Lighting the Way to Energy Efficiency in Corridors
Corridors, whether in commercial buildings, educational institutions, or healthcare facilities, are high-traffic areas that often remain illuminated throughout the day, leading to significant energy consumption. These spaces typically use fluorescent or LED lighting, which, while energy-efficient, can still contribute to high energy costs when left on unnecessarily.
The challenge lies in the fact that corridors are intermittently occupied, with periods of high foot traffic interspersed with times of vacancy. Traditional manual lighting controls can lead to lights being left on during these vacant periods, resulting in unnecessary energy waste.
By integrating our occupancy sensors into your corridor lighting system, you can ensure that lights are only on when needed, saving energy and reducing costs. Our sensors, including wall and ceiling-mounted options, are designed to comply with US Energy Codes, making them an essential component in meeting energy efficiency requirements for commercial buildings.
Cumplimiento de los códigos energéticos

El Código Internacional de Conservación de Energía (IECC) es un código modelo desarrollado por el Consejo Internacional de Códigos (ICC) para establecer los requisitos mínimos de diseño y construcción en materia de eficiencia energética en edificios. El IECC se actualiza cada tres años para incorporar las últimas prácticas y tecnologías en conservación de energía.
Por qué debería interesarle el IECC
El IECC ha sido adoptado ampliamente por estados y municipios de todo Estados Unidos. El IECC abarca diversos aspectos del uso de la energía, como la envolvente del edificio (paredes, cubiertas y ventanas), los sistemas de calefacción y climatización, y los sistemas de iluminación.
El IECC exige controles de iluminación específicos, como sensores de presencia, para minimizar el desperdicio de energía en espacios desocupados en diversas áreas.

La norma ANSI/ASHRAE/IES 90.1, Norma energética para sitios y edificios, excepto edificios residenciales de baja altura, es una norma energética ampliamente reconocida y publicada por la Sociedad Americana de Ingenieros de Calefacción, Refrigeración y Aire Acondicionado (ASHRAE).
Por qué debería interesarle la norma ASHRAE 90.1
La norma ASHRAE 90.1 se utiliza como referencia para los códigos energéticos de edificación en todo Estados Unidos y sirve como vía de cumplimiento dentro del IECC, definiendo los requisitos mínimos para el rendimiento de eficiencia energética de los componentes de los edificios comerciales, incluidos los cerramientos de los edificios, los sistemas HVAC, los sistemas de calentamiento de agua y los sistemas de iluminación.
La norma ASHRAE 90.1 especifica las densidades máximas de potencia de iluminación permitidas y los requisitos mínimos de control de iluminación, incluida la instalación de sensores de presencia en áreas específicas.

El Título 24, parte 6 del Código de Normas de Edificación de California, conocido oficialmente como las Normas de Eficiencia Energética en Edificios para Edificios Residenciales y No Residenciales (Título 24), es administrado por la Comisión de Energía de California y se actualiza periódicamente para reflejar las nuevas tecnologías y métodos de eficiencia energética.
Por qué debería interesarle el Título 24
El Título 24 es conocido por sus exigentes requisitos, a menudo considerados más estrictos que los de muchos otros códigos energéticos de Estados Unidos. El Título 24 exige normas estrictas de rendimiento energético para todos los aspectos de la construcción de edificios, como la calefacción, la ventilación, el aire acondicionado (HVAC), el calentamiento de agua y la iluminación.
El Título 24 requiere la instalación de sensores de presencia que regulen la iluminación en función de la ocupación de las salas en áreas específicas de edificios comerciales para garantizar que no se desperdicie energía.
Adopción de códigos energéticos por estado

Expand to see the detailed table ↓
| State | Current Commercial Code | Commercial Code Efficiency Category |
|---|---|---|
| Alabama | 90.1-2013 | 90.1-2013 |
| Alaska | None statewide | No statewide code |
| Arizona | Home rule | <90.1-2007 |
| Arkansas | 2009 IECC and 90.1-2007 | 90.1-2007 |
| California | 2022 Building Energy Efficiency Standards | 90.1-2019 |
| Colorado | Home rule | No statewide code |
| Connecticut | 2021 IECC and 90.1-2019 | 90.1-2019 |
| Delaware | 2018 IECC and 90.1-2016 | 90.1-2013 |
| District of Columbia | 90.1-2013^ | 90.1-2019 |
| Florida | 2021 IECC and 90.1-2019^ | 90.1-2016 |
| Georgia | 2015 IECC and 90.1-2013^ | 90.1-2013 |
| Hawaii | Home rule | 90.1-2013 |
| Idaho | 2018 IECC and 90.1-2016 | 90.1-2013 |
| Illinois | 2021 IECC and 90.1-2019 | 90.1-2019 |
| Indiana | 90.1-2007 | 90.1-2007 |
| Iowa | 2012 IECC and 90.1-2010 | 90.1-2007 |
| Kansas | Home rule | No statewide code |
| Kentucky | 2012 IECC and 90.1-2010 | 90.1-2007 |
| Louisiana | 2021 IECC and 90.1-2019^ | 90.1-2016 |
| Maine | 2015 IECC and 90.1-2013 | 90.1-2013 |
| Maryland | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Massachusetts | 2018 IECC and 90.1-2016^ | 90.1-2019 |
| Michigan | 2015 IECC and 90.1-2013^ | 90.1-2013 |
| Minnesota | 90.1-2019^ | 90.1-2019 |
| Mississippi | None statewide | No statewide code |
| Missouri | Home rule | No statewide code |
| Montana | 2021 IECC and 90.1-2019 | 90.1-2019 |
| Nebraska | 2018 IECC and 90.1-2016 | 90.1-2013 |
| Nevada | 2018 IECC and 90.1-2016 | 90.1-2013 |
| New Hampshire | 2018 IECC and 90.1-2016^ | 90.1-2013 |
| New Jersey | 90.1-2019 | 90.1-2019 |
| New Mexico | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| New York | 2018 IECC and 90.1-2016^ | 90.1-2016 |
| North Carolina | 2015 IECC and 90.1-2013^ | 90.1-2010 |
| North Dakota | Home rule | No statewide code |
| Ohio | 2021 IECC and 90.1-2019^ | 90.1-2016 |
| Oklahoma | 2006 IECC and 90.1-2004 | <90.1-2007 |
| Oregon | 90.1-2019 | 90.1-2019 |
| Pennsylvania | 2018 IECC and 90.1-2016 | 90.1-2013 |
| Rhode Island | 2018 IECC and 90.1-2016^ | 90.1-2013 |
| South Carolina | 2009 IECC and 90.1-2007 | 90.1-2007 |
| South Dakota | Home rule | No statewide code |
| Tennessee | 2021 IECC and 90.1-2013 | 90.1-2007 |
| Texas | 2015 IECC and 90.1-2013 | 90.1-2013 |
| Utah | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Vermont | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Virginia | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Washington | 2018 Washington State Energy Code | 90.1-2019 |
| Tennessee | 2012 IECC and 90.1-2010 | 90.1-2007 |
| Texas | 2015 IECC and 90.1-2013 | 90.1-2013 |
| Utah | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Vermont | 2018 IECC and 90.1-2016^ | 90.1-2019 |
| Virginia | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Washington | 2018 Washington State Energy Code | 90.1-2019 |
| West Virginia | 90.1-2013 | 90.1-2013 |
| Wisconsin | 2015 IECC and 90.1-2013^ | 90.1-2010 |
| Wyoming | Home rule | No statewide code |
- ^ When an amendment impacting energy efficiency can be quantified using DOE Prototype Building Models, they were captured in the analysis.
- For states adopting both IECC and 90.1, the IECC code is usually analyzed as the state current code in this study except for states with extensive amendments to the IECC.
Design Guide Key Concepts for Corridors
Designing an energy-efficient lighting control solution for corridors involves strategic placement of occupancy sensors to ensure comprehensive coverage of the space.

In a corridor, the primary goal is to ensure safe and well-lit passage for occupants while minimizing energy waste and all potential access points and the entire length of the corridor are covered by the sensors. Here are some design considerations:
- Sensor Placement: For long corridors, multiple sensors may be required. Ceiling-mounted sensors can be placed at regular intervals along the length of the corridor to ensure comprehensive coverage. Alternatively, wall-mounted sensors can be placed at both ends of the corridor, with their coverage areas overlapping in the middle to avoid any blind spots. Also, consider the height and range of the sensors to ensure they can effectively detect movement across the entire corridor.
- Tipo de sensor: Depending on the ceiling height and the presence of any potential obstructions, either ceiling-mounted or wall-mounted sensors can be used. Rayzeek’s ceiling sensors offer automatic ON and full OFF functionality, while our wall sensors provide manual ON and full OFF functionality.
- Additional Manual Controls: In addition to occupancy sensors, manual controls can be integrated for instances where manual override is necessary. These controls can be conveniently located near entrances or exits.
- Avoiding False Triggers: Sensors should be placed such that they do not directly face doors leading to other spaces, external light sources and air vents, as this could lead to false triggers when movement is detected in these adjacent spaces.
Featured Products & Solutions
Core features included:
- Integrated manual ON/OFF control for all lighting
- Vacancy sensors (Manual ON only): Lights must be turned on manually only
- Adjustable time-delay, lighting is automatically turned full OFF after 15mins
- Additional: multi-location wireless kits to expand the control range without re-wring
- Additional: multiple wiring options available for both new constructions and retrofit projects.

Meets the Mandatory Provisions
IECC – 2011
C405.2.1 Occupant sensor controls
Occupant sensor controls shall be installed to control lights in the space.
C405.2.1.1 Occupant sensor control functions
- Manual on or partial on to no more than 50% power.
- Full off within 20 minutes after all occupants have left the space
- A manual control to turn off the lights.
Full automatic-on controls with no manual control are permitted in corridors where manual operation would endanger occupant safety or security.
C405.2.1.4 Occupant sensor control function in corridors.
Occupant sensor controls in corridors shall uniformly reduce lighting power to an occupied setpoint not more than 50 percent offull power within 20 minutes after all occupants have left the space.
Exception: Corridors provided with less than two footcandles of illumination on the floor at the darkest point with all lights on.
ASHRAE 90.1 – 2022
9.4.1.1 a Local control
There shall be one or more manual lighting control device that provides ON and OFF control
of all lighting in the space.
9.4.1.1 g Automatic reduction control
The general lighting power in the space shall be automatically reduced by at least 50% within 15 minutes of all occupants leaving the space.
9.4.1.1 h Automatic full OFF control
All lighting in the space shall be automatically shut off within 15 minutes of all occupants leaving the space.
9.4.1.1 i Scheduled shutoff
All lighting in the space shall be automatically shut off during periods when the space is scheduled to be unoccupied.
** NOTE: At least one 9.4.1.1 h or 9.4.1.1 i shall be implemented.
Title 24 – 2022
130.1 (a) Manual area controls.
Each area enclosed by ceiling-height partitions shall provide lighting controls that allow the lighting in that area to be manually turned on and off.
130.1 (c) Shut-OFF Controls.
In corridors, lighting shall be controlled by Full or partial-OFF occupant sensing controls that separately reduce the lighting power in each space by at least 50 percent when the space is unoccupied. The occupant sensing controls shall be capable of automatically turning the lighting fully ON only in the separately controlled space, and shall be automatically activated from all designed paths of egress.