Private Offices

Discover energy-saving solutions for private offices with Rayzeek’s occupancy sensor design guide. Learn how to meet energy code requirements while optimizing lighting control for efficiency and comfort.

Optimize Energy Use in Private Offices with Smart Lighting Control

Private offices are individual workspaces, often enclosed by walls and a door, providing a quiet and focused environment for tasks that require concentration. These spaces are typically equipped with overhead lighting and task lighting, which can contribute significantly to the overall energy consumption of a commercial building.

Despite their benefits, private offices often face the issue of lights being left on when the space is unoccupied, leading to unnecessary energy waste. This is particularly problematic given that private offices are not continuously occupied throughout the day, with occupants often leaving for meetings, breaks, or other tasks.

To address this issue, occupancy sensors offer an effective solution. These devices can automatically turn off lights when the office is vacant, significantly reducing energy consumption. By integrating occupancy sensors into private offices, businesses can not only meet energy code requirements but also achieve substantial energy savings and improve their sustainability efforts.

Atenda aos Códigos de Energia

O International Energy Conservation Code (IECC) é um código modelo desenvolvido pelo International Code Council (ICC) para estabelecer requisitos mínimos de projeto e construção para a eficiência energética em edifícios. O IECC é atualizado a cada três anos para incorporar as mais recentes práticas e tecnologias de conservação de energia.

IECC, Por Que Você Deve Se Importar

O IECC é amplamente adotado por estados e municípios nos Estados Unidos. O IECC abrange vários aspectos do uso de energia, incluindo o envoltório do edifício (paredes, telhados e janelas), sistemas de aquecimento e resfriamento, e sistemas de iluminação.

O IECC exige controles de iluminação específicos, como sensores de presença, para minimizar o desperdício de energia em espaços desocupados em diversas áreas.

A Norma ANSI/ASHRAE/IES 90.1, Padrão de Energia para Locais e Edifícios, Exceto Edifícios Residenciais de Baixa Altura, é uma norma de energia amplamente reconhecida e publicada pela American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).

ASHRAE 90.1, Por Que Você Deve Se Importar

A ASHRAE 90.1 é utilizada como referência para códigos de energia prediais em todos os Estados Unidos e serve como uma via de conformidade dentro do IECC, delineando os requisitos mínimos para o desempenho energeticamente eficiente dos componentes de edifícios comerciais, incluindo envoltórios prediais, sistemas de HVAC, sistemas de aquecimento de água e sistemas de iluminação.

A norma ASHRAE 90.1 especifica as densidades de potência de iluminação máximas permitidas e os requisitos mínimos de controle de iluminação, incluindo o uso de sensores de presença em áreas específicas.

O Title 24, Parte 6 do Código de Padrões de Construção da Califórnia, oficialmente conhecido como Padrões de Eficiência Energética Edilícia para Edifícios Residenciais e Não Residenciais, é administrado pela California Energy Commission e é atualizado periodicamente para refletir novas tecnologias e métodos de eficiência energética.

Title 24, Por Que Você Deve Se Importar

O Title 24 é conhecido por seus requisitos rigorosos, frequentemente considerados mais severos do que os encontrados em muitos outros códigos de energia nos Estados Unidos. O Title 24 exige normas estritas de desempenho energético para todos os aspectos da construção civil, o que inclui aquecimento, ventilação, ar-condicionado (HVAC), aquecimento de água e iluminação.

O Title 24 exige a instalação de sensores de presença que ajustam a iluminação com base na ocupação da sala em áreas específicas de edifícios comerciais para garantir que a energia não seja desperdiçada.

Adoção de Códigos de Energia por Estado

Expanda para ver a tabela detalhada ↓

EstadoCódigo comercial atualCategoria de eficiência do código comercial
Alabama90.1-201390.1-2013
AlascaNenhum em todo o estadoSem código em todo o estado
ArizonaAutonomia municipal<90.1-2007
ArkansasIECC 2009 e 90.1-200790.1-2007
CalifórniaNormas de Eficiência Energética de Edificações de 202290.1-2019
ColoradoAutonomia municipalSem código em todo o estado
Connecticut2021 IECC e 90.1-201990.1-2019
Delaware2018 IECC e 90.1-201690.1-2013
Distrito de Colúmbia90.1-2013^90.1-2019
Flórida2021 IECC e 90.1-2019^90.1-2016
Geórgia2015 IECC e 90.1-2013^90.1-2013
HavaíAutonomia municipal90.1-2013
Idaho2018 IECC e 90.1-201690.1-2013
Illinois2021 IECC e 90.1-201990.1-2019
Indiana90.1-200790.1-2007
Iowa2012 IECC e 90.1-201090.1-2007
KansasAutonomia municipalSem código em todo o estado
Kentucky2012 IECC e 90.1-201090.1-2007
Luisiána2021 IECC e 90.1-2019^90.1-2016
Maine2015 IECC e 90.1-201390.1-2013
Maryland2021 IECC e 90.1-2019^90.1-2019
Massachusetts2018 IECC e 90.1-2016^90.1-2019
Michigan2015 IECC e 90.1-2013^90.1-2013
Minnesota90.1-2019^90.1-2019
MississippiNenhum em todo o estadoSem código em todo o estado
MissouriAutonomia municipalSem código em todo o estado
Montana2021 IECC e 90.1-201990.1-2019
Nebraska2018 IECC e 90.1-201690.1-2013
Nevada2018 IECC e 90.1-201690.1-2013
New Hampshire2018 IECC e 90.1-2016^90.1-2013
New Jersey90.1-201990.1-2019
Novo México2021 IECC e 90.1-2019^90.1-2019
Nova York2018 IECC e 90.1-2016^90.1-2016
Carolina do Norte2015 IECC e 90.1-2013^90.1-2010
Dakota do NorteAutonomia municipalSem código em todo o estado
Ohio2021 IECC e 90.1-2019^90.1-2016
Oklahoma2006 IECC e 90.1-2004<90.1-2007
Oregon90.1-201990.1-2019
Pensilvânia2018 IECC e 90.1-201690.1-2013
Rhode Island2018 IECC e 90.1-2016^90.1-2013
Carolina do SulIECC 2009 e 90.1-200790.1-2007
Dakota do SulAutonomia municipalSem código em todo o estado
Tennessee2021 IECC e 90.1-201390.1-2007
Texas2015 IECC e 90.1-201390.1-2013
Utah2021 IECC e 90.1-2019^90.1-2019
Vermont2021 IECC e 90.1-2019^90.1-2019
Virginia2021 IECC e 90.1-2019^90.1-2019
Washington2018 Washington State Energy Code90.1-2019
Tennessee2012 IECC e 90.1-201090.1-2007
Texas2015 IECC e 90.1-201390.1-2013
Utah2021 IECC e 90.1-2019^90.1-2019
Vermont2018 IECC e 90.1-2016^90.1-2019
Virginia2021 IECC e 90.1-2019^90.1-2019
Washington2018 Washington State Energy Code90.1-2019
West Virginia90.1-201390.1-2013
Wisconsin2015 IECC e 90.1-2013^90.1-2010
WyomingAutonomia municipalSem código em todo o estado
  • ^ When an amendment impacting energy efficiency can be quantified using DOE Prototype Building Models, they were captured in the analysis.
  • For states adopting both IECC and 90.1, the IECC code is usually analyzed as the state current code in this study except for states with extensive amendments to the IECC.

Sensor Solutions

Find out how Rayzeek can solve your energy saving challenges.

Ver todas as ofertas

Conceitos-chave do guia de projeto para escritórios individuais

Projetar uma solução de controle de iluminação energeticamente eficiente para escritórios individuais envolve o posicionamento estratégico de sensores de presença para garantir a cobertura completa do espaço.

  • Posicionamento do sensor: Position the sensor to cover the main areas of activity, such as the desk and the entrance. The sensor should have a clear line of sight to these areas, unobstructed by furniture or other objects. For private offices, wall-mounted sensors or ceiling-mounted sensors can be effective, depending on the room layout and furniture arrangement.
  • Coverage of Minor Movements: Ensure that the desk area falls within the minor motion coverage area of the sensor. This means that even small movements, such as typing or turning pages in a book, should be detected by the sensor to prevent the lights from turning off while the space is occupied.
  • Avoidance of Obstructions: If using wall-mounted sensors, ensure that tall furniture like bookcases does not block the sensor’s view of the room. Similarly, the sensor’s view should not be blocked by the door when it’s open.
  • Entrance Coverage: The sensor should have a clear view of the entrance to detect occupancy as soon as someone enters the room. If the door blocks the sensor’s view when open, consider using an additional sensor to cover the entrance.
  • Avoidance of Interference: Sensors should not be mounted close to air vents, as the vibration and air flow can reduce their effectiveness.
  • Manual Control: Incorporate manual controls for occupants to turn the lights ON/OFF as needed. These controls should be conveniently located, often near the entrance.

Wall Sensor Switches

RZ020/021 Motion Sensor Switches

  • 2-wire, 3-wire, 4-wires wiring options
  • Occupancy, Vacancy, Manual ON/OFF
  • Adjustive time delay and ambient light control

Multi-Location Wireless Wall Sensors

RZ020A/021A + RZ022W Kits

  • Hardwired RZ021A/022A occupancy sensor switch
  • Wireless companion switch (RZ022W) for multi-location control

Ceiling Occupancy Sensors

RZ036

  • Hardwired occupancy sensors
  • Auto ON, auto OFF
  • Line voltage and Low voltage available

Core features included:

  • Integrated manual ON/OFF control for all lighting
  • Vacancy sensors (Manual ON only): Lights must be turned on manually only
  • Adjustable time-delay, lighting is automatically turned full OFF after 15mins
  • Additional: multi-location wireless kits to expand the control range without re-wring
  • Additional: multiple wiring options available for both new constructions and retrofit projects.

Meets the Mandatory Provisions

IECC – 2011

C405.2.1 Occupant sensor controls

Occupant sensor controls shall be installed to control lights in the space.

For private/small offices <300 sq. ft:

C405.2.1.1 Occupant sensor control functions

  • Manual on or partial on to no more than 50% power.
  • Full off within 20 minutes after all occupants have left the space
  • A manual control to turn off the lights.

ASHRAE 90.1 – 2022

For private/small/enclosed offices <300 sq. ft:

9.4.1.1 a Local control

There shall be one or more manual lighting control device that provides ON and OFF control
of all lighting in the space.

9.4.1.1 b Restricted to manual ON

None of the lighting shall be automatically turned on

9.4.1.1 c Restricted to partial automatic ON

No more than 50% of the lighting power for the general lighting shall be allowed to be automatically turned on

** NOTE: At least one 9.4.1.1 b or 9.4.1.1 c shall be implemented.

9.4.1.1 H Automatic full OFF control

All lighting in the space shall be automatically shut off within 20 minutes of all occupants leaving the space

Title 24 – 2022

For private/small offices <250 sq. ft:

130.1 (a) Manual area controls.

Each area enclosed by ceiling-height partitions shall provide lighting controls that allow the lighting in that area to be manually turned on and off.

130.1 (c) Shut-OFF Controls.

Lighting shall be controlled with occupant sensing controls to automatically shut OFF all of the lighting in 20 minutes or less after the control zone is unoccupied that shall function either as:

  • A. Occupant sensing controls (if 130.1(b) not required to have multi-level lighting controls); or
  • B. Partial-ON occupant sensing controls, or
  • C. Vacancy sensing controls, where all lighting responds to a manual ON input only