Private Offices

Discover energy-saving solutions for private offices with Rayzeek’s occupancy sensor design guide. Learn how to meet energy code requirements while optimizing lighting control for efficiency and comfort.

Optimize Energy Use in Private Offices with Smart Lighting Control

Private offices are individual workspaces, often enclosed by walls and a door, providing a quiet and focused environment for tasks that require concentration. These spaces are typically equipped with overhead lighting and task lighting, which can contribute significantly to the overall energy consumption of a commercial building.

Despite their benefits, private offices often face the issue of lights being left on when the space is unoccupied, leading to unnecessary energy waste. This is particularly problematic given that private offices are not continuously occupied throughout the day, with occupants often leaving for meetings, breaks, or other tasks.

To address this issue, occupancy sensors offer an effective solution. These devices can automatically turn off lights when the office is vacant, significantly reducing energy consumption. By integrating occupancy sensors into private offices, businesses can not only meet energy code requirements but also achieve substantial energy savings and improve their sustainability efforts.

エネルギー基準(省エネコード)への適合

国際省エネルギー基準(IECC)は、建築物におけるエネルギー効率の最小設計・施工要件を確立するために、国際基準評価機構(ICC)によって策定されたモデル基準です。IECCは、最新の省エネルギー手法や技術を取り入れるため、3年ごとに改定されています。

IECCに準拠すべき理由

IECCは全米の州や自治体で広く採用されています。IECCは、建築外皮(壁、屋根、窓)、冷暖房システム、照明システムなど、エネルギー利用の多様な側面をカバーしています。

IECCでは、さまざまなエリアの不在空間におけるエネルギーの無駄を最小限に抑えるため、人感センサーなどの特定の照明制御の設置が義務付けられています。

ANSI/ASHRAE/IES Standard 90.1(低層住宅を除く敷地および建築物のためのエネルギー基準)は、米国暖房冷凍空調学会(ASHRAE)が発行している、広く認知されたエネルギー基準です。

ASHRAE 90.1に準拠すべき理由

ASHRAE 90.1は、全米における建築物エネルギー基準のベンチマークとして使用されており、IECC内の適合パスとしても機能しています。この基準は、建築外皮、HVACシステム、給湯システム、照明システムを含む、商業ビル構成要素の省エネルギー性能に関する最小要件を提示しています。

ASHRAE 90.1基準では、許容される最大照明電力密度の規定に加え、特定エリアにおける人感センサーの使用を含む、最小限の照明制御要件を規定しています。

カリフォルニア州建築基準法第24条第6部(正式名称:住宅および非住宅建築物のための建築エネルギー効率基準)は、カリフォルニア州エネルギー委員会(CEC)によって管理され、新しい省エネ技術や手法を反映するために定期的に改定されています。

Title 24に準拠すべき理由

Title 24はその厳格な要件で知られており、全米の他の多くのエネルギー基準よりも厳しいと評価されることがよくあります。Title 24は、暖房、換気、空調(HVAC)、給湯、照明など、建築物施工のあらゆる側面に対して厳しいエネルギー性能基準を義務付けています。

Title 24では、エネルギーの無駄を確実に防ぐため、商業ビルの特定エリアにおいて室内の占有状況に応じて照明を調整する人感センサーの設置が義務付けられています。

州別のエネルギー基準(省エネコード)採用状況

Expand to see the detailed table ↓

StateCurrent Commercial CodeCommercial Code Efficiency Category
Alabama90.1-201390.1-2013
AlaskaNone statewideNo statewide code
ArizonaHome rule<90.1-2007
Arkansas2009 IECC and 90.1-200790.1-2007
California2022 Building Energy Efficiency Standards90.1-2019
ColoradoHome ruleNo statewide code
Connecticut2021 IECC and 90.1-201990.1-2019
Delaware2018 IECC and 90.1-201690.1-2013
District of Columbia90.1-2013^90.1-2019
Florida2021 IECC and 90.1-2019^90.1-2016
Georgia2015 IECC and 90.1-2013^90.1-2013
HawaiiHome rule90.1-2013
Idaho2018 IECC and 90.1-201690.1-2013
Illinois2021 IECC and 90.1-201990.1-2019
Indiana90.1-200790.1-2007
Iowa2012 IECC and 90.1-201090.1-2007
KansasHome ruleNo statewide code
Kentucky2012 IECC and 90.1-201090.1-2007
Louisiana2021 IECC and 90.1-2019^90.1-2016
Maine2015 IECC and 90.1-201390.1-2013
Maryland2021 IECC and 90.1-2019^90.1-2019
Massachusetts2018 IECC and 90.1-2016^90.1-2019
Michigan2015 IECC and 90.1-2013^90.1-2013
Minnesota90.1-2019^90.1-2019
MississippiNone statewideNo statewide code
MissouriHome ruleNo statewide code
Montana2021 IECC and 90.1-201990.1-2019
Nebraska2018 IECC and 90.1-201690.1-2013
Nevada2018 IECC and 90.1-201690.1-2013
New Hampshire2018 IECC and 90.1-2016^90.1-2013
New Jersey90.1-201990.1-2019
New Mexico2021 IECC and 90.1-2019^90.1-2019
New York2018 IECC and 90.1-2016^90.1-2016
North Carolina2015 IECC and 90.1-2013^90.1-2010
North DakotaHome ruleNo statewide code
Ohio2021 IECC and 90.1-2019^90.1-2016
Oklahoma2006 IECC and 90.1-2004<90.1-2007
Oregon90.1-201990.1-2019
Pennsylvania2018 IECC and 90.1-201690.1-2013
Rhode Island2018 IECC and 90.1-2016^90.1-2013
South Carolina2009 IECC and 90.1-200790.1-2007
South DakotaHome ruleNo statewide code
Tennessee2021 IECC and 90.1-201390.1-2007
Texas2015 IECC and 90.1-201390.1-2013
Utah2021 IECC and 90.1-2019^90.1-2019
Vermont2021 IECC and 90.1-2019^90.1-2019
Virginia2021 IECC and 90.1-2019^90.1-2019
Washington2018 Washington State Energy Code90.1-2019
Tennessee2012 IECC and 90.1-201090.1-2007
Texas2015 IECC and 90.1-201390.1-2013
Utah2021 IECC and 90.1-2019^90.1-2019
Vermont2018 IECC and 90.1-2016^90.1-2019
Virginia2021 IECC and 90.1-2019^90.1-2019
Washington2018 Washington State Energy Code90.1-2019
West Virginia90.1-201390.1-2013
Wisconsin2015 IECC and 90.1-2013^90.1-2010
WyomingHome ruleNo statewide code
  • ^ When an amendment impacting energy efficiency can be quantified using DOE Prototype Building Models, they were captured in the analysis.
  • For states adopting both IECC and 90.1, the IECC code is usually analyzed as the state current code in this study except for states with extensive amendments to the IECC.

Sensor Solutions

Find out how Rayzeek can solve your energy saving challenges.

View All Offerings

Design Guide Key Concepts for Private Offices

Designing an energy-efficient lighting control solution for private offices involves strategic placement of occupancy sensors to ensure comprehensive coverage of the space.

  • Sensor Placement: Position the sensor to cover the main areas of activity, such as the desk and the entrance. The sensor should have a clear line of sight to these areas, unobstructed by furniture or other objects. For private offices, wall-mounted sensors or ceiling-mounted sensors can be effective, depending on the room layout and furniture arrangement.
  • Coverage of Minor Movements: Ensure that the desk area falls within the minor motion coverage area of the sensor. This means that even small movements, such as typing or turning pages in a book, should be detected by the sensor to prevent the lights from turning off while the space is occupied.
  • Avoidance of Obstructions: If using wall-mounted sensors, ensure that tall furniture like bookcases does not block the sensor’s view of the room. Similarly, the sensor’s view should not be blocked by the door when it’s open.
  • Entrance Coverage: The sensor should have a clear view of the entrance to detect occupancy as soon as someone enters the room. If the door blocks the sensor’s view when open, consider using an additional sensor to cover the entrance.
  • Avoidance of Interference: Sensors should not be mounted close to air vents, as the vibration and air flow can reduce their effectiveness.
  • Manual Control: Incorporate manual controls for occupants to turn the lights ON/OFF as needed. These controls should be conveniently located, often near the entrance.

Wall Sensor Switches

RZ020/021 Motion Sensor Switches

  • 2-wire, 3-wire, 4-wires wiring options
  • Occupancy, Vacancy, Manual ON/OFF
  • Adjustive time delay and ambient light control

Multi-Location Wireless Wall Sensors

RZ020A/021A + RZ022W Kits

  • Hardwired RZ021A/022A occupancy sensor switch
  • Wireless companion switch (RZ022W) for multi-location control

Ceiling Occupancy Sensors

RZ036

  • Hardwired occupancy sensors
  • Auto ON, auto OFF
  • Line voltage and Low voltage available

Core features included:

  • Integrated manual ON/OFF control for all lighting
  • Vacancy sensors (Manual ON only): Lights must be turned on manually only
  • Adjustable time-delay, lighting is automatically turned full OFF after 15mins
  • Additional: multi-location wireless kits to expand the control range without re-wring
  • Additional: multiple wiring options available for both new constructions and retrofit projects.

Meets the Mandatory Provisions

IECC – 2011

C405.2.1 Occupant sensor controls

Occupant sensor controls shall be installed to control lights in the space.

For private/small offices <300 sq. ft:

C405.2.1.1 Occupant sensor control functions

  • Manual on or partial on to no more than 50% power.
  • Full off within 20 minutes after all occupants have left the space
  • A manual control to turn off the lights.

ASHRAE 90.1 – 2022

For private/small/enclosed offices <300 sq. ft:

9.4.1.1 a Local control

There shall be one or more manual lighting control device that provides ON and OFF control
of all lighting in the space.

9.4.1.1 b Restricted to manual ON

None of the lighting shall be automatically turned on

9.4.1.1 c Restricted to partial automatic ON

No more than 50% of the lighting power for the general lighting shall be allowed to be automatically turned on

** NOTE: At least one 9.4.1.1 b or 9.4.1.1 c shall be implemented.

9.4.1.1 H Automatic full OFF control

All lighting in the space shall be automatically shut off within 20 minutes of all occupants leaving the space

Title 24 – 2022

For private/small offices <250 sq. ft:

130.1 (a) Manual area controls.

Each area enclosed by ceiling-height partitions shall provide lighting controls that allow the lighting in that area to be manually turned on and off.

130.1 (c) Shut-OFF Controls.

Lighting shall be controlled with occupant sensing controls to automatically shut OFF all of the lighting in 20 minutes or less after the control zone is unoccupied that shall function either as:

  • A. Occupant sensing controls (if 130.1(b) not required to have multi-level lighting controls); or
  • B. Partial-ON occupant sensing controls, or
  • C. Vacancy sensing controls, where all lighting responds to a manual ON input only

Let us hear you.