Open Offices
Uncover the power of automated lighting control in enhancing efficiency and reducing energy waste. Learn how to optimize lighting control for efficiency and comfort in your workspace.

Revolutionize Your Open Office Lighting with Smart Occupancy Sensors
Open offices, characterized by their large areas and cubicle partitions, are a common sight in many modern workplaces. These spaces are typically bustling with activity, filled with employees working, collaborating, and moving around. The expansive area requires ample illumination, often provided by high-intensity light fixtures. These lights, left on throughout the workday, consume a substantial amount of energy. Moreover, even when the office is vacant, during off-hours or lunch breaks, the lights often remain on, leading to unnecessary energy consumption.
The high energy consumption of lighting in open offices is a concern for both environmental and economic reasons. With the increasing emphasis on energy efficiency and sustainability, businesses are seeking ways to reduce their energy footprint. Moreover, energy costs can account for a significant portion of a company’s operating expenses, making energy-saving measures a smart financial decision as well.
To address this, the integration of occupancy sensors in open offices presents a compelling solution. Occupancy sensors can automatically control lighting based on the presence of individuals in the space, significantly reducing unnecessary energy consumption. When the office is vacant, the sensors can automatically switch off or dim the lights, thereby conserving energy. With our sensors seamlessly integrated into your open office layout, you can transform your open office into an energy-efficient workspace that meets the stringent requirements of US Energy Codes.
Respecter les codes de l'énergie

L'IECC (International Energy Conservation Code) est un code modèle élaboré par l'ICC (International Code Council) afin d'établir les exigences minimales de conception et de construction pour l'efficacité énergétique des bâtiments. L'IECC est mis à jour tous les trois ans pour intégrer les dernières pratiques et technologies en matière d'économies d'énergie.
IECC, pourquoi vous devriez vous en soucier
L'IECC est largement adopté par les États et les municipalités à travers les États-Unis. L'IECC couvre divers aspects de la consommation d'énergie, notamment l'enveloppe du bâtiment (murs, toits et fenêtres), les systèmes de chauffage et de refroidissement, ainsi que les systèmes d'éclairage.
L'IECC impose des commandes d'éclairage spécifiques, telles que des détecteurs de présence, afin de minimiser le gaspillage d'énergie dans les espaces inoccupés de diverses zones.

La norme ANSI/ASHRAE/IES 90.1, Norme énergétique pour les sites et les bâtiments à l'exclusion des bâtiments résidentiels bas, est une norme énergétique largement reconnue publiée par l'American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
ASHRAE 90.1, pourquoi vous devriez vous en soucier
La norme ASHRAE 90.1 sert de référence pour les codes énergétiques du bâtiment à travers les États-Unis et constitue une voie de conformité au sein de l'IECC. Elle définit les exigences minimales en matière de performance d'efficacité énergétique des composants des bâtiments commerciaux, y compris les enveloppes de bâtiment, les systèmes CVC, les systèmes de chauffage de l'eau et les systèmes d'éclairage.
La norme ASHRAE 90.1 spécifie les densités de puissance d'éclairage maximales autorisées et les exigences minimales en matière de contrôle de l'éclairage, notamment l'utilisation de détecteurs de présence dans des zones spécifiques.

Titre 24, partie 6 du California Building Standards Code, officiellement connu sous le nom de Building Energy Efficiency Standards for Residential and Nonresidential Buildings, le Titre 24 est administré par la California Energy Commission et est mis à jour périodiquement pour refléter les nouvelles technologies et méthodes d'efficacité énergétique.
Titre 24, pourquoi vous devriez vous en soucier
Le Titre 24 est reconnu pour ses exigences rigoureuses, souvent considérées comme plus strictes que celles de nombreux autres codes énergétiques aux États-Unis. Le Titre 24 impose des normes de performance énergétique strictes pour tous les aspects de la construction de bâtiments, ce qui comprend le chauffage, la ventilation, la climatisation (CVC), le chauffage de l'eau et l'éclairage.
Le Titre 24 exige l'installation de détecteurs de présence qui ajustent l'éclairage en fonction de l'occupation des pièces dans des zones spécifiques des bâtiments commerciaux pour garantir que l'énergie ne soit pas gaspillée.
Adoption des codes énergétiques par État

Développer pour voir le tableau détaillé ↓
| État | Code commercial actuel | Catégorie d'efficacité du code commercial |
|---|---|---|
| Alabama | 90.1-2013 | 90.1-2013 |
| Alaska | Aucun à l'échelle de l'État | Pas de code à l'échelle de l'État |
| Arizona | Autonomie communale | <90.1-2007 |
| Arkansas | IECC 2009 et 90.1-2007 | 90.1-2007 |
| Californie | Normes d'efficacité énergétique des bâtiments de 2022 | 90.1-2019 |
| Colorado | Autonomie communale | Pas de code à l'échelle de l'État |
| Connecticut | IECC 2021 et 90.1-2019 | 90.1-2019 |
| Delaware | IECC 2018 et 90.1-2016 | 90.1-2013 |
| District de Columbia | 90.1-2013^ | 90.1-2019 |
| Floride | IECC 2021 et 90.1-2019^ | 90.1-2016 |
| Géorgie | IECC 2015 et 90.1-2013^ | 90.1-2013 |
| Hawaï | Autonomie communale | 90.1-2013 |
| Idaho | IECC 2018 et 90.1-2016 | 90.1-2013 |
| Illinois | IECC 2021 et 90.1-2019 | 90.1-2019 |
| Indiana | 90.1-2007 | 90.1-2007 |
| Iowa | IECC 2012 et ASHRAE 90.1-2010 | 90.1-2007 |
| Kansas | Autonomie communale | Pas de code à l'échelle de l'État |
| Kentucky | IECC 2012 et ASHRAE 90.1-2010 | 90.1-2007 |
| Louisiane | IECC 2021 et 90.1-2019^ | 90.1-2016 |
| Maine | IECC 2015 et ASHRAE 90.1-2013 | 90.1-2013 |
| Maryland | IECC 2021 et 90.1-2019^ | 90.1-2019 |
| Massachusetts | IECC 2018 et ASHRAE 90.1-2016^ | 90.1-2019 |
| Michigan | IECC 2015 et 90.1-2013^ | 90.1-2013 |
| Minnesota | 90.1-2019^ | 90.1-2019 |
| Mississippi | Aucun à l'échelle de l'État | Pas de code à l'échelle de l'État |
| Missouri | Autonomie communale | Pas de code à l'échelle de l'État |
| Montana | IECC 2021 et 90.1-2019 | 90.1-2019 |
| Nebraska | IECC 2018 et 90.1-2016 | 90.1-2013 |
| Nevada | IECC 2018 et 90.1-2016 | 90.1-2013 |
| Nouveau-Hampshire | IECC 2018 et ASHRAE 90.1-2016^ | 90.1-2013 |
| New Jersey | 90.1-2019 | 90.1-2019 |
| Nouveau-Mexique | IECC 2021 et 90.1-2019^ | 90.1-2019 |
| New York | IECC 2018 et ASHRAE 90.1-2016^ | 90.1-2016 |
| Caroline du Nord | IECC 2015 et 90.1-2013^ | 90.1-2010 |
| Dakota du Nord | Autonomie communale | Pas de code à l'échelle de l'État |
| Ohio | IECC 2021 et 90.1-2019^ | 90.1-2016 |
| Oklahoma | 2006 IECC et 90.1-2004 | <90.1-2007 |
| Oregon | 90.1-2019 | 90.1-2019 |
| Pennsylvanie | IECC 2018 et 90.1-2016 | 90.1-2013 |
| Rhode Island | IECC 2018 et ASHRAE 90.1-2016^ | 90.1-2013 |
| Caroline du Sud | IECC 2009 et 90.1-2007 | 90.1-2007 |
| Dakota du Sud | Autonomie communale | Pas de code à l'échelle de l'État |
| Tennessee | 2021 IECC et 90.1-2013 | 90.1-2007 |
| Texas | IECC 2015 et ASHRAE 90.1-2013 | 90.1-2013 |
| Utah | IECC 2021 et 90.1-2019^ | 90.1-2019 |
| Vermont | IECC 2021 et 90.1-2019^ | 90.1-2019 |
| Virginie | IECC 2021 et 90.1-2019^ | 90.1-2019 |
| Washington | Code de l'énergie de l'État de Washington 2018 | 90.1-2019 |
| Tennessee | IECC 2012 et ASHRAE 90.1-2010 | 90.1-2007 |
| Texas | IECC 2015 et ASHRAE 90.1-2013 | 90.1-2013 |
| Utah | IECC 2021 et 90.1-2019^ | 90.1-2019 |
| Vermont | IECC 2018 et ASHRAE 90.1-2016^ | 90.1-2019 |
| Virginie | IECC 2021 et 90.1-2019^ | 90.1-2019 |
| Washington | Code de l'énergie de l'État de Washington 2018 | 90.1-2019 |
| Gaspésie–Îles-de-la-Madeleine / Virginie-Occidentale | 90.1-2013 | 90.1-2013 |
| Wisconsin | IECC 2015 et 90.1-2013^ | 90.1-2010 |
| Wyoming | Autonomie communale | Pas de code à l'échelle de l'État |
- ^ Lorsqu'un amendement ayant un impact sur l'efficacité énergétique peut être quantifié à l'aide des modèles de bâtiments prototypes du DOE, il a été pris en compte dans l'analyse.
- Pour les États adoptant à la fois l'IECC et la norme 90.1, le code IECC est généralement analysé comme le code en vigueur de l'État dans cette étude, à l'exception des États ayant apporté des amendements importants à l'IECC.
Design Guide Key Concepts for Open Offices
Designing an energy-efficient lighting control solution for open offices involves strategic placement of occupancy sensors to ensure comprehensive coverage of the space.

In an open office setting, the primary areas to consider for sensor placement are the main walkways and areas with high foot traffic. These areas are crucial for sensor placement as they are the main areas of human traffic:
- Cover Main Walkways: The main walkways in an open office are the areas with the highest foot traffic. Therefore, these should be the primary focus when placing sensors. Ceiling-mounted sensors are ideal for these areas as they provide a wide coverage area and are strategically placed to cover the entire length.
- Overlap Coverage on Walkways: To avoid blind spots, ensure that the coverage patterns of the sensors overlap along the walkways. This ensures continuous detection as people move through the space, preventing any gaps in sensor coverage.
- Use a Long Timeout: Given the size and activity level in open offices, use a longer timeout setting (15 or 20 minutes) on the sensors. This prevents the lights from turning off too soon when there’s no movement detected for a brief period.
- Consider Wall-Mounted Sensors: If the cubicle walls are short, consider using wall-mounted sensors in addition to ceiling-mounted ones. These can provide additional coverage and ensure that all areas of the office are monitored.
- Avoid Air Vents: Don’t place sensors near air vents. The vibration and airflow can reduce the effectiveness of the sensors. PIR sensors should not be within 4ft of an air vent, and ultrasonic sensors should not be within 6ft of an air vent.
- Commande manuelle: Incorporate manual controls that are integrated with the occupancy sensors. This allows for manual override to turn ON/OFF all lighting when necessary.
Produits et solutions en vedette
Caractéristiques principales incluses :
- Commande manuelle Marche/Arrêt intégrée pour l'ensemble de l'éclairage
- Détecteurs d'absence (allumage manuel uniquement) : les lumières doivent être allumées uniquement de manière manuelle
- Temporisation réglable, l'éclairage s'éteint automatiquement et complètement au bout de 15 min
- En option : kits sans fil multi-emplacements pour étendre la portée de contrôle sans re-câblage
- En option : plusieurs options de câblage disponibles pour les nouvelles constructions et les projets de rénovation.

Conforme aux dispositions obligatoires
IECC – 2011
C405.2.1 Commandes par détecteur de présence
Des commandes par détecteur de présence doivent être installées pour contrôler l'éclairage dans l'espace.
For open offices < 300 sq. ft:
C405.2.1.1 Fonctions de commande par détecteur de présence
- Allumage manuel ou allumage partiel à pas plus de 50% de puissance.
- Extinction complète dans les 20 minutes suivant le départ de tous les occupants de l'espace
- Une commande manuelle pour éteindre les lumières.
For open offices > 300 sq. ft:
- The general lighting shall be controlled separately in control zones with floor areas not greater than 600 sq. ft within the open plan office space.
- In each control zone, the general lighting shall be permitted to automatically turn on within the control zone. In other unoccupied zones, the general lighting shall be permitted to turn on to < 20% full power(or unaffected).
- Automatically turn off general lighting in all control zones within 20 minutes after all occupants have left the space.
- In each control zone, the general lighting shall turn off or uniformly reduce lighting power to an unoccupied setpoint of < 20% full power within 20 minutes after all occupants have left.
ASHRAE 90.1 – 2022
For open offices in any sizes:
9.4.1.1 a Commande locale
Il doit y avoir un ou plusieurs dispositifs de commande manuelle de l'éclairage assurant le contrôle MARCHE et ARRÊT
de tout l'éclairage de l'espace.
9.4.1.1 b Limité à l'allumage manuel
Aucun éclairage ne doit s'allumer automatiquement
9.4.1.1 c Restricted to partial automatic ON
No more than 50% of the lighting power for the general lighting shall be allowed to be automatically turned on
** NOTE: At least one 9.4.1.1 b or 9.4.1.1 c shall be implemented.
9.4.1.1 H Commande d'extinction automatique complète
Tout l'éclairage de l'espace doit s'éteindre automatiquement dans les 20 minutes suivant le départ de tous les occupants de l'espace
Additionally, for open offices > 300 sq. ft:
9.4.1.1 g Automatic reduction control
The general lighting power in the space shall be automatically reduced by at least 50% within 15 minutes of all occupants leaving the space.
Titre 24 – 2022
For open offices in any sizes:
130.1 (a) Commandes manuelles de zone.
Chaque zone délimitée par des cloisons jusqu'au plafond doit être équipée de commandes d'éclairage permettant d'allumer et d'éteindre manuellement l'éclairage de cette zone.
130.1 (c) Commandes d'extinction.
Additionally, for open offices <250 sq. ft:
130.1 (c) 5. Occupant sensing controls are required for specified offices.
L'éclairage doit être contrôlé par des détecteurs de présence afin d'éteindre automatiquement tout l'éclairage dans un délai maximal de 20 minutes après que la zone de contrôle n'est plus occupée, fonctionnant soit comme :
- A. Commandes par détecteur de présence (si la section 130.1(b) ne requiert pas de commandes d'éclairage multiniveau) ; ou
- B. Commandes par détecteur de présence avec allumage partiel (Partial-ON), ou
- C. Commandes par détecteur d'absence, où tout l'éclairage réagit uniquement à une commande d'allumage manuel
Additionally, for open offices > 250 sq. ft:
130.1 (c) 6. Full or partial-OFF occupant sensing controls are required for offices greater than 250 square feet.
In office spaces greater than 250 square feet, general lighting shall be controlled with occupant sensing controls that meet all of the following:
- Lighting shall be controlled separately in control zones not greater than 600 square feet. For luminaires with an embedded occupant sensor that are capable of reducing power independently from other luminaires, each luminaire can be considered its own control zone
- The occupant sensing controls shall uniformly reduce lighting power in the control zone by at least 80% full power(or off) in 20 minutes or less after the control zone is unoccupied.
- The occupant sensing controls shall automatically turn off lighting in ALL control zones in 20 minutes or less after the entire office space is unoccupied
- When occupancy is detected:
- in each control zone, lighting shall be allowed to automatically turn on to any level up to full power.
- in other control zones that are unoccupied, lighting shall operate at no more than 20% full power.