Interruttore con sensore di movimento a microonde da soffitto a 360 gradi RZ047-10A
RZ047-10A
RZ047-10A is the higher-load AC version of the ceiling-mounted microwave motion sensor switch for automatic lighting control.
It keeps the same 5.8 GHz microwave sensing platform as the 5A model while using source-backed 10A load ratings for compatible 100-265 VAC lighting circuits.
- Ingresso tensione di linea 100-265 VAC, modello da 10A
- Rilevamento a microonde a 5,8 GHz con copertura a 360 gradi
- Diametro di rilevamento di 8-12 m in condizioni manuali
- Ritardo di spegnimento: da 15 s a 30 min
- Impostazione Lux: Disattivato, 15, 25 o 35 Lux
Caratteristiche principali del prodotto
- Modello CA da 10A: 100-265 VAC ceiling microwave sensor switch with higher source-backed load ratings than the 5A model.
- Rilevamento a microonde: Rilevamento Doppler a 5,8 GHz con copertura del soffitto a 360 gradi.
- Installer setup: Push-button settings for time delay, Lux threshold, and high/low sensitivity.
Non è quello che stai cercando? Visualizza il nostro catalogo:
Consulti un esperto
Consegna rapida: 99% in magazzino
Linea completa di prodotti ad attivazione motoria
Richiedi informazioni per ordini all'ingrosso ODM/OEM

Higher-Load AC Microwave Control From The Ceiling
The RZ047-10A is the higher-load AC model in the RZ047 ceiling microwave sensor family, built for automatic lighting control where a ceiling sensor is the right detection position.
Utilizza un cablaggio di fase, neutro e carico a 100-265 VAC, con regolazione manuale per il ritardo di spegnimento, la soglia Lux e la sensibilità alta/bassa dopo l'installazione.

Rilevamento CA per carichi più elevati per l'illuminazione di ambienti interni condivisi
Use the RZ047-10A when the project needs the RZ047 microwave sensing platform and the higher verified AC load profile shown in the manual.
L'installazione a soffitto è adatta per corridoi, locali condivisi, vani tecnici e spazi interni simili, a condizione che il sensore sia posizionato in modo da evitare rilevamenti indesiderati attraverso porte, finestre, pareti divisorie, superfici metalliche o apparecchiature in movimento.
Caratteristiche, vantaggi, specifiche
The RZ047-10A pairs 10A AC load ratings with 5.8 GHz microwave detection so installers can compare load capacity, room coverage, and adjustment options before ordering.

Caratteristiche e vantaggi
- 10A line-voltage control: Supports 100-265 VAC lighting circuits with the source-backed RZ047-10A load ratings shown in the specifications.
- Higher AC load profile: The 10A model is the RZ047 choice when the verified lighting load exceeds the 5A model rating.
- 5.8 GHz microwave sensing: High-frequency Doppler detection actively senses movement for ceiling-mounted automatic lighting control.
- 360-degree ceiling coverage: Ceiling placement gives broad room coverage with an 8-12 m detection diameter under manual conditions.
- Non-metal material penetration: Microwave detection can pass through many plastics, glass, and thin partitions, while metal blocks detection.
- Adjustable time delay: Choose 15 s, 30 s, 1 min, 3 min, 5 min, 10 min, or 30 min to match room traffic patterns.
- High/low sensitivity: The SENS button helps reduce nuisance detection through doors, glass, partitions, or adjacent spaces.
- Caratteristiche
-
Model
RZ047-10A
Product type
Interruttore da soffitto con sensore di movimento a microonde
Sensor type
High-frequency microwave Doppler (HF)
Microwave frequency
5.8 GHz ISM band
Transmission power
0.4 mW
Time delay
15 s, 30 s, 1 min (default), 3 min, 5 min, 10 min, 30 min
Light sensor level
Off, 15 Lux, 25 Lux (default), 35 Lux
Sensitivity
High or Low
Material penetration
Detects through most plastics, glass, and thin partitions; metal blocks detection
- Electrical
-
Alimentazione
100 VAC ~ 265 VAC
Power frequency
50/60 Hz
Cablaggio
White to Neutral; Red to Load; Black to Live
Power consumption
<=0.5 W standby; 1 W operation
Incandescent / Halogen load
1000 W / 110 VAC; 2200 W / 220 VAC
Fluorescent / Ballast / LED load
500 W / 110 VAC; 1000 W / 220 VAC
- Detection & Installation
-
Detection diameter
8-12 m
Detection range
360-degree ceiling coverage
Installation height
2.5-5 m
Working temperature
-10 to +40 C
Working humidity
< 93% RH non-condensing
Metal clearance
Keep at least 1 m from large metal or highly reflective surfaces; do not fully enclose in metal
Installation notes
Avoid windows, doors, automatic doors, rotating equipment, HVAC airflow, fans, moving machinery, and vibrating fixtures that may cause nuisance detection
FAQ
How is the RZ047-10A different from the 5A model?
The 10A model has higher verified AC load ratings. Both models use 100-265 VAC input, neutral-required wiring, and the same RZ047 ceiling microwave sensing platform.
Does the RZ047-10A need a neutral wire?
Yes. The AC wiring diagram requires White to Neutral, Red to Load, and Black to Live.
What loads can the 10A model control?
The manual lists 1000 W / 110 VAC and 2200 W / 220 VAC for incandescent or halogen loads, and 500 W / 110 VAC and 1000 W / 220 VAC for fluorescent, ballast, or LED loads.
Can microwave sensing detect through glass or partitions?
Yes. The manual states that microwave sensing can detect through most plastics, glass, and thin partitions, while metal blocks detection. Placement and sensitivity should be adjusted accordingly.
How can nuisance triggering be reduced?
Reduce sensitivity to Low or relocate the sensor to avoid doors, windows, adjacent spaces, moving machinery, HVAC airflow, fans, vibrating fixtures, and large metal or reflective surfaces.
What time delay settings are available?
Time delay settings are 15 s, 30 s, 1 min, 3 min, 5 min, 10 min, and 30 min. The manual default is 1 min.



Recensioni
Ancora non ci sono recensioni.