Corridors
Discover the energy-saving potential of corridors with Rayzeek’s occupancy sensor design guide. Uncover the power of automated lighting control in your commercial building’s passageways.

Lighting the Way to Energy Efficiency in Corridors
Corridors, whether in commercial buildings, educational institutions, or healthcare facilities, are high-traffic areas that often remain illuminated throughout the day, leading to significant energy consumption. These spaces typically use fluorescent or LED lighting, which, while energy-efficient, can still contribute to high energy costs when left on unnecessarily.
The challenge lies in the fact that corridors are intermittently occupied, with periods of high foot traffic interspersed with times of vacancy. Traditional manual lighting controls can lead to lights being left on during these vacant periods, resulting in unnecessary energy waste.
By integrating our occupancy sensors into your corridor lighting system, you can ensure that lights are only on when needed, saving energy and reducing costs. Our sensors, including wall and ceiling-mounted options, are designed to comply with US Energy Codes, making them an essential component in meeting energy efficiency requirements for commercial buildings.
Uppfyll energireglerna

International Energy Conservation Code (IECC) är en modellkod framtagen av International Code Council (ICC) för att fastställa minimikrav för utformning och konstruktion avseende energieffektivitet i byggnader. IECC uppdateras vart tredje år för att inkludera de senaste metoderna och teknikerna inom energibesparing.
IECC – Varför du bör bry dig
IECC har antagits i stor utsträckning av delstater och kommuner över hela USA. IECC omfattar olika aspekter av energianvändning, inklusive byggnadsskalet (väggar, tak och fönster), värme- och kylsystem samt belysningssystem.
IECC föreskriver specifik belysningsstyrning, såsom närvarosensorer, för att minimera energislöseri i outnyttjade utrymmen i olika områden.

ANSI/ASHRAE/IES Standard 90.1, Energy Standard for Sites and Buildings Except Low-Rise Residential Buildings, är en allmänt erkänd energistandard som publiceras av American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
ASHRAE 90.1 – Varför du bör bry dig
ASHRAE 90.1 används som riktmärke för energikoder för byggnader i hela USA och fungerar som en efterlevnadsväg inom IECC, vilken anger minimikrav för energieffektiva prestanda hos komponenter i kommersiella byggnader, inklusive byggnadsskal, VVS-system, varmvattensystem och belysningssystem.
Standarden ASHRAE 90.1 anger maximalt tillåtna belysningseffekttätheter och minimikrav på belysningsstyrning, inklusive användning av närvarosensorer inom specifika områden.

Title 24, del 6 i California Building Standards Code, officiellt känd som Building Energy Efficiency Standards for Residential and Nonresidential Buildings, administreras av California Energy Commission och uppdateras regelbundet för att återspegla ny teknik och nya metoder för energieffektivitet.
Title 24 – Varför du bör bry dig
Title 24 är känd för sina stränga krav, vilka ofta anses vara striktare än de som finns i många andra energikoder i USA. Title 24 föreskriver strikta energiprestandastandarder för alla aspekter av byggnadskonstruktion, vilket inkluderar uppvärmning, ventilation, luftkonditionering (VVS), varmvatten och belysning.
Title 24 kräver installation av närvarosensorer som anpassar belysningen baserat på rumsutnyttjande i specifika utrymmen i kommersiella byggnader för att säkerställa att energi inte slösas bort.
Införande av energikoder per delstat

Expandera för att se den utförliga tabellen ↓
| Delstat | Gällande kommersiella föreskrifter | Effektivitetskategori för kommersiella föreskrifter |
|---|---|---|
| Alabama | 90.1-2013 | 90.1-2013 |
| Alaska | Inga delstatsövergripande | Inga delstatsövergripande föreskrifter |
| Arizona | Lokal självstyre | <90.1-2007 |
| Arkansas | 2009 IECC och 90.1-2007 | 90.1-2007 |
| Kalifornien | 2022 Building Energy Efficiency Standards | 90.1-2019 |
| Colorado | Lokal självstyre | Inga delstatsövergripande föreskrifter |
| Connecticut | 2021 IECC och 90.1-2019 | 90.1-2019 |
| Delaware | 2018 IECC och 90.1-2016 | 90.1-2013 |
| District of Columbia | 90.1-2013^ | 90.1-2019 |
| Florida | 2021 IECC and 90.1-2019^ | 90.1-2016 |
| Georgia | 2015 IECC and 90.1-2013^ | 90.1-2013 |
| Hawaii | Lokal självstyre | 90.1-2013 |
| Idaho | 2018 IECC och 90.1-2016 | 90.1-2013 |
| Illinois | 2021 IECC och 90.1-2019 | 90.1-2019 |
| Indiana | 90.1-2007 | 90.1-2007 |
| Iowa | 2012 IECC and 90.1-2010 | 90.1-2007 |
| Kansas | Lokal självstyre | Inga delstatsövergripande föreskrifter |
| Kentucky | 2012 IECC and 90.1-2010 | 90.1-2007 |
| Louisiana | 2021 IECC and 90.1-2019^ | 90.1-2016 |
| Maine | 2015 IECC och 90.1-2013 | 90.1-2013 |
| Maryland | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Massachusetts | 2018 IECC och 90.1-2016^ | 90.1-2019 |
| Michigan | 2015 IECC and 90.1-2013^ | 90.1-2013 |
| Minnesota | 90.1-2019^ | 90.1-2019 |
| Mississippi | Inga delstatsövergripande | Inga delstatsövergripande föreskrifter |
| Missouri | Lokal självstyre | Inga delstatsövergripande föreskrifter |
| Montana | 2021 IECC och 90.1-2019 | 90.1-2019 |
| Nebraska | 2018 IECC och 90.1-2016 | 90.1-2013 |
| Nevada | 2018 IECC och 90.1-2016 | 90.1-2013 |
| New Hampshire | 2018 IECC och 90.1-2016^ | 90.1-2013 |
| New Jersey | 90.1-2019 | 90.1-2019 |
| New Mexico | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| New York | 2018 IECC och 90.1-2016^ | 90.1-2016 |
| North Carolina | 2015 IECC and 90.1-2013^ | 90.1-2010 |
| North Dakota | Lokal självstyre | Inga delstatsövergripande föreskrifter |
| Ohio | 2021 IECC and 90.1-2019^ | 90.1-2016 |
| Oklahoma | 2006 IECC och 90.1-2004 | <90.1-2007 |
| Oregon | 90.1-2019 | 90.1-2019 |
| Pennsylvania | 2018 IECC och 90.1-2016 | 90.1-2013 |
| Rhode Island | 2018 IECC och 90.1-2016^ | 90.1-2013 |
| South Carolina | 2009 IECC och 90.1-2007 | 90.1-2007 |
| South Dakota | Lokal självstyre | Inga delstatsövergripande föreskrifter |
| Tennessee | 2021 IECC and 90.1-2013 | 90.1-2007 |
| Texas | 2015 IECC och 90.1-2013 | 90.1-2013 |
| Utah | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Vermont | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Virginia | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Washington | 2018 Washington State Energy Code | 90.1-2019 |
| Tennessee | 2012 IECC and 90.1-2010 | 90.1-2007 |
| Texas | 2015 IECC och 90.1-2013 | 90.1-2013 |
| Utah | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Vermont | 2018 IECC och 90.1-2016^ | 90.1-2019 |
| Virginia | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Washington | 2018 Washington State Energy Code | 90.1-2019 |
| West Virginia | 90.1-2013 | 90.1-2013 |
| Wisconsin | 2015 IECC and 90.1-2013^ | 90.1-2010 |
| Wyoming | Lokal självstyre | Inga delstatsövergripande föreskrifter |
- ^ When an amendment impacting energy efficiency can be quantified using DOE Prototype Building Models, they were captured in the analysis.
- For states adopting both IECC and 90.1, the IECC code is usually analyzed as the state current code in this study except for states with extensive amendments to the IECC.
Viktiga begrepp i projekteringsguiden för korridorer
Projektering av en energieffektiv belysningsstyrning för korridorer kräver strategisk placering av närvarodetektorer för att säkerställa fullständig täckning av utrymmet.

In a corridor, the primary goal is to ensure safe and well-lit passage for occupants while minimizing energy waste and all potential access points and the entire length of the corridor are covered by the sensors. Here are some design considerations:
- Sensorplacering: For long corridors, multiple sensors may be required. Ceiling-mounted sensors can be placed at regular intervals along the length of the corridor to ensure comprehensive coverage. Alternatively, wall-mounted sensors can be placed at both ends of the corridor, with their coverage areas overlapping in the middle to avoid any blind spots. Also, consider the height and range of the sensors to ensure they can effectively detect movement across the entire corridor.
- Sensortyp: Depending on the ceiling height and the presence of any potential obstructions, either ceiling-mounted or wall-mounted sensors can be used. Rayzeek’s ceiling sensors offer automatic ON and full OFF functionality, while our wall sensors provide manual ON and full OFF functionality.
- Additional Manual Controls: In addition to occupancy sensors, manual controls can be integrated for instances where manual override is necessary. These controls can be conveniently located near entrances or exits.
- Avoiding False Triggers: Sensors should be placed such that they do not directly face doors leading to other spaces, external light sources and air vents, as this could lead to false triggers when movement is detected in these adjacent spaces.
Featured Products & Solutions
Core features included:
- Integrated manual ON/OFF control for all lighting
- Vacancy sensors (Manual ON only): Lights must be turned on manually only
- Adjustable time-delay, lighting is automatically turned full OFF after 15mins
- Additional: multi-location wireless kits to expand the control range without re-wring
- Additional: multiple wiring options available for both new constructions and retrofit projects.

Meets the Mandatory Provisions
IECC – 2011
C405.2.1 Occupant sensor controls
Occupant sensor controls shall be installed to control lights in the space.
C405.2.1.1 Occupant sensor control functions
- Manual on or partial on to no more than 50% power.
- Full off within 20 minutes after all occupants have left the space
- A manual control to turn off the lights.
Full automatic-on controls with no manual control are permitted in corridors where manual operation would endanger occupant safety or security.
C405.2.1.4 Occupant sensor control function in corridors.
Occupant sensor controls in corridors shall uniformly reduce lighting power to an occupied setpoint not more than 50 percent offull power within 20 minutes after all occupants have left the space.
Exception: Corridors provided with less than two footcandles of illumination on the floor at the darkest point with all lights on.
ASHRAE 90.1 – 2022
9.4.1.1 a Local control
There shall be one or more manual lighting control device that provides ON and OFF control
of all lighting in the space.
9.4.1.1 g Automatic reduction control
The general lighting power in the space shall be automatically reduced by at least 50% within 15 minutes of all occupants leaving the space.
9.4.1.1 h Automatic full OFF control
All lighting in the space shall be automatically shut off within 15 minutes of all occupants leaving the space.
9.4.1.1 i Scheduled shutoff
All lighting in the space shall be automatically shut off during periods when the space is scheduled to be unoccupied.
** NOTE: At least one 9.4.1.1 h or 9.4.1.1 i shall be implemented.
Title 24 – 2022
130.1 (a) Manual area controls.
Each area enclosed by ceiling-height partitions shall provide lighting controls that allow the lighting in that area to be manually turned on and off.
130.1 (c) Shut-OFF Controls.
In corridors, lighting shall be controlled by Full or partial-OFF occupant sensing controls that separately reduce the lighting power in each space by at least 50 percent when the space is unoccupied. The occupant sensing controls shall be capable of automatically turning the lighting fully ON only in the separately controlled space, and shall be automatically activated from all designed paths of egress.