Hol de acces

Descoperiți potențialul de economisire a energiei din holul dumneavoastră de acces. Aflați cum puteți respecta codurile energetice și reduce risipa de energie cu soluțiile noastre personalizate.

Transform Your Lobby into an Energy-Efficient Space

The lobby is often the first point of contact for visitors and employees in a commercial building. It’s a space that needs to be well-lit and welcoming at all times. It’s a bustling area, filled with people coming and going at all hours. The lighting in these areas is typically high-intensity and left on for extended periods, leading to significant energy consumption.

Traditional lighting systems in lobbies are often manually controlled, resulting in lights being left on unnecessarily when the space is unoccupied, leading to high energy waste. Moreover, the diverse activities and varying occupancy levels in lobbies make it challenging to manage lighting efficiently. This not only increases operational costs but also contributes to a larger carbon footprint.

To address these issues, occupancy sensors offer an effective solution. These devices can automatically turn off or dim the lights when the lobby is vacant, significantly reducing energy consumption. Rayzeek’s range of occupancy sensors, including wall and ceiling-mounted options, provide a tailored solution for lobbies, ensuring efficient lighting control without compromising on comfort or safety.

Respectarea codurilor de energie

International Energy Conservation Code (IECC) este un cod model dezvoltat de International Code Council (ICC) pentru a stabili cerințele minime de proiectare și construcție privind eficiența energetică a clădirilor. IECC este actualizat la fiecare trei ani pentru a încorpora cele mai recente practici și tehnologii în domeniul conservării energiei.

IECC: De ce ar trebui să vă intereseze

IECC este adoptat pe scară largă de state și municipalități din întreaga regiune a Statelor Unite. IECC acoperă diverse aspecte ale utilizării energiei, inclusiv anvelopa clădirii (pereți, acoperișuri și ferestre), sistemele de încălzire și răcire, precum și sistemele de iluminat.

IECC impune controale specifice ale iluminatului, cum ar fi senzorii de prezență, pentru a minimiza risipa de energie în spațiile neocupate din diverse zone.

Standardul ANSI/ASHRAE/IES 90.1, Energy Standard for Sites and Buildings Except Low-Rise Residential Buildings, este un standard de energie recunoscut la nivel larg, publicat de American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).

ASHRAE 90.1: De ce ar trebui să vă intereseze

ASHRAE 90.1 este utilizat ca punct de referință pentru codurile de energie ale clădirilor din Statele Unite și servește ca cale de conformitate în cadrul IECC, stabilind cerințele minime pentru performanța energetică a componentelor clădirilor comerciale, inclusiv anvelopele clădirilor, sistemele HVAC, sistemele de încălzire a apei și sistemele de iluminat.

Standardul ASHRAE 90.1 specifică densitățile maxime admise ale puterii de iluminat și cerințele minime de control al iluminatului, inclusiv utilizarea senzorilor de prezență în anumite zone.

Title 24, partea 6 din California Building Standards Code, cunoscut oficial sub numele de Building Energy Efficiency Standards for Residential and Nonresidential Buildings, Title 24 este administrat de California Energy Commission și este actualizat periodic pentru a reflecta noile tehnologii și metode de eficiență energetică.

Title 24: De ce ar trebui să vă intereseze

Title 24 este cunoscut pentru cerințele sale riguroase, fiind adesea considerat mai strict decât multe alte coduri energetice din Statele Unite. Title 24 impune standarde stricte de performanță energetică pentru toate aspectele construcției clădirilor, care includ încălzirea, ventilația, aerul condiționat (HVAC), încălzirea apei și iluminatul.

Title 24 necesită instalarea de senzori de prezență care ajustează iluminatul în funcție de gradul de ocupare a încăperii în anumite zone ale clădirilor comerciale, pentru a se asigura că energia nu este risipită.

Adoptarea codului de energie pe state

Extindeți pentru a vedea tabelul detaliat ↓

StatCod comercial actualCategorie de eficiență a codului comercial
Alabama90.1-201390.1-2013
AlaskaNiciunul la nivel de statFără cod la nivel de stat
ArizonaAutonomie locală<90.1-2007
Arkansas2009 IECC și 90.1-200790.1-2007
CaliforniaStandardele de Eficiență Energetică a Clădirilor din 202290.1-2019
ColoradoAutonomie localăFără cod la nivel de stat
ConnecticutIECC 2021 și 90.1-201990.1-2019
DelawareIECC 2018 și 90.1-201690.1-2013
Districtul Columbia90.1-2013^90.1-2019
FloridaIECC 2021 și 90.1-2019^90.1-2016
GeorgiaIECC 2015 și 90.1-2013^90.1-2013
HawaiiAutonomie locală90.1-2013
IdahoIECC 2018 și 90.1-201690.1-2013
IllinoisIECC 2021 și 90.1-201990.1-2019
Indiana90.1-200790.1-2007
Iowa2012 IECC și 90.1-201090.1-2007
KansasAutonomie localăFără cod la nivel de stat
Kentucky2012 IECC și 90.1-201090.1-2007
LouisianaIECC 2021 și 90.1-2019^90.1-2016
Maine2015 IECC și 90.1-201390.1-2013
MarylandIECC 2021 și 90.1-2019^90.1-2019
Massachusetts2018 IECC și 90.1-2016^90.1-2019
MichiganIECC 2015 și 90.1-2013^90.1-2013
Minnesota90.1-2019^90.1-2019
MississippiNiciunul la nivel de statFără cod la nivel de stat
MissouriAutonomie localăFără cod la nivel de stat
MontanaIECC 2021 și 90.1-201990.1-2019
NebraskaIECC 2018 și 90.1-201690.1-2013
NevadaIECC 2018 și 90.1-201690.1-2013
New Hampshire2018 IECC și 90.1-2016^90.1-2013
New Jersey90.1-201990.1-2019
Noul MexicIECC 2021 și 90.1-2019^90.1-2019
New York2018 IECC și 90.1-2016^90.1-2016
Carolina de NordIECC 2015 și 90.1-2013^90.1-2010
Dakota de NordAutonomie localăFără cod la nivel de stat
OhioIECC 2021 și 90.1-2019^90.1-2016
Oklahoma2006 IECC și 90.1-2004<90.1-2007
Oregon90.1-201990.1-2019
PennsylvaniaIECC 2018 și 90.1-201690.1-2013
Rhode Island2018 IECC și 90.1-2016^90.1-2013
Carolina de Sud2009 IECC și 90.1-200790.1-2007
Dakota de SudAutonomie localăFără cod la nivel de stat
Tennessee2021 IECC și 90.1-201390.1-2007
Texas2015 IECC și 90.1-201390.1-2013
UtahIECC 2021 și 90.1-2019^90.1-2019
VermontIECC 2021 și 90.1-2019^90.1-2019
VirginiaIECC 2021 și 90.1-2019^90.1-2019
WashingtonCodul Energetic al Statului Washington din 201890.1-2019
Tennessee2012 IECC și 90.1-201090.1-2007
Texas2015 IECC și 90.1-201390.1-2013
UtahIECC 2021 și 90.1-2019^90.1-2019
Vermont2018 IECC și 90.1-2016^90.1-2019
VirginiaIECC 2021 și 90.1-2019^90.1-2019
WashingtonCodul Energetic al Statului Washington din 201890.1-2019
Virginia de Vest90.1-201390.1-2013
WisconsinIECC 2015 și 90.1-2013^90.1-2010
WyomingAutonomie localăFără cod la nivel de stat
  • ^ When an amendment impacting energy efficiency can be quantified using DOE Prototype Building Models, they were captured in the analysis.
  • For states adopting both IECC and 90.1, the IECC code is usually analyzed as the state current code in this study except for states with extensive amendments to the IECC.

Sensor Solutions

Find out how Rayzeek can solve your energy saving challenges.

Vizualizați toate ofertele

Concepte cheie din ghidul de proiectare pentru holuri

Proiectarea unei soluții eficiente din punct de vedere energetic pentru controlul iluminatului din holuri implică amplasarea strategică a senzorilor de prezență, pentru a asigura o acoperire completă a spațiului.

In a lobby, the primary areas that need to be covered by occupancy sensors are the entrance, the reception desk, and any seating or waiting areas. Here’s a possible design guide for a lobby:

  • Entrance Area: Install a ceiling occupancy sensor near the entrance. This sensor will detect the movement of people entering or exiting the lobby, ensuring the lights are activated when needed. Our ceiling sensors offer Auto ON and Full OFF functionality, providing automatic control of lighting based on occupancy.
  • Main Lobby Area: For larger lobbies, additional ceiling sensors may be required to cover the entire space. These sensors should be strategically placed to cover high-traffic areas, such as near the reception desk or waiting areas. The overlapping coverage of multiple sensors ensures there are no blind spots.
  • Reception Desk: Place a wall-mounted sensor near the reception desk. This sensor will detect the presence of the receptionist and any visitors at the desk, keeping the lights on in this area during occupied periods.
  • Seating/Waiting Areas: Install additional ceiling-mounted sensors in any seating or waiting areas. These sensors will detect when these areas are occupied and adjust the lighting accordingly.
  • Manual Control: Install a manual control near the entrance or reception desk. This allows for manual override of the lighting system when necessary.
  • Corridors Leading to Other Areas: Corridors leading to elevators, staircases, or other parts of the building should have their own wall or ceiling-mounted sensors. This ensures that lights in these areas are only activated when someone is passing through.

Wall Sensor Switches

RZ020/021 Motion Sensor Switches

  • 2-wire, 3-wire, 4-wires wiring options
  • Occupancy, Vacancy, Manual ON/OFF
  • Adjustive time delay and ambient light control

Multi-Location Wireless Wall Sensors

RZ020A/021A + RZ022W Kits

  • Hardwired RZ021A/022A occupancy sensor switch
  • Wireless companion switch (RZ022W) for multi-location control

Ceiling Occupancy Sensors

RZ036

  • Hardwired occupancy sensors
  • Auto ON, auto OFF
  • Line voltage and Low voltage available

Core features included:

  • Integrated manual ON/OFF control for all lighting
  • Vacancy sensors (Manual ON only): Lights must be turned on manually only
  • Adjustable time-delay, lighting is automatically turned full OFF after 15mins
  • Additional: multi-location wireless kits to expand the control range without re-wring
  • Additional: multiple wiring options available for both new constructions and retrofit projects.

Meets the Mandatory Provisions

IECC – 2011

C405.2.1 Occupant sensor controls

Occupant sensor controls shall be installed to control lights in the space.

C405.2.1.1 Occupant sensor control functions

  • Manual on or partial on to no more than 50% power.
  • Full off within 20 minutes after all occupants have left the space
  • A manual control to turn off the lights.

Full automatic-on controls with no manual control are permitted in lobbies where manual operation would endanger occupant safety or security.

ASHRAE 90.1 – 2022

9.4.1.1 a Local control

There shall be one or more manual lighting control device that provides ON and OFF control
of all lighting in the space.

9.4.1.1 g Automatic reduction control

The general lighting power in the space shall be automatically reduced by at least 50% within 15 minutes of all occupants leaving the space.

** NOTE: 9.4.1.1 g is required in all other lobbies except (Elevator, Hotel, Motion picture theater, Performing arts theater)

9.4.1.1 h Automatic full OFF control

All lighting in the space shall be automatically shut off within 15 minutes of all occupants leaving the space.

9.4.1.1 i Scheduled shutoff

All lighting in the space shall be automatically shut off during periods when the space is scheduled to be unoccupied.

** NOTE: At least one 9.4.1.1 h or 9.4.1.1 i shall be implemented.

Title 24 – 2022

130.1 (a) Manual area controls.

Each area enclosed by ceiling-height partitions shall provide lighting controls that allow the lighting in that area to be manually turned on and off.

130.1 (c) Shut-OFF Controls.

Lighting shall be controlled with occupant sensing controls to automatically shut OFF all of the lighting in 20 minutes or less after the control zone is unoccupied that shall function either as:

  • A. Occupant sensing controls (if 130.1(b) not required to have multi-level lighting controls); or
  • B. Partial-ON occupant sensing controls, or
  • C. Vacancy sensing controls, where all lighting responds to a manual ON input only

Let us hear you.

Let Rayzeek help design and deliver a bespoke energy-saving lighting solution for you.

    Romanian