unnecessary energy waste. This is particularly problematic given that private offices are not continuously occupied throughout the day, with occupants often leaving for meetings, breaks, or other tasks.
To address this issue, occupancy sensors offer an effective solution. These devices can automatically turn off lights when the office is vacant, significantly reducing energy consumption. By integrating occupancy sensors into private offices, businesses can not only meet energy code requirements but also achieve substantial energy savings and improve their sustainability efforts.
Соответствие энергетическим стандартам

Международный код по энергосбережению (IECC) представляет собой типовой свод правил, разработанный Международным советом по строительным нормам и правилам (ICC) для установления минимальных требований к проектированию и строительству с точки зрения энергоэффективности зданий. IECC обновляется каждые три года, чтобы включать новейшие практики и технологии в области энергосбережения.
Почему IECC важен для вас
IECC широко применяется штатами и муниципалитетами по всей территории США. IECC охватывает различные аспекты энергопотребления, включая ограждающие конструкции здания (стены, крыши и окна), системы отопления и охлаждения, а также системы освещения.
IECC предписывает обязательное использование специальных средств управления освещением, таких как датчики присутствия, чтобы минимизировать потерю энергии в незанятых помещениях различных зон.

Стандарт ANSI/ASHRAE/IES 90.1 «Стандарт энергоэффективности зданий и сооружений, за исключением малоэтажных жилых зданий» — это широко признанный стандарт энергоэффективности, публикуемый Американским обществом инженеров по отоплению, охлаждению и кондиционированию воздуха (ASHRAE).
Почему ASHRAE 90.1 важен для вас
ASHRAE 90.1 используется в качестве ориентира для энергетических строительных норм по всей территории США и служит вариантом подтверждения соответствия в рамках IECC, определяя минимальные требования к энергоэффективности компонентов коммерческих зданий, включая ограждающие конструкции, системы HVAC, системы горячего водоснабжения и системы освещения.
Стандарт ASHRAE 90.1 устанавливает максимально допустимую удельную мощность освещения и минимальные требования к управлению освещением, включая использование датчиков присутствия в определенных зонах.

Раздел 24, часть 6 Строительных стандартов штата Калифорния, официально известный как «Стандарты энергоэффективности жилых и нежилых зданий» (Title 24), находится в ведении Энергетической комиссии штата Калифорния и периодически обновляется с учетом новых технологий и методов энергоэффективности.
Почему Title 24 важен для вас
Стандарт Title 24 известен своими строгими требованиями, которые часто считаются более жесткими, чем нормы других энергетических сводов правил в США. Title 24 устанавливает строгие стандарты энергоэффективности для всех аспектов строительства зданий, включая отопление, вентиляцию, кондиционирование воздуха (HVAC), горячее водоснабжение и освещение.
Title 24 требует установки датчиков присутствия, регулирующих освещение в зависимости от наличия людей в определенных помещениях коммерческих зданий, что предотвращает нерациональный расход энергии.
Применение энергетических стандартов по штатам

Разверните, чтобы просмотреть подробную таблицу ↓
| Штат | Действующий коммерческий строительный код | Категория эффективности коммерческого строительного кода |
|---|---|---|
| Алабама | 90.1-2013 | 90.1-2013 |
| Аляска | Отсутствует на уровне штата | Нет единого строительного кода на уровне штата |
| Аризона | Местное самоуправление | <90.1-2007 |
| Арканзас | 2009 IECC и 90.1-2007 | 90.1-2007 |
| Калифорния | 2022 Стандарты энергоэффективности зданий | 90.1-2019 |
| Колорадо | Местное самоуправление | Нет единого строительного кода на уровне штата |
| Коннектикут | 2021 IECC и 90.1-2019 | 90.1-2019 |
| Делавэр | 2018 IECC и 90.1-2016 | 90.1-2013 |
| Округ Колумбия | 90.1-2013^ | 90.1-2019 |
| Флорида | 2021 IECC и 90.1-2019^ | 90.1-2016 |
| Джорджия | 2015 IECC и 90.1-2013^ | 90.1-2013 |
| Гавайи | Местное самоуправление | 90.1-2013 |
| Айдахо | 2018 IECC и 90.1-2016 | 90.1-2013 |
| Иллинойс | 2021 IECC и 90.1-2019 | 90.1-2019 |
| Индиана | 90.1-2007 | 90.1-2007 |
| Айова | 2012 IECC и 90.1-2010 | 90.1-2007 |
| Канзас | Местное самоуправление | Нет единого строительного кода на уровне штата |
| Кентукки | 2012 IECC и 90.1-2010 | 90.1-2007 |
| Луизиана | 2021 IECC и 90.1-2019^ | 90.1-2016 |
| Мэн | 2015 IECC и 90.1-2013 | 90.1-2013 |
| Мэриленд | 2021 IECC и 90.1-2019^ | 90.1-2019 |
| Массачусетс | 2018 IECC и 90.1-2016^ | 90.1-2019 |
| Мичиган | 2015 IECC и 90.1-2013^ | 90.1-2013 |
| Миннесота | 90.1-2019^ | 90.1-2019 |
| Миссисипи | Отсутствует на уровне штата | Нет единого строительного кода на уровне штата |
| Миссури | Местное самоуправление | Нет единого строительного кода на уровне штата |
| Монтана | 2021 IECC и 90.1-2019 | 90.1-2019 |
| Небраска | 2018 IECC и 90.1-2016 | 90.1-2013 |
| Невада | 2018 IECC и 90.1-2016 | 90.1-2013 |
| Нью-Гэмпшир | 2018 IECC и 90.1-2016^ | 90.1-2013 |
| Нью-Джерси | 90.1-2019 | 90.1-2019 |
| Нью-Мексико | 2021 IECC и 90.1-2019^ | 90.1-2019 |
| Нью-Йорк | 2018 IECC и 90.1-2016^ | 90.1-2016 |
| Северная Каролина | 2015 IECC и 90.1-2013^ | 90.1-2010 |
| Северная Дакота | Местное самоуправление | Нет единого строительного кода на уровне штата |
| Огайо | 2021 IECC и 90.1-2019^ | 90.1-2016 |
| Оклахома | 2006 IECC и 90.1-2004 | <90.1-2007 |
| Орегон | 90.1-2019 | 90.1-2019 |
| Пенсильвания | 2018 IECC и 90.1-2016 | 90.1-2013 |
| Род-Айленд | 2018 IECC и 90.1-2016^ | 90.1-2013 |
| Южная Каролина | 2009 IECC и 90.1-2007 | 90.1-2007 |
| Южная Дакота | Местное самоуправление | Нет единого строительного кода на уровне штата |
| Теннесси | 2021 IECC и 90.1-2013 | 90.1-2007 |
| Техас | 2015 IECC и 90.1-2013 | 90.1-2013 |
| Юта | 2021 IECC и 90.1-2019^ | 90.1-2019 |
| Вермонт | 2021 IECC и 90.1-2019^ | 90.1-2019 |
| Виргиния | 2021 IECC и 90.1-2019^ | 90.1-2019 |
| Вашингтон | Энергетический кодекс штата Вашингтон 2018 года | 90.1-2019 |
| Теннесси | 2012 IECC и 90.1-2010 | 90.1-2007 |
| Техас | 2015 IECC и 90.1-2013 | 90.1-2013 |
| Юта | 2021 IECC и 90.1-2019^ | 90.1-2019 |
| Вермонт | 2018 IECC и 90.1-2016^ | 90.1-2019 |
| Виргиния | 2021 IECC и 90.1-2019^ | 90.1-2019 |
| Вашингтон | Энергетический кодекс штата Вашингтон 2018 года | 90.1-2019 |
| Западная Виргиния | 90.1-2013 | 90.1-2013 |
| Висконсин | 2015 IECC и 90.1-2013^ | 90.1-2010 |
| Вайоминг | Местное самоуправление | Нет единого строительного кода на уровне штата |
- ^ Если поправка, влияющая на энергоэффективность, могла быть количественно оценена с использованием типовых моделей зданий Министерства энергетики США (DOE), она учитывалась в анализе.
- Для штатов, принимающих как IECC, так и 90.1, кодекс IECC обычно анализируется в данном исследовании как действующий кодекс штата, за исключением штатов с обширными поправками к IECC.
Основные концепции руководства по проектированию освещения для отдельных кабинетов
Проектирование энергоэффективного решения по управлению освещением для отдельных кабинетов требует стратегического размещения датчиков присутствия для обеспечения полного охвата помещения.

- Размещение датчика: Position the sensor to cover the main areas of activity, such as the desk and the entrance. The sensor should have a clear line of sight to these areas, unobstructed by furniture or other objects. For private offices, wall-mounted sensors or ceiling-mounted sensors can be effective, depending on the room layout and furniture arrangement.
- Coverage of Minor Movements: Ensure that the desk area falls within the minor motion coverage area of the sensor. This means that even small movements, such as typing or turning pages in a book, should be detected by the sensor to prevent the lights from turning off while the space is occupied.
- Avoidance of Obstructions: If using wall-mounted sensors, ensure that tall furniture like bookcases does not block the sensor’s view of the room. Similarly, the sensor’s view should not be blocked by the door when it’s open.
- Зона входа: The sensor should have a clear view of the entrance to detect occupancy as soon as someone enters the room. If the door blocks the sensor’s view when open, consider using an additional sensor to cover the entrance.
- Avoidance of Interference: Sensors should not be mounted close to air vents, as the vibration and air flow can reduce their effectiveness.
- Manual Control: Incorporate manual controls for occupants to turn the lights ON/OFF as needed. These controls should be conveniently located, often near the entrance.
Рекомендуемые продукты и решения
Основные функции:
- Встроенное ручное управление включением/выключением для всего освещения
- Датчики отсутствия (только ручное включение): свет необходимо включать только вручную
- Регулируемая задержка времени, освещение автоматически полностью выключается через 15 минут
- Дополнительно: многоточечные беспроводные комплекты для расширения зоны управления без прокладки новой проводки
- Дополнительно: несколько вариантов подключения как для нового строительства, так и для проектов модернизации.

Соответствует обязательным требованиям
IECC – 2011
C405.2.1 Элементы управления датчиков присутствия
Для управления освещением в помещении должны быть установлены элементы управления датчиков присутствия.
For private/small offices <300 sq. ft:
C405.2.1.1 Функции элементов управления датчиков присутствия
- Ручное включение или частичное включение не более чем на 50% мощности.
- Полное выключение в течение 20 минут после того, как все люди покинут помещение
- Ручной орган управления для выключения света.
ASHRAE 90.1 – 2022
For private/small/enclosed offices <300 sq. ft:
9.4.1.1 a Локальное управление
Должно быть предусмотрено одно или несколько устройств ручного управления освещением, обеспечивающих включение (ON) и выключение (OFF)
всего освещения в помещении.
9.4.1.1 b Ограничение только ручным включением (ON)
Никакая часть освещения не должна включаться автоматически
9.4.1.1 c Ограничение частичным автоматическим включением (ON)
Автоматическое включение допускается не более чем для 50% мощности общего освещения
** NOTE: At least one 9.4.1.1 b or 9.4.1.1 c shall be implemented.
9.4.1.1 H Automatic full OFF control
All lighting in the space shall be automatically shut off within 20 minutes of all occupants leaving the space
Title 24 – 2022
For private/small offices <250 sq. ft:
130.1 (a) Manual area controls.
Each area enclosed by ceiling-height partitions shall provide lighting controls that allow the lighting in that area to be manually turned on and off.
130.1 (c) Shut-OFF Controls.
Lighting shall be controlled with occupant sensing controls to automatically shut OFF all of the lighting in 20 minutes or less after the control zone is unoccupied that shall function either as:
- A. Occupant sensing controls (if 130.1(b) not required to have multi-level lighting controls); or
- B. Partial-ON occupant sensing controls, or
- C. Vacancy sensing controls, where all lighting responds to a manual ON input only