Restrooms
Esplora la nostra guida al risparmio energetico per i bagni, ideata per aiutarti a comprendere e implementare soluzioni con sensori di presenza per un controllo efficiente dell'illuminazione in conformità con i codici energetici degli Stati Uniti.

Maximize Energy Efficiency in Restrooms with Occupancy Sensors
Restrooms in commercial buildings are frequently used spaces that often remain lit even when unoccupied, leading to significant energy wastage. These spaces typically use high-intensity lighting fixtures that consume substantial amounts of energy. The sporadic and unpredictable nature of restroom usage further exacerbates this issue, as lights are often left on unnecessarily during periods of non-use.
Given these factors, the potential for energy savings in restrooms is substantial. By implementing occupancy sensor solutions, commercial facilities can significantly reduce their lighting energy consumption. Occupancy sensors detect the presence or absence of people and automatically control the lighting accordingly, ensuring lights are only on when needed. This not only saves energy but also extends the lifespan of lighting fixtures, leading to additional cost savings.
Rispettare i codici energetici

L'International Energy Conservation Code (IECC) è un modello di codice sviluppato dall'International Code Council (ICC) per stabilire i requisiti minimi di progettazione e costruzione volti all'efficienza energetica degli edifici. L'IECC viene aggiornato ogni tre anni per integrare le più recenti prassi e tecnologie nel campo del risparmio energetico.
IECC: perché è importante
L'IECC è ampiamente adottato da stati e comuni negli Stati Uniti. Copre vari aspetti dell'uso dell'energia, tra cui l'involucro edilizio (pareti, tetti e finestre), gli impianti di riscaldamento e raffrescamento e i sistemi di illuminazione.
L'IECC impone controlli dell'illuminazione specifici, come i sensori di presenza, per ridurre al minimo lo spreco di energia negli spazi non occupati in diverse aree.

Lo standard ANSI/ASHRAE/IES 90.1, Energy Standard for Sites and Buildings Except Low-Rise Residential Buildings, è uno standard energetico ampiamente riconosciuto e pubblicato dall'American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
ASHRAE 90.1: perché è importante
Lo standard ASHRAE 90.1 viene utilizzato come punto di riferimento per i codici energetici degli edifici in tutti gli Stati Uniti e funge da percorso di conformità all'interno dell'IECC; definisce i requisiti minimi per le prestazioni di efficienza energetica dei componenti degli edifici commerciali, inclusi involucri edilizi, sistemi HVAC, sistemi di riscaldamento dell'acqua e impianti di illuminazione.
Lo standard ASHRAE 90.1 specifica le densità di potenza massima consentite per l'illuminazione e i requisiti minimi di controllo dell'illuminazione, compreso l'uso di sensori di presenza in aree specifiche.

Il Title 24, parte 6 del California Building Standards Code, ufficialmente noto come Building Energy Efficiency Standards for Residential and Nonresidential Buildings, è amministrato dalla California Energy Commission e viene aggiornato periodicamente per riflettere le nuove tecnologie e metodologie di efficienza energetica.
Title 24: perché è importante
Il Title 24 è noto per i suoi requisiti rigorosi, spesso considerati più severi rispetto a quelli di molti altri codici energetici negli Stati Uniti. Il Title 24 impone severi standard di prestazione energetica per tutti gli aspetti della costruzione di un edificio, tra cui riscaldamento, ventilazione, aria condizionata (HVAC), riscaldamento dell'acqua e illuminazione.
Il Title 24 richiede l'installazione di sensori di presenza che regolino l'illuminazione in base all'occupazione della stanza in specifiche aree degli edifici commerciali, in modo da evitare sprechi di energia.
Adozione dei codici energetici per stato

Espandere per visualizzare la tabella dettagliata ↓
| Stato | Codice commerciale attuale | Categoria di efficienza del codice commerciale |
|---|---|---|
| Alabama | 90.1-2013 | 90.1-2013 |
| Alaska | Nessuno a livello statale | Nessun codice a livello statale |
| Arizona | Autonomia locale | <90.1-2007 |
| Arkansas | 2009 IECC e 90.1-2007 | 90.1-2007 |
| California | 2022 Building Energy Efficiency Standards | 90.1-2019 |
| Colorado | Autonomia locale | Nessun codice a livello statale |
| Connecticut | 2021 IECC and 90.1-2019 | 90.1-2019 |
| Delaware | 2018 IECC and 90.1-2016 | 90.1-2013 |
| District of Columbia | 90.1-2013^ | 90.1-2019 |
| Florida | 2021 IECC and 90.1-2019^ | 90.1-2016 |
| Georgia | 2015 IECC and 90.1-2013^ | 90.1-2013 |
| Hawaii | Autonomia locale | 90.1-2013 |
| Idaho | 2018 IECC and 90.1-2016 | 90.1-2013 |
| Illinois | 2021 IECC and 90.1-2019 | 90.1-2019 |
| Indiana | 90.1-2007 | 90.1-2007 |
| Iowa | 2012 IECC e 90.1-2010 | 90.1-2007 |
| Kansas | Autonomia locale | Nessun codice a livello statale |
| Kentucky | 2012 IECC e 90.1-2010 | 90.1-2007 |
| Louisiana | 2021 IECC and 90.1-2019^ | 90.1-2016 |
| Maine | 2015 IECC e 90.1-2013 | 90.1-2013 |
| Maryland | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Massachusetts | 2018 IECC e 90.1-2016^ | 90.1-2019 |
| Michigan | 2015 IECC and 90.1-2013^ | 90.1-2013 |
| Minnesota | 90.1-2019^ | 90.1-2019 |
| Mississippi | Nessuno a livello statale | Nessun codice a livello statale |
| Missouri | Autonomia locale | Nessun codice a livello statale |
| Montana | 2021 IECC and 90.1-2019 | 90.1-2019 |
| Nebraska | 2018 IECC and 90.1-2016 | 90.1-2013 |
| Nevada | 2018 IECC and 90.1-2016 | 90.1-2013 |
| New Hampshire | 2018 IECC e 90.1-2016^ | 90.1-2013 |
| New Jersey | 90.1-2019 | 90.1-2019 |
| New Mexico | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| New York | 2018 IECC e 90.1-2016^ | 90.1-2016 |
| North Carolina | 2015 IECC and 90.1-2013^ | 90.1-2010 |
| North Dakota | Autonomia locale | Nessun codice a livello statale |
| Ohio | 2021 IECC and 90.1-2019^ | 90.1-2016 |
| Oklahoma | 2006 IECC e 90.1-2004 | <90.1-2007 |
| Oregon | 90.1-2019 | 90.1-2019 |
| Pennsylvania | 2018 IECC and 90.1-2016 | 90.1-2013 |
| Rhode Island | 2018 IECC e 90.1-2016^ | 90.1-2013 |
| South Carolina | 2009 IECC e 90.1-2007 | 90.1-2007 |
| South Dakota | Autonomia locale | Nessun codice a livello statale |
| Tennessee | 2021 IECC e 90.1-2013 | 90.1-2007 |
| Texas | 2015 IECC e 90.1-2013 | 90.1-2013 |
| Utah | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Vermont | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Virginia | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Washington | Codice energetico dello Stato di Washington 2018 | 90.1-2019 |
| Tennessee | 2012 IECC e 90.1-2010 | 90.1-2007 |
| Texas | 2015 IECC e 90.1-2013 | 90.1-2013 |
| Utah | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Vermont | 2018 IECC e 90.1-2016^ | 90.1-2019 |
| Virginia | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Washington | Codice energetico dello Stato di Washington 2018 | 90.1-2019 |
| West Virginia | 90.1-2013 | 90.1-2013 |
| Wisconsin | 2015 IECC and 90.1-2013^ | 90.1-2010 |
| Wyoming | Autonomia locale | Nessun codice a livello statale |
- ^ Quando una modifica che influisce sull'efficienza energetica può essere quantificata utilizzando i modelli di edificio prototipo del DOE, questa è stata inclusa nell'analisi.
- Per gli Stati che adottano sia l'IECC che la norma 90.1, il codice IECC viene solitamente analizzato come codice statale vigente in questo studio, ad eccezione degli Stati con modifiche estese all'IECC.
Design Guide Key Concepts for Restrooms
Designing an energy-efficient lighting control solution for restrooms involves strategic placement of occupancy sensors to ensure comprehensive coverage of the space.

By following these guidelines, businesses can create an energy-efficient lighting control solution for restrooms that reduces energy waste, and lowers maintenance costs:
- Entrance Coverage: Install a wall occupancy sensor near the entrance to detect when someone enters the restroom. This sensor should be positioned high enough to avoid obstructions from the door and should not directly face the entrance to avoid false triggers from movement outside the restroom.
- Stall Coverage: Depending on customer preference for privacy, stalls can either be covered by a sensor or not. If stalls are not covered by a sensor, program a longer timeout (15 or 20 minutes) to prevent lights from turning off when someone is in the stall. If individual stall sensors are used, they should be installed in such a way that they do not detect movement outside the stall to avoid false triggers.
- Sink and Mirror Area: Install a ceiling occupancy sensor above the sink and mirror area. This sensor should be positioned to cover the entire area, ensuring that lights remain on when someone is using the sink or mirror.
- Avoidance of Air Vents: Do not mount sensors close to air vents, as the vibration and air flow can reduce the effectiveness of the sensor. PIR sensors should not be within 4ft of an air vent, and ultrasonic sensors should not be within 6ft of an air vent.
- Controllo manuale: Integrate manual control to turn ON/OFF all lighting with our occupancy/vacancy sensors. This allows for manual override of the lighting system if necessary.
Featured Products & Solutions
Core features included:
- Integrated manual ON/OFF control for all lighting
- Vacancy sensors (Manual ON only): Lights must be turned on manually only
- Adjustable time-delay, lighting is automatically turned full OFF after 15mins
- Additional: multi-location wireless kits to expand the control range without re-wring
- Additional: multiple wiring options available for both new constructions and retrofit projects.

Meets the Mandatory Provisions
IECC – 2011
C405.2.1 Occupant sensor controls
Occupant sensor controls shall be installed to control lights in the space.
C405.2.1.1 Occupant sensor control functions
- Manual on or partial on to no more than 50% power.
- Full off within 20 minutes after all occupants have left the space
- A manual control to turn off the lights.
**Full automatic-on controls with no manual control are permitted in restrooms where manual operation would endanger occupant safety or security.
ASHRAE 90.1 – 2022
Restrooms shall also be controlled by occupant sensors.
9.4.1.1 H Automatic full OFF control
All lighting in the space shall be automatically shut off within 20 minutes of all occupants leaving the space
Title 24 – 2022
130.1 (a) Manual area controls.
Each area enclosed by ceiling-height partitions shall provide lighting controls that allow the lighting in that area to be manually turned on and off.
** Restrooms having two or more stalls may use a manual control not accessible to unauthorized personnel.
130.1 (c) Shut-OFF Controls.
Lighting shall be controlled with occupant sensing controls to automatically shut OFF all of the lighting in 20 minutes or less after the control zone is unoccupied that shall function either as:
- A. Occupant sensing controls (if 130.1(b) not required to have multi-level lighting controls); or
- B. Partial-ON occupant sensing controls, or
- C. Vacancy sensing controls, where all lighting responds to a manual ON input only
Let us hear you.
Let Rayzeek help design and deliver a bespoke energy-saving lighting solution for you.