Conference Rooms
Discover the energy-saving potential of your conference room with Rayzeek’s occupancy sensor design guide.

Maximize Energy Efficiency in Conference Rooms with Occupancy Sensors
Conference rooms are integral to the functioning of any commercial building, serving as the hub for meetings, presentations, and brainstorming sessions. These rooms are often equipped with high-intensity lighting to ensure visibility during presentations and discussions. However, due to their intermittent usage, they are prone to high energy wastage. Lights are often left on when the room is vacant, leading to unnecessary energy consumption.
Moreover, the sporadic usage of conference rooms means that they often remain vacant for extended periods, leading to unnecessary energy consumption if the lights are left on. This wastage not only impacts the building’s energy efficiency but also contributes to higher operational costs.
With Rayzeek’s occupancy sensors, you can transform your conference room into an energy-efficient space, meeting the requirements of energy codes and contributing to a greener environment.
ปฏิบัติตามมาตรฐานการอนุรักษ์พลังงาน

International Energy Conservation Code (IECC) คือประมวลข้อกำหนดมาตรฐานที่พัฒนาโดย International Code Council (ICC) เพื่อกำหนดข้อกำหนดขั้นต่ำด้านการออกแบบและการก่อสร้างสำหรับการใช้พลังงานอย่างมีประสิทธิภาพในอาคาร ทั้งนี้ IECC จะมีการปรับปรุงข้อมูลให้ทันสมัยในทุกๆ สามปี เพื่อรวบรวมแนวปฏิบัติและเทคโนโลยีล่าสุดด้านการอนุรักษ์พลังงาน.
ทำไมคุณจึงควรใส่ใจ IECC
IECC ได้รับการนำไปใช้อย่างแพร่หลายในรัฐและเทศบาลต่างๆ ทั่วสหรัฐอเมริกา โดย IECC ครอบคลุมการใช้พลังงานในหลากหลายแง่มุม รวมถึงกรอบอาคาร (ผนัง หลังคา และหน้าต่าง) ระบบปรับอากาศและระบายอากาศ และระบบแสงสว่าง.
IECC กำหนดให้มีการควบคุมระบบแสงสว่างเฉพาะ เช่น การใช้เซนเซอร์ตรวจจับการเปิด-ปิดไฟอัตโนมัติ เพื่อลดการสูญเสียพลังงานในพื้นที่ที่ไม่มีผู้ใช้งานตามจุดต่างๆ.

มาตรฐาน ANSI/ASHRAE/IES 90.1 (Energy Standard for Sites and Buildings Except Low-Rise Residential Buildings) เป็นมาตรฐานด้านพลังงานที่ได้รับความยินยอมรับอย่างแพร่หลาย ซึ่งจัดทำโดย American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
ทำไมคุณจึงควรใส่ใจ ASHRAE 90.1
ASHRAE 90.1 ถูกใช้เป็นเกณฑ์มาตรฐานสำหรับกฎหมายการอนุรักษ์พลังงานในอาคารทั่วสหรัฐอเมริกา และทำหน้าที่เป็นแนวทางการปฏิบัติตามข้อกำหนดภายใน IECC ซึ่งระบุข้อกำหนดขั้นต่ำสำหรับประสิทธิภาพการใช้พลังงานของส่วนประกอบในอาคารพาณิชย์ รวมถึงกรอบอาคาร ระบบ HVAC ระบบทำน้ำร้อน และระบบแสงสว่าง.
มาตรฐาน ASHRAE 90.1 ระบุความหนาแน่นกำลังไฟฟ้าสูงสุดที่อนุญาตสำหรับระบบแสงสว่าง และข้อกำหนดขั้นต่ำในการควบคุมแสงสว่าง ซึ่งรวมถึงการใช้เซนเซอร์ตรวจจับการเปิด-ปิดไฟอัตโนมัติในพื้นที่ที่กำหนด.

Title 24 Part 6 ของ California Building Standards Code หรือรู้จักกันในชื่ออย่างเป็นทางการว่า Building Energy Efficiency Standards for Residential and Nonresidential Buildings อยู่ภายใต้การกำกับดูแลของ California Energy Commission และได้รับการปรับปรุงเป็นระยะเพื่อสะท้อนถึงเทคโนโลยีและวิธีการด้านประสิทธิภาพการใช้พลังงานใหม่ๆ.
ทำไมคุณจึงควรใส่ใจ Title 24
Title 24 เป็นที่รู้จักในด้านข้อกำหนดที่เข้มงวด และมักถูกมองว่ามีความเข้มงวดมากกว่ากฎหมายการอนุรักษ์พลังงานอื่นๆ ในหลายรัฐทั่วสหรัฐอเมริกา โดย Title 24 กำหนดมาตรฐานประสิทธิภาพการใช้พลังงานที่เข้มงวดสำหรับทุกด้านของการก่อสร้างอาคาร รวมถึงระบบการทำความร้อน ระบบระบายอากาศ ระบบปรับอากาศ (HVAC) ระบบทำน้ำร้อน และระบบแสงสว่าง.
Title 24 กำหนดให้มีการติดตั้งเซนเซอร์ตรวจจับการเปิด-ปิดไฟอัตโนมัติเพื่อปรับแสงสว่างตามการเข้าใช้ห้องในพื้นที่เฉพาะของอาคารพาณิชย์ เพื่อให้มั่นใจว่าไม่มีการสูญเสียพลังงานโดยเปล่าประโยชน์.
การประกาศใช้มาตรฐานการอนุรักษ์พลังงานแยกตามรัฐ

ขยายเพื่อดูตารางรายละเอียด ↓
| State | Current Commercial Code | Commercial Code Efficiency Category |
|---|---|---|
| Alabama | 90.1-2013 | 90.1-2013 |
| Alaska | None statewide | No statewide code |
| Arizona | Home rule | <90.1-2007 |
| Arkansas | 2009 IECC and 90.1-2007 | 90.1-2007 |
| California | 2022 Building Energy Efficiency Standards | 90.1-2019 |
| Colorado | Home rule | No statewide code |
| Connecticut | 2021 IECC and 90.1-2019 | 90.1-2019 |
| Delaware | 2018 IECC and 90.1-2016 | 90.1-2013 |
| District of Columbia | 90.1-2013^ | 90.1-2019 |
| Florida | 2021 IECC and 90.1-2019^ | 90.1-2016 |
| Georgia | 2015 IECC and 90.1-2013^ | 90.1-2013 |
| Hawaii | Home rule | 90.1-2013 |
| Idaho | 2018 IECC and 90.1-2016 | 90.1-2013 |
| Illinois | 2021 IECC and 90.1-2019 | 90.1-2019 |
| Indiana | 90.1-2007 | 90.1-2007 |
| Iowa | 2012 IECC and 90.1-2010 | 90.1-2007 |
| Kansas | Home rule | No statewide code |
| Kentucky | 2012 IECC and 90.1-2010 | 90.1-2007 |
| Louisiana | 2021 IECC and 90.1-2019^ | 90.1-2016 |
| Maine | 2015 IECC and 90.1-2013 | 90.1-2013 |
| Maryland | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Massachusetts | 2018 IECC and 90.1-2016^ | 90.1-2019 |
| Michigan | 2015 IECC and 90.1-2013^ | 90.1-2013 |
| Minnesota | 90.1-2019^ | 90.1-2019 |
| Mississippi | None statewide | No statewide code |
| Missouri | Home rule | No statewide code |
| Montana | 2021 IECC and 90.1-2019 | 90.1-2019 |
| Nebraska | 2018 IECC and 90.1-2016 | 90.1-2013 |
| Nevada | 2018 IECC and 90.1-2016 | 90.1-2013 |
| New Hampshire | 2018 IECC and 90.1-2016^ | 90.1-2013 |
| New Jersey | 90.1-2019 | 90.1-2019 |
| New Mexico | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| New York | 2018 IECC and 90.1-2016^ | 90.1-2016 |
| North Carolina | 2015 IECC and 90.1-2013^ | 90.1-2010 |
| North Dakota | Home rule | No statewide code |
| Ohio | 2021 IECC and 90.1-2019^ | 90.1-2016 |
| Oklahoma | 2006 IECC and 90.1-2004 | <90.1-2007 |
| Oregon | 90.1-2019 | 90.1-2019 |
| Pennsylvania | 2018 IECC and 90.1-2016 | 90.1-2013 |
| Rhode Island | 2018 IECC and 90.1-2016^ | 90.1-2013 |
| South Carolina | 2009 IECC and 90.1-2007 | 90.1-2007 |
| South Dakota | Home rule | No statewide code |
| Tennessee | 2021 IECC and 90.1-2013 | 90.1-2007 |
| Texas | 2015 IECC and 90.1-2013 | 90.1-2013 |
| Utah | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Vermont | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Virginia | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Washington | 2018 Washington State Energy Code | 90.1-2019 |
| Tennessee | 2012 IECC and 90.1-2010 | 90.1-2007 |
| Texas | 2015 IECC and 90.1-2013 | 90.1-2013 |
| Utah | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Vermont | 2018 IECC and 90.1-2016^ | 90.1-2019 |
| Virginia | 2021 IECC and 90.1-2019^ | 90.1-2019 |
| Washington | 2018 Washington State Energy Code | 90.1-2019 |
| West Virginia | 90.1-2013 | 90.1-2013 |
| Wisconsin | 2015 IECC and 90.1-2013^ | 90.1-2010 |
| Wyoming | Home rule | No statewide code |
- ^ When an amendment impacting energy efficiency can be quantified using DOE Prototype Building Models, they were captured in the analysis.
- For states adopting both IECC and 90.1, the IECC code is usually analyzed as the state current code in this study except for states with extensive amendments to the IECC.
Design Guide Key Concepts for Conference Rooms
Designing an energy-efficient lighting control solution for conference rooms involves strategic placement of occupancy sensors to ensure comprehensive coverage of the space.

Designing an energy-efficient lighting system for a conference room involves strategic placement of occupancy sensors to ensure comprehensive coverage. Here are some guidelines to consider:
- Entrance Coverage: Install a wall-mounted sensor near the entrance to detect when someone enters or exits the room. This sensor should be positioned high enough to avoid obstruction from the open door and should not directly face the entrance to avoid false triggers from movement outside the room.
- Table Coverage: Place a ceiling-mounted sensor above the conference table to detect occupancy in the main area of the room. This sensor should be positioned centrally to ensure comprehensive coverage.
- Presentation Area Coverage: If your conference room has a dedicated presentation area, consider installing an additional wall-mounted sensor to cover this space. This sensor should be positioned to avoid any potential obstructions, such as screens or projectors.
- Wall Control: Install a wall control unit near the entrance for manual override or adjustments of the lighting settings. This control should be easily accessible upon entering or exiting the room.
- Avoidance of Obstructions and Interference: Ensure that sensors are not placed near air vents to prevent interference from air flow or vibrations. Also, consider the height and placement of furniture to avoid blocking the sensor’s field of view.
- Integration with Existing Systems: Our occupancy sensors can be integrated with existing lighting systems for seamless operation. They can also be programmed to turn off all lights after a certain period of inactivity, further enhancing energy efficiency.
Featured Products & Solutions
Core features included:
- Integrated manual ON/OFF control for all lighting
- Vacancy sensors (Manual ON only): Lights must be turned on manually only
- Adjustable time-delay, lighting is automatically turned full OFF after 15mins
- Additional: multi-location wireless kits to expand the control range without re-wring
- Additional: multiple wiring options available for both new constructions and retrofit projects.

Meets the Mandatory Provisions
IECC – 2011
C405.2.1 Occupant sensor controls
Occupant sensor controls shall be installed to control lights in the space.
C405.2.1.1 Occupant sensor control functions
- Manual on or partial on to no more than 50% power.
- Full off within 20 minutes after all occupants have left the space
- A manual control to turn off the lights.
ASHRAE 90.1 – 2022
9.4.1.1 a Local control
There shall be one or more manual lighting control device that provides ON and OFF control
of all lighting in the space.
9.4.1.1 b Restricted to manual ON
None of the lighting shall be automatically turned on
9.4.1.1 c Restricted to partial automatic ON
No more than 50% of the lighting power for the general lighting shall be allowed to be automatically turned on
** NOTE: At least one 9.4.1.1 b or 9.4.1.1 c shall be implemented.
9.4.1.1 h Automatic full OFF control
All lighting in the space shall be automatically shut off within 20 minutes of all occupants leaving the space
Title 24 – 2022
130.1 (a) Manual area controls.
Each area enclosed by ceiling-height partitions shall provide lighting controls that allow the lighting in that area to be manually turned on and off.
130.1 (c) Shut-OFF Controls.
Lighting shall be controlled with occupant sensing controls to automatically shut OFF all of the lighting in 20 minutes or less after the control zone is unoccupied that shall function either as:
- A. Occupant sensing controls (if 130.1(b) not required to have multi-level lighting controls); or
- B. Partial-ON occupant sensing controls, or
- C. Vacancy sensing controls, where all lighting responds to a manual ON input only
Let us hear you.
Let Rayzeek help design and deliver a bespoke energy-saving lighting solution for you.