Private Offices

Discover energy-saving solutions for private offices with Rayzeek’s occupancy sensor design guide. Learn how to meet energy code requirements while optimizing lighting control for efficiency and comfort.

Optimize Energy Use in Private Offices with Smart Lighting Control

Private offices are individual workspaces, often enclosed by walls and a door, providing a quiet and focused environment for tasks that require concentration. These spaces are typically equipped with overhead lighting and task lighting, which can contribute significantly to the overall energy consumption of a commercial building.

Despite their benefits, private offices often face the issue of lights being left on when the space is unoccupied, leading to unnecessary energy waste. This is particularly problematic given that private offices are not continuously occupied throughout the day, with occupants often leaving for meetings, breaks, or other tasks.

To address this issue, occupancy sensors offer an effective solution. These devices can automatically turn off lights when the office is vacant, significantly reducing energy consumption. By integrating occupancy sensors into private offices, businesses can not only meet energy code requirements but also achieve substantial energy savings and improve their sustainability efforts.

Respectarea codurilor de energie

International Energy Conservation Code (IECC) este un cod model dezvoltat de International Code Council (ICC) pentru a stabili cerințele minime de proiectare și construcție privind eficiența energetică a clădirilor. IECC este actualizat la fiecare trei ani pentru a încorpora cele mai recente practici și tehnologii în domeniul conservării energiei.

IECC: De ce ar trebui să vă intereseze

IECC este adoptat pe scară largă de state și municipalități din întreaga regiune a Statelor Unite. IECC acoperă diverse aspecte ale utilizării energiei, inclusiv anvelopa clădirii (pereți, acoperișuri și ferestre), sistemele de încălzire și răcire, precum și sistemele de iluminat.

IECC impune controale specifice ale iluminatului, cum ar fi senzorii de prezență, pentru a minimiza risipa de energie în spațiile neocupate din diverse zone.

Standardul ANSI/ASHRAE/IES 90.1, Energy Standard for Sites and Buildings Except Low-Rise Residential Buildings, este un standard de energie recunoscut la nivel larg, publicat de American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).

ASHRAE 90.1: De ce ar trebui să vă intereseze

ASHRAE 90.1 este utilizat ca punct de referință pentru codurile de energie ale clădirilor din Statele Unite și servește ca cale de conformitate în cadrul IECC, stabilind cerințele minime pentru performanța energetică a componentelor clădirilor comerciale, inclusiv anvelopele clădirilor, sistemele HVAC, sistemele de încălzire a apei și sistemele de iluminat.

Standardul ASHRAE 90.1 specifică densitățile maxime admise ale puterii de iluminat și cerințele minime de control al iluminatului, inclusiv utilizarea senzorilor de prezență în anumite zone.

Title 24, partea 6 din California Building Standards Code, cunoscut oficial sub numele de Building Energy Efficiency Standards for Residential and Nonresidential Buildings, Title 24 este administrat de California Energy Commission și este actualizat periodic pentru a reflecta noile tehnologii și metode de eficiență energetică.

Title 24: De ce ar trebui să vă intereseze

Title 24 este cunoscut pentru cerințele sale riguroase, fiind adesea considerat mai strict decât multe alte coduri energetice din Statele Unite. Title 24 impune standarde stricte de performanță energetică pentru toate aspectele construcției clădirilor, care includ încălzirea, ventilația, aerul condiționat (HVAC), încălzirea apei și iluminatul.

Title 24 necesită instalarea de senzori de prezență care ajustează iluminatul în funcție de gradul de ocupare a încăperii în anumite zone ale clădirilor comerciale, pentru a se asigura că energia nu este risipită.

Adoptarea codului de energie pe state

Extindeți pentru a vedea tabelul detaliat ↓

StatCod comercial actualCategorie de eficiență a codului comercial
Alabama90.1-201390.1-2013
AlaskaNiciunul la nivel de statFără cod la nivel de stat
ArizonaAutonomie locală<90.1-2007
Arkansas2009 IECC și 90.1-200790.1-2007
CaliforniaStandardele de Eficiență Energetică a Clădirilor din 202290.1-2019
ColoradoAutonomie localăFără cod la nivel de stat
ConnecticutIECC 2021 și 90.1-201990.1-2019
DelawareIECC 2018 și 90.1-201690.1-2013
Districtul Columbia90.1-2013^90.1-2019
FloridaIECC 2021 și 90.1-2019^90.1-2016
GeorgiaIECC 2015 și 90.1-2013^90.1-2013
HawaiiAutonomie locală90.1-2013
IdahoIECC 2018 și 90.1-201690.1-2013
IllinoisIECC 2021 și 90.1-201990.1-2019
Indiana90.1-200790.1-2007
Iowa2012 IECC și 90.1-201090.1-2007
KansasAutonomie localăFără cod la nivel de stat
Kentucky2012 IECC și 90.1-201090.1-2007
LouisianaIECC 2021 și 90.1-2019^90.1-2016
Maine2015 IECC și 90.1-201390.1-2013
MarylandIECC 2021 și 90.1-2019^90.1-2019
Massachusetts2018 IECC și 90.1-2016^90.1-2019
MichiganIECC 2015 și 90.1-2013^90.1-2013
Minnesota90.1-2019^90.1-2019
MississippiNiciunul la nivel de statFără cod la nivel de stat
MissouriAutonomie localăFără cod la nivel de stat
MontanaIECC 2021 și 90.1-201990.1-2019
NebraskaIECC 2018 și 90.1-201690.1-2013
NevadaIECC 2018 și 90.1-201690.1-2013
New Hampshire2018 IECC și 90.1-2016^90.1-2013
New Jersey90.1-201990.1-2019
Noul MexicIECC 2021 și 90.1-2019^90.1-2019
New York2018 IECC și 90.1-2016^90.1-2016
Carolina de NordIECC 2015 și 90.1-2013^90.1-2010
Dakota de NordAutonomie localăFără cod la nivel de stat
OhioIECC 2021 și 90.1-2019^90.1-2016
Oklahoma2006 IECC și 90.1-2004<90.1-2007
Oregon90.1-201990.1-2019
PennsylvaniaIECC 2018 și 90.1-201690.1-2013
Rhode Island2018 IECC și 90.1-2016^90.1-2013
Carolina de Sud2009 IECC și 90.1-200790.1-2007
Dakota de SudAutonomie localăFără cod la nivel de stat
Tennessee2021 IECC și 90.1-201390.1-2007
Texas2015 IECC și 90.1-201390.1-2013
UtahIECC 2021 și 90.1-2019^90.1-2019
VermontIECC 2021 și 90.1-2019^90.1-2019
VirginiaIECC 2021 și 90.1-2019^90.1-2019
WashingtonCodul Energetic al Statului Washington din 201890.1-2019
Tennessee2012 IECC și 90.1-201090.1-2007
Texas2015 IECC și 90.1-201390.1-2013
UtahIECC 2021 și 90.1-2019^90.1-2019
Vermont2018 IECC și 90.1-2016^90.1-2019
VirginiaIECC 2021 și 90.1-2019^90.1-2019
WashingtonCodul Energetic al Statului Washington din 201890.1-2019
Virginia de Vest90.1-201390.1-2013
WisconsinIECC 2015 și 90.1-2013^90.1-2010
WyomingAutonomie localăFără cod la nivel de stat
  • ^ When an amendment impacting energy efficiency can be quantified using DOE Prototype Building Models, they were captured in the analysis.
  • For states adopting both IECC and 90.1, the IECC code is usually analyzed as the state current code in this study except for states with extensive amendments to the IECC.

Sensor Solutions

Find out how Rayzeek can solve your energy saving challenges.

Vizualizați toate ofertele

Concepte cheie ale ghidului de proiectare pentru birouri individuale

Proiectarea unei soluții de control al iluminatului eficiente din punct de vedere energetic pentru birouri individuale implică amplasarea strategică a senzorilor de prezență pentru a asigura o acoperire completă a spațiului.

  • Sensor Placement: Position the sensor to cover the main areas of activity, such as the desk and the entrance. The sensor should have a clear line of sight to these areas, unobstructed by furniture or other objects. For private offices, wall-mounted sensors or ceiling-mounted sensors can be effective, depending on the room layout and furniture arrangement.
  • Coverage of Minor Movements: Ensure that the desk area falls within the minor motion coverage area of the sensor. This means that even small movements, such as typing or turning pages in a book, should be detected by the sensor to prevent the lights from turning off while the space is occupied.
  • Avoidance of Obstructions: If using wall-mounted sensors, ensure that tall furniture like bookcases does not block the sensor’s view of the room. Similarly, the sensor’s view should not be blocked by the door when it’s open.
  • Entrance Coverage: The sensor should have a clear view of the entrance to detect occupancy as soon as someone enters the room. If the door blocks the sensor’s view when open, consider using an additional sensor to cover the entrance.
  • Avoidance of Interference: Sensors should not be mounted close to air vents, as the vibration and air flow can reduce their effectiveness.
  • Manual Control: Incorporate manual controls for occupants to turn the lights ON/OFF as needed. These controls should be conveniently located, often near the entrance.

Wall Sensor Switches

RZ020/021 Motion Sensor Switches

  • 2-wire, 3-wire, 4-wires wiring options
  • Occupancy, Vacancy, Manual ON/OFF
  • Adjustive time delay and ambient light control

Multi-Location Wireless Wall Sensors

RZ020A/021A + RZ022W Kits

  • Hardwired RZ021A/022A occupancy sensor switch
  • Wireless companion switch (RZ022W) for multi-location control

Ceiling Occupancy Sensors

RZ036

  • Hardwired occupancy sensors
  • Auto ON, auto OFF
  • Line voltage and Low voltage available

Core features included:

  • Integrated manual ON/OFF control for all lighting
  • Vacancy sensors (Manual ON only): Lights must be turned on manually only
  • Adjustable time-delay, lighting is automatically turned full OFF after 15mins
  • Additional: multi-location wireless kits to expand the control range without re-wring
  • Additional: multiple wiring options available for both new constructions and retrofit projects.

Meets the Mandatory Provisions

IECC – 2011

C405.2.1 Occupant sensor controls

Occupant sensor controls shall be installed to control lights in the space.

For private/small offices <300 sq. ft:

C405.2.1.1 Occupant sensor control functions

  • Manual on or partial on to no more than 50% power.
  • Full off within 20 minutes after all occupants have left the space
  • A manual control to turn off the lights.

ASHRAE 90.1 – 2022

For private/small/enclosed offices <300 sq. ft:

9.4.1.1 a Local control

There shall be one or more manual lighting control device that provides ON and OFF control
of all lighting in the space.

9.4.1.1 b Restricted to manual ON

None of the lighting shall be automatically turned on

9.4.1.1 c Restricted to partial automatic ON

No more than 50% of the lighting power for the general lighting shall be allowed to be automatically turned on

** NOTE: At least one 9.4.1.1 b or 9.4.1.1 c shall be implemented.

9.4.1.1 H Automatic full OFF control

All lighting in the space shall be automatically shut off within 20 minutes of all occupants leaving the space

Title 24 – 2022

For private/small offices <250 sq. ft:

130.1 (a) Manual area controls.

Each area enclosed by ceiling-height partitions shall provide lighting controls that allow the lighting in that area to be manually turned on and off.

130.1 (c) Shut-OFF Controls.

Lighting shall be controlled with occupant sensing controls to automatically shut OFF all of the lighting in 20 minutes or less after the control zone is unoccupied that shall function either as:

  • A. Occupant sensing controls (if 130.1(b) not required to have multi-level lighting controls); or
  • B. Partial-ON occupant sensing controls, or
  • C. Vacancy sensing controls, where all lighting responds to a manual ON input only

Let us hear you.

Let Rayzeek help design and deliver a bespoke energy-saving lighting solution for you.

    Romanian