會議室

透過 Rayzeek 的佔用感應器設計指南,探索會議室的節能潛力。

利用佔用感應器最大限度提高會議室的能源效益

會議室是任何商業大樓運作不可或缺的一部分,為會議、簡報和腦力激盪環節的核心場所。這些房間通常配備高強度照明,以確保在簡報和討論期間擁有充足光線。然而,由於使用時間不固定,會議室極易造成大量能源浪費。當房間無人時,燈光經常處於開啟狀態,導致不必要的能源消耗。

Moreover, the sporadic usage of conference rooms means that they often remain vacant for extended periods, leading to unnecessary energy consumption if the lights are left on. This wastage not only impacts the building’s energy efficiency but also contributes to higher operational costs.

借助 Rayzeek 的佔用感應器,您可以將會議室轉化為高效節能的空間,滿足能源法規要求,並為環保事業作出貢獻。

符合能源法規

《國際能源節約規範》(International Energy Conservation Code,簡稱 IECC)是由國際規範委員會(International Code Council,簡稱 ICC)制定的示範規範,旨在確立建築物能源效益的最低設計與建造要求。IECC 每三年更新一次,以納入最新的能源節約實踐與技術。

IECC:為何您需要關注

IECC 已被美國各州和地方政府廣泛採用。IECC 涵蓋能源使用的多個方面,包括建築外圍結構(牆壁、屋頂和窗戶)、供暖與制冷系統,以及照明系統。

IECC 強制要求使用特定的照明控制設備(例如佔用感應器),以最大限度地減少各區域無人空間的能源浪費。

ANSI/ASHRAE/IES Standard 90.1(除低層住宅建築外的地點與建築能源標準)是由美國採暖、制冷與空調工程師學會(ASHRAE)發布的廣受認可之能源標準。

ASHRAE 90.1:為何您需要關注

ASHRAE 90.1 被用作全美建築能源法規的基準,並作為 IECC 內部的合規途徑,其中概述了商業建築組件(包括建築外圍結構、HVAC 系統、水加熱系統和照明系統)能源效益表現的最低要求。

ASHRAE 90.1 標準規定了最大允許照明功率密度和最低照明控制要求,包括在特定區域使用佔用感應器。

Title 24 為加州建築標準法規第 6 部分,官方稱為《住宅與非住宅建築能源效益標準》。Title 24 由加州能源委員會管理,並定期更新以反映新的能源效益技術與方法。

Title 24:為何您需要關注

Title 24 以其嚴格的要求而聞名,通常被認為比美國許多其他能源法規更為嚴格。Title 24 對建築施工的所有方面(包括供暖、通風、空調 (HVAC)、水加熱和照明)都制定了嚴格的能源表現標準。

Title 24 要求在商業建築的特定區域安裝佔用感應器,根據房間的佔用情況調節燈光,以確保不會浪費能源。

按州劃分的能源法規採用情況

展開以查看詳細表格 ↓

州份現行商業法規商業法規效益類別
阿拉巴馬州90.1-201390.1-2013
阿拉斯加州無全州統一規範無全州統一法規
亞利桑那州地方自治<90.1-2007
阿肯色州2009 IECC 及 90.1-200790.1-2007
加利福尼亞州2022年建築能源效益標準90.1-2019
科羅拉多州地方自治無全州統一法規
康涅狄格州2021 IECC 及 90.1-201990.1-2019
特拉華州2018 IECC 及 90.1-201690.1-2013
哥倫比亞特區90.1-2013^90.1-2019
佛羅里達州2021 IECC 及 90.1-2019^90.1-2016
佐治亞州2015 IECC 及 90.1-2013^90.1-2013
夏威夷州地方自治90.1-2013
愛達荷州2018 IECC 及 90.1-201690.1-2013
伊利諾伊州2021 IECC 及 90.1-201990.1-2019
印第安納州90.1-200790.1-2007
愛荷華州2012 IECC 與 90.1-201090.1-2007
堪薩斯州地方自治無全州統一法規
肯塔基州2012 IECC 與 90.1-201090.1-2007
路易斯安那州2021 IECC 及 90.1-2019^90.1-2016
緬因州2015 IECC 與 90.1-201390.1-2013
馬里蘭州2021 IECC 及 90.1-2019^90.1-2019
麻省2018 IECC 與 90.1-2016^90.1-2019
密歇根州2015 IECC 及 90.1-2013^90.1-2013
明尼蘇達州90.1-2019^90.1-2019
密西西比州無全州統一規範無全州統一法規
密蘇里州地方自治無全州統一法規
蒙大拿州2021 IECC 及 90.1-201990.1-2019
Nebraska2018 IECC 及 90.1-201690.1-2013
Nevada2018 IECC 及 90.1-201690.1-2013
New Hampshire2018 IECC 與 90.1-2016^90.1-2013
New Jersey90.1-201990.1-2019
New Mexico2021 IECC 及 90.1-2019^90.1-2019
New York2018 IECC 與 90.1-2016^90.1-2016
North Carolina2015 IECC 及 90.1-2013^90.1-2010
North Dakota地方自治無全州統一法規
Ohio2021 IECC 及 90.1-2019^90.1-2016
Oklahoma2006 IECC and 90.1-2004<90.1-2007
Oregon90.1-201990.1-2019
Pennsylvania2018 IECC 及 90.1-201690.1-2013
Rhode Island2018 IECC 與 90.1-2016^90.1-2013
South Carolina2009 IECC 及 90.1-200790.1-2007
South Dakota地方自治無全州統一法規
Tennessee2021 IECC and 90.1-201390.1-2007
Texas2015 IECC 與 90.1-201390.1-2013
Utah2021 IECC 及 90.1-2019^90.1-2019
Vermont2021 IECC 及 90.1-2019^90.1-2019
Virginia2021 IECC 及 90.1-2019^90.1-2019
Washington2018 Washington State Energy Code90.1-2019
Tennessee2012 IECC 與 90.1-201090.1-2007
Texas2015 IECC 與 90.1-201390.1-2013
Utah2021 IECC 及 90.1-2019^90.1-2019
Vermont2018 IECC 與 90.1-2016^90.1-2019
Virginia2021 IECC 及 90.1-2019^90.1-2019
Washington2018 Washington State Energy Code90.1-2019
West Virginia90.1-201390.1-2013
Wisconsin2015 IECC 及 90.1-2013^90.1-2010
Wyoming地方自治無全州統一法規
  • ^ When an amendment impacting energy efficiency can be quantified using DOE Prototype Building Models, they were captured in the analysis.
  • For states adopting both IECC and 90.1, the IECC code is usually analyzed as the state current code in this study except for states with extensive amendments to the IECC.

Sensor Solutions

Find out how Rayzeek can solve your energy saving challenges.

檢視所有方案

會議室設計指南核心概念

為會議室設計節能照明控制方案時,需要策略性地佈置佔空感應器,以確保全面覆蓋整個空間。

Designing an energy-efficient lighting system for a conference room involves strategic placement of occupancy sensors to ensure comprehensive coverage. Here are some guidelines to consider:

  • Entrance Coverage: Install a wall-mounted sensor near the entrance to detect when someone enters or exits the room. This sensor should be positioned high enough to avoid obstruction from the open door and should not directly face the entrance to avoid false triggers from movement outside the room.
  • Table Coverage: Place a ceiling-mounted sensor above the conference table to detect occupancy in the main area of the room. This sensor should be positioned centrally to ensure comprehensive coverage.
  • Presentation Area Coverage: If your conference room has a dedicated presentation area, consider installing an additional wall-mounted sensor to cover this space. This sensor should be positioned to avoid any potential obstructions, such as screens or projectors.
  • Wall Control: Install a wall control unit near the entrance for manual override or adjustments of the lighting settings. This control should be easily accessible upon entering or exiting the room.
  • Avoidance of Obstructions and Interference: Ensure that sensors are not placed near air vents to prevent interference from air flow or vibrations. Also, consider the height and placement of furniture to avoid blocking the sensor’s field of view.
  • Integration with Existing Systems: Our occupancy sensors can be integrated with existing lighting systems for seamless operation. They can also be programmed to turn off all lights after a certain period of inactivity, further enhancing energy efficiency.

Wall Sensor Switches

RZ020/021 Motion Sensor Switches

  • 2-wire, 3-wire, 4-wires wiring options
  • Occupancy, Vacancy, Manual ON/OFF
  • Adjustive time delay and ambient light control

Multi-Location Wireless Wall Sensors

RZ020A/021A + RZ022W Kits

  • Hardwired RZ021A/022A occupancy sensor switch
  • Wireless companion switch (RZ022W) for multi-location control

Ceiling Occupancy Sensors

RZ036

  • Hardwired occupancy sensors
  • Auto ON, auto OFF
  • Line voltage and Low voltage available

Core features included:

  • Integrated manual ON/OFF control for all lighting
  • Vacancy sensors (Manual ON only): Lights must be turned on manually only
  • Adjustable time-delay, lighting is automatically turned full OFF after 15mins
  • Additional: multi-location wireless kits to expand the control range without re-wring
  • Additional: multiple wiring options available for both new constructions and retrofit projects.

Meets the Mandatory Provisions

IECC – 2011

C405.2.1 Occupant sensor controls

Occupant sensor controls shall be installed to control lights in the space.

C405.2.1.1 Occupant sensor control functions

  • Manual on or partial on to no more than 50% power.
  • Full off within 20 minutes after all occupants have left the space
  • A manual control to turn off the lights.

ASHRAE 90.1 – 2022

9.4.1.1 a Local control

There shall be one or more manual lighting control device that provides ON and OFF control
of all lighting in the space.

9.4.1.1 b Restricted to manual ON

None of the lighting shall be automatically turned on

9.4.1.1 c Restricted to partial automatic ON

No more than 50% of the lighting power for the general lighting shall be allowed to be automatically turned on

** NOTE: At least one 9.4.1.1 b or 9.4.1.1 c shall be implemented.

9.4.1.1 h Automatic full OFF control

All lighting in the space shall be automatically shut off within 20 minutes of all occupants leaving the space

Title 24 – 2022

130.1 (a) Manual area controls.

Each area enclosed by ceiling-height partitions shall provide lighting controls that allow the lighting in that area to be manually turned on and off.

130.1 (c) Shut-OFF Controls.

Lighting shall be controlled with occupant sensing controls to automatically shut OFF all of the lighting in 20 minutes or less after the control zone is unoccupied that shall function either as:

  • A. Occupant sensing controls (if 130.1(b) not required to have multi-level lighting controls); or
  • B. Partial-ON occupant sensing controls, or
  • C. Vacancy sensing controls, where all lighting responds to a manual ON input only

Let us hear you.