Corridors
Discover the energy-saving potential of corridors with Rayzeek’s occupancy sensor design guide. Uncover the power of automated lighting control in your commercial building’s passageways.

Lighting the Way to Energy Efficiency in Corridors
Corridors, whether in commercial buildings, educational institutions, or healthcare facilities, are high-traffic areas that often remain illuminated throughout the day, leading to significant energy consumption. These spaces typically use fluorescent or LED lighting, which, while energy-efficient, can still contribute to high energy costs when left on unnecessarily.
The challenge lies in the fact that corridors are intermittently occupied, with periods of high foot traffic interspersed with times of vacancy. Traditional manual lighting controls can lead to lights being left on during these vacant periods, resulting in unnecessary energy waste.
By integrating our occupancy sensors into your corridor lighting system, you can ensure that lights are only on when needed, saving energy and reducing costs. Our sensors, including wall and ceiling-mounted options, are designed to comply with US Energy Codes, making them an essential component in meeting energy efficiency requirements for commercial buildings.
Cumpra os Códigos de Energia

O International Energy Conservation Code (IECC) é um código modelo desenvolvido pelo International Code Council (ICC) para estabelecer requisitos mínimos de design e construção para a eficiência energética nos edifícios. O IECC é atualizado a cada três anos para incorporar as últimas práticas e tecnologias de conservação de energia.
IECC, Por Que Deve Preocupar-Se
O IECC é amplamente adotado por estados e municípios em todo os Estados Unidos. O IECC abrange vários aspetos do uso de energia, incluindo o envelope do edifício (paredes, tetos e janelas), sistemas de aquecimento e arrefecimento, e sistemas de iluminação.
O IECC exige controlos de iluminação específicos, como sensores de ocupação, para minimizar o desperdício de energia em espaços desocupados em várias áreas.

O padrão ANSI/ASHRAE/IES 90.1, Padrão de Energia para Locais e Edifícios Exceto Edifícios Resenciais de Baixa Elevação, é um padrão de energia amplamente reconhecido, publicado pela American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
ASHRAE 90.1, Por Que Deve Preocupar-Se
O ASHRAE 90.1 é usado como referência para os códigos de energia de edifícios em todo os Estados Unidos e serve como caminho de conformidade dentro do IECC, que descreve os requisitos mínimos para o desempenho energético eficiente dos componentes de edifícios comerciais, incluindo envelopes de edifícios, sistemas HVAC, sistemas de aquecimento de água e sistemas de iluminação.
O padrão ASHRAE 90.1 especifica as densidades de potência de iluminação máximas permitidas e os requisitos mínimos de controlo de iluminação, incluindo o uso de sensores de ocupação em áreas específicas.

O Título 24, parte 6 do California Building Standards Code, oficialmente conhecido como Building Energy Efficiency Standards for Residential and Nonresidential Buildings, é administrado pela California Energy Commission e é atualizado periodicamente para refletir novas tecnologias e métodos de eficiência energética.
Título 24, Por Que Deve Preocupar-Se
O Título 24 é conhecido pelos seus requisitos rigorosos, frequentemente considerados mais rigorosos do que os encontrados em muitos outros códigos de energia em todo os Estados Unidos. O Título 24 exige padrões rigorosos de desempenho energético para todos os aspetos da construção de edifícios, o que inclui aquecimento, ventilação, ar condicionado (HVAC), aquecimento de água e iluminação.
O Título 24 exige a instalação de sensores de ocupação que ajustam a iluminação com base na ocupação do espaço em áreas específicas de edifícios comerciais para garantir que a energia não seja desperdiçada.
Adoção do Código de Energia por Estado

Expanda para ver a tabela detalhada ↓
| Estado | Código Comercial Atual | Categoria de Eficiência do Código Comercial |
|---|---|---|
| Alabama | 90.1-2013 | 90.1-2013 |
| Alasca | Nenhum estadual | Sem código estadual |
| Arizona | Governo local | <90.1-2007 |
| Arkansas | 2009 IECC e 90.1-2007 | 90.1-2007 |
| Califórnia | 2022 Building Energy Efficiency Standards | 90.1-2019 |
| Colorado | Governo local | Sem código estadual |
| Connecticut | 2021 IECC e 90.1-2019 | 90.1-2019 |
| Delaware | 2018 IECC e 90.1-2016 | 90.1-2013 |
| Distrito de Columbia | 90.1-2013^ | 90.1-2019 |
| Flórida | 2021 IECC e 90.1-2019^ | 90.1-2016 |
| Geórgia | 2015 IECC e 90.1-2013^ | 90.1-2013 |
| Havaí | Governo local | 90.1-2013 |
| Idaho | 2018 IECC e 90.1-2016 | 90.1-2013 |
| Illinois | 2021 IECC e 90.1-2019 | 90.1-2019 |
| Indiana | 90.1-2007 | 90.1-2007 |
| Iowa | IECC 2012 e 90.1-2010 | 90.1-2007 |
| Kansas | Governo local | Sem código estadual |
| Kentucky | IECC 2012 e 90.1-2010 | 90.1-2007 |
| Louisiana | 2021 IECC e 90.1-2019^ | 90.1-2016 |
| Maine | IECC 2015 e 90.1-2013 | 90.1-2013 |
| Maryland | 2021 IECC e 90.1-2019^ | 90.1-2019 |
| Massachusetts | IECC 2018 e 90.1-2016^ | 90.1-2019 |
| Michigan | 2015 IECC e 90.1-2013^ | 90.1-2013 |
| Minnesota | 90.1-2019^ | 90.1-2019 |
| Mississippi | Nenhum estadual | Sem código estadual |
| Missouri | Governo local | Sem código estadual |
| Montana | 2021 IECC e 90.1-2019 | 90.1-2019 |
| Nebraska | 2018 IECC e 90.1-2016 | 90.1-2013 |
| Nevada | 2018 IECC e 90.1-2016 | 90.1-2013 |
| New Hampshire | IECC 2018 e 90.1-2016^ | 90.1-2013 |
| New Jersey | 90.1-2019 | 90.1-2019 |
| New Mexico | 2021 IECC e 90.1-2019^ | 90.1-2019 |
| New York | IECC 2018 e 90.1-2016^ | 90.1-2016 |
| North Carolina | 2015 IECC e 90.1-2013^ | 90.1-2010 |
| North Dakota | Governo local | Sem código estadual |
| Ohio | 2021 IECC e 90.1-2019^ | 90.1-2016 |
| Oklahoma | IECC 2006 e 90.1-2004 | <90.1-2007 |
| Oregon | 90.1-2019 | 90.1-2019 |
| Pennsylvania | 2018 IECC e 90.1-2016 | 90.1-2013 |
| Rhode Island | IECC 2018 e 90.1-2016^ | 90.1-2013 |
| South Carolina | 2009 IECC e 90.1-2007 | 90.1-2007 |
| South Dakota | Governo local | Sem código estadual |
| Tennessee | IECC 2021 e 90.1-2013 | 90.1-2007 |
| Texas | IECC 2015 e 90.1-2013 | 90.1-2013 |
| Utah | 2021 IECC e 90.1-2019^ | 90.1-2019 |
| Vermont | 2021 IECC e 90.1-2019^ | 90.1-2019 |
| Virginia | 2021 IECC e 90.1-2019^ | 90.1-2019 |
| Washington | Código de Energia do Estado de Washington 2018 | 90.1-2019 |
| Tennessee | IECC 2012 e 90.1-2010 | 90.1-2007 |
| Texas | IECC 2015 e 90.1-2013 | 90.1-2013 |
| Utah | 2021 IECC e 90.1-2019^ | 90.1-2019 |
| Vermont | IECC 2018 e 90.1-2016^ | 90.1-2019 |
| Virginia | 2021 IECC e 90.1-2019^ | 90.1-2019 |
| Washington | Código de Energia do Estado de Washington 2018 | 90.1-2019 |
| West Virginia | 90.1-2013 | 90.1-2013 |
| Wisconsin | 2015 IECC e 90.1-2013^ | 90.1-2010 |
| Wyoming | Governo local | Sem código estadual |
- ^ Quando uma emenda com impacto na eficiência energética pode ser quantificada usando os Modelos de Edifícios Protótipo do DOE, ela foi incluída na análise.
- Para estados que adotam tanto o IECC como o 90.1, o código IECC é geralmente analisado como o código estadual atual neste estudo, exceto para estados com extensas emendas ao IECC.
Design Guide Key Concepts for Corridors
Designing an energy-efficient lighting control solution for corridors involves strategic placement of occupancy sensors to ensure comprehensive coverage of the space.

In a corridor, the primary goal is to ensure safe and well-lit passage for occupants while minimizing energy waste and all potential access points and the entire length of the corridor are covered by the sensors. Here are some design considerations:
- Sensor Placement: For long corridors, multiple sensors may be required. Ceiling-mounted sensors can be placed at regular intervals along the length of the corridor to ensure comprehensive coverage. Alternatively, wall-mounted sensors can be placed at both ends of the corridor, with their coverage areas overlapping in the middle to avoid any blind spots. Also, consider the height and range of the sensors to ensure they can effectively detect movement across the entire corridor.
- Sensor Type: Depending on the ceiling height and the presence of any potential obstructions, either ceiling-mounted or wall-mounted sensors can be used. Rayzeek’s ceiling sensors offer automatic ON and full OFF functionality, while our wall sensors provide manual ON and full OFF functionality.
- Additional Manual Controls: In addition to occupancy sensors, manual controls can be integrated for instances where manual override is necessary. These controls can be conveniently located near entrances or exits.
- Avoiding False Triggers: Sensors should be placed such that they do not directly face doors leading to other spaces, external light sources and air vents, as this could lead to false triggers when movement is detected in these adjacent spaces.
Produtos e Soluções em Destaque
Características principais incluídas:
- Controlo manual integrado para ligar/desligar toda a iluminação
- Sensores de vacância (Apenas Manual ON): As luzes devem ser ligadas apenas manualmente
- Tempo de atraso ajustável, a iluminação desliga-se automaticamente completamente após 15 minutos
- Adicional: kits sem fios multi-localização para expandir o alcance de controlo sem refazer a fiação
- Adicional: múltiplas opções de fiação disponíveis tanto para novas construções como para projetos de retrofit.

Cumprimento das Disposições Obrigatórias
IECC – 2011
C405.2.1 Controlos de sensor de ocupante
Devem ser instalados controlos de sensor de ocupante para controlar as luzes no espaço.
C405.2.1.1 Funções de controlo do sensor de ocupante
- Ligação manual ou parcial a uma potência não superior a 50%.
- Desligamento completo dentro de 20 minutos após todos os ocupantes terem saído do espaço
- Um controlo manual para desligar as luzes.
Full automatic-on controls with no manual control are permitted in corridors where manual operation would endanger occupant safety or security.
C405.2.1.4 Occupant sensor control function in corridors.
Occupant sensor controls in corridors shall uniformly reduce lighting power to an occupied setpoint not more than 50 percent offull power within 20 minutes after all occupants have left the space.
Exception: Corridors provided with less than two footcandles of illumination on the floor at the darkest point with all lights on.
ASHRAE 90.1 – 2022
9.4.1.1 a Controlo local
Deve haver um ou mais dispositivos de controlo manual de iluminação que proporcionem controlo LIGAR e DESLIGAR
de toda a iluminação no espaço.
9.4.1.1 g Automatic reduction control
The general lighting power in the space shall be automatically reduced by at least 50% within 15 minutes of all occupants leaving the space.
9.4.1.1 h Automatic full OFF control
All lighting in the space shall be automatically shut off within 15 minutes of all occupants leaving the space.
9.4.1.1 i Scheduled shutoff
All lighting in the space shall be automatically shut off during periods when the space is scheduled to be unoccupied.
** NOTE: At least one 9.4.1.1 h or 9.4.1.1 i shall be implemented.
Title 24 – 2022
130.1 (a) Controlos manuais de área.
Cada área delimitada por divisórias que atinjam o teto deve dispor de controlos de iluminação que permitam ligar e desligar manualmente a iluminação nessa área.
130.1 (c) Controlos de desligamento.
In corridors, lighting shall be controlled by Full or partial-OFF occupant sensing controls that separately reduce the lighting power in each space by at least 50 percent when the space is unoccupied. The occupant sensing controls shall be capable of automatically turning the lighting fully ON only in the separately controlled space, and shall be automatically activated from all designed paths of egress.