Open Offices

Entdecken Sie die Leistungsfähigkeit automatisierter Beleuchtungssteuerung zur Steigerung der Effizienz und zur Reduzierung von Energieverschwendung. Erfahren Sie, wie Sie die Beleuchtungssteuerung für Effizienz und Komfort in Ihrem Arbeitsbereich optimieren.

Revolutionize Your Open Office Lighting with Smart Occupancy Sensors

Open offices, characterized by their large areas and cubicle partitions, are a common sight in many modern workplaces. These spaces are typically bustling with activity, filled with employees working, collaborating, and moving around. The expansive area requires ample illumination, often provided by high-intensity light fixtures. These lights, left on throughout the workday, consume a substantial amount of energy. Moreover, even when the office is vacant, during off-hours or lunch breaks, the lights often remain on, leading to unnecessary energy consumption.

The high energy consumption of lighting in open offices is a concern for both environmental and economic reasons. With the increasing emphasis on energy efficiency and sustainability, businesses are seeking ways to reduce their energy footprint. Moreover, energy costs can account for a significant portion of a company’s operating expenses, making energy-saving measures a smart financial decision as well.

To address this, the integration of occupancy sensors in open offices presents a compelling solution. Occupancy sensors can automatically control lighting based on the presence of individuals in the space, significantly reducing unnecessary energy consumption. When the office is vacant, the sensors can automatically switch off or dim the lights, thereby conserving energy. With our sensors seamlessly integrated into your open office layout, you can transform your open office into an energy-efficient workspace that meets the stringent requirements of US Energy Codes.

Einhaltung der Energievorschriften

Der International Energy Conservation Code (IECC) ist ein Modellcode, der vom International Code Council (ICC) entwickelt wurde, um Mindestanforderungen an Entwurf und Bau für die Energieeffizienz von Gebäuden festzulegen. Der IECC wird alle drei Jahre aktualisiert, um die neuesten Praktiken und Technologien der Energiesparung zu berücksichtigen.

IECC: Warum es Sie interessieren sollte

Der IECC wird von den US-Bundesstaaten und Gemeinden weithin übernommen. Der IECC deckt verschiedene Aspekte des Energieverbrauchs ab, einschließlich der Gebäudehülle (Wände, Dächer und Fenster), Heiz- und Kühlsysteme sowie Beleuchtungssysteme.

Der IECC schreibt spezifische Beleuchtungssteuerungen vor, wie z. B. Belegungssensoren, um Energieverschwendung in unbesetzten Räumen in verschiedenen Bereichen zu minimieren.

ANSI/ASHRAE/IES Standard 90.1, Energienorm für Standorte und Gebäude mit Ausnahme von niedrigen Wohngebäuden, ist eine weithin anerkannte Energienorm, die von der American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) veröffentlicht wird.

ASHRAE 90.1: Warum es Sie interessieren sollte

ASHRAE 90.1 dient als Referenzwert für Gebäude-Energievorschriften in den gesamten USA und ist ein Konformitätsweg innerhalb des IECC, der Mindestanforderungen an die energieeffiziente Leistung von Komponenten gewerblicher Gebäude skizziert, einschließlich Gebäudehüllen, HLK-Systemen, Warmwassersystemen und Beleuchtungssystemen.

Die Norm ASHRAE 90.1 legt maximal zulässige Beleuchtungsleistungsdichten und Mindestanforderungen an die Beleuchtungssteuerung fest, einschließlich der Verwendung von Belegungssensoren in bestimmten Bereichen.

Title 24, Teil 6 des California Building Standards Code, offiziell bekannt als die Building Energy Efficiency Standards for Residential and Nonresidential Buildings (Gebäudeenergieeffizienzstandards für Wohn- und Nichtwohngebäude), wird von der California Energy Commission verwaltet und regelmäßig aktualisiert, um neue Energieeffizienztechnologien und -methoden widerzuspiegeln.

Title 24: Warum es Sie interessieren sollte

Title 24 ist für seine strengen Anforderungen bekannt, die oft als strenger angesehen werden als die vieler anderer Energievorschriften in den USA. Title 24 schreibt strenge Energiestandards für alle Aspekte des Gebäudebaus vor, einschließlich Heizung, Lüftung, Klimaanlage (HLK), Warmwasserbereitung und Beleuchtung.

Title 24 verlangt die Installation von Belegungssensoren, die die Beleuchtung basierend auf der Raumnutzung in bestimmten Bereichen gewerblicher Gebäude anpassen, um sicherzustellen, dass keine Energie verschwendet wird.

Übernahme der Energievorschriften nach Bundesstaat

Erweitern, um die detaillierte Tabelle anzuzeigen ↓

BundesstaatAktuelle Gewerbliche VorschriftEffizienzkategorie der Gewerblichen Vorschrift
Alabama90.1-201390.1-2013
AlaskaKeine bundesstaatliche VorschriftKeine bundesstaatliche Vorschrift
ArizonaHome Rule<90.1-2007
Arkansas2009 IECC und 90.1-200790.1-2007
Kalifornien2022 Building Energy Efficiency Standards90.1-2019
ColoradoHome RuleKeine bundesstaatliche Vorschrift
Connecticut2021 IECC und 90.1-201990.1-2019
Delaware2018 IECC und 90.1-201690.1-2013
District of Columbia90.1-2013^90.1-2019
Florida2021 IECC und 90.1-2019^90.1-2016
Georgia2015 IECC und 90.1-2013^90.1-2013
HawaiiHome Rule90.1-2013
Idaho2018 IECC und 90.1-201690.1-2013
Illinois2021 IECC und 90.1-201990.1-2019
Indiana90.1-200790.1-2007
Iowa2012 IECC und 90.1-201090.1-2007
KansasHome RuleKeine bundesstaatliche Vorschrift
Kentucky2012 IECC und 90.1-201090.1-2007
Louisiana2021 IECC und 90.1-2019^90.1-2016
Maine2015 IECC und 90.1-201390.1-2013
Maryland2021 IECC und 90.1-2019^90.1-2019
Massachusetts2018 IECC und 90.1-2016^90.1-2019
Michigan2015 IECC und 90.1-2013^90.1-2013
Minnesota90.1-2019^90.1-2019
MississippiKeine bundesstaatliche VorschriftKeine bundesstaatliche Vorschrift
MissouriHome RuleKeine bundesstaatliche Vorschrift
Montana2021 IECC und 90.1-201990.1-2019
Nebraska2018 IECC und 90.1-201690.1-2013
Nevada2018 IECC und 90.1-201690.1-2013
New Hampshire2018 IECC und 90.1-2016^90.1-2013
New Jersey90.1-201990.1-2019
New Mexico2021 IECC und 90.1-2019^90.1-2019
New York2018 IECC und 90.1-2016^90.1-2016
North Carolina2015 IECC und 90.1-2013^90.1-2010
North DakotaHome RuleKeine bundesstaatliche Vorschrift
Ohio2021 IECC und 90.1-2019^90.1-2016
Oklahoma2006 IECC und 90.1-2004<90.1-2007
Oregon90.1-201990.1-2019
Pennsylvania2018 IECC und 90.1-201690.1-2013
Rhode Island2018 IECC und 90.1-2016^90.1-2013
South Carolina2009 IECC und 90.1-200790.1-2007
South DakotaHome RuleKeine bundesstaatliche Vorschrift
Tennessee2021 IECC und 90.1-201390.1-2007
Texas2015 IECC und 90.1-201390.1-2013
Utah2021 IECC und 90.1-2019^90.1-2019
Vermont2021 IECC und 90.1-2019^90.1-2019
Virginia2021 IECC und 90.1-2019^90.1-2019
WashingtonWashington State Energiecode 201890.1-2019
Tennessee2012 IECC und 90.1-201090.1-2007
Texas2015 IECC und 90.1-201390.1-2013
Utah2021 IECC und 90.1-2019^90.1-2019
Vermont2018 IECC und 90.1-2016^90.1-2019
Virginia2021 IECC und 90.1-2019^90.1-2019
WashingtonWashington State Energiecode 201890.1-2019
West Virginia90.1-201390.1-2013
Wisconsin2015 IECC und 90.1-2013^90.1-2010
WyomingHome RuleKeine bundesstaatliche Vorschrift
  • ^ Wenn eine Änderung, die die Energieeffizienz beeinflusst, mit DOE-Prototypgebäudemodellen quantifiziert werden konnte, wurde sie in die Analyse einbezogen.
  • Für Staaten, die sowohl den IECC als auch 90.1 annehmen, wird in dieser Studie in der Regel der IECC-Code als aktueller Code des Staates analysiert, mit Ausnahme von Staaten mit umfangreichen Änderungen am IECC.

Sensorlösungen

Erfahren Sie, wie Rayzeek Ihre Herausforderungen bei der Energieeinsparung lösen kann.

Alle Angebote anzeigen

Design Guide Key Concepts for Open Offices

Designing an energy-efficient lighting control solution for open offices involves strategic placement of occupancy sensors to ensure comprehensive coverage of the space.

In an open office setting, the primary areas to consider for sensor placement are the main walkways and areas with high foot traffic. These areas are crucial for sensor placement as they are the main areas of human traffic:

  • Cover Main Walkways: The main walkways in an open office are the areas with the highest foot traffic. Therefore, these should be the primary focus when placing sensors. Ceiling-mounted sensors are ideal for these areas as they provide a wide coverage area and are strategically placed to cover the entire length.
  • Overlap Coverage on Walkways: To avoid blind spots, ensure that the coverage patterns of the sensors overlap along the walkways. This ensures continuous detection as people move through the space, preventing any gaps in sensor coverage.
  • Use a Long Timeout: Given the size and activity level in open offices, use a longer timeout setting (15 or 20 minutes) on the sensors. This prevents the lights from turning off too soon when there’s no movement detected for a brief period.
  • Consider Wall-Mounted Sensors: If the cubicle walls are short, consider using wall-mounted sensors in addition to ceiling-mounted ones. These can provide additional coverage and ensure that all areas of the office are monitored.
  • Avoid Air Vents: Don’t place sensors near air vents. The vibration and airflow can reduce the effectiveness of the sensors. PIR sensors should not be within 4ft of an air vent, and ultrasonic sensors should not be within 6ft of an air vent.
  • Manuelle Steuerung: Incorporate manual controls that are integrated with the occupancy sensors. This allows for manual override to turn ON/OFF all lighting when necessary.

Wandsensor-Schalter

RZ020/021 Bewegungssensor-Schalter

  • 2-Draht-, 3-Draht-, 4-Draht-Verdrahtungsoptionen
  • Präsenz, Abwesenheit, Manuell EIN/AUS
  • Einstellbare Zeitverzögerung und Umgebungslichtsteuerung

Kabellose Mehrfachpositions-Wandsensoren

RZ020A/021A + RZ022W Kits

  • Verkabelter RZ021A/022A Präsenzsensor-Schalter
  • Kabelloser Begleitschalter (RZ022W) für Mehrfachpositionssteuerung

Decken-Präsenzsensoren

RZ036

  • Verkabelte Präsenzsensoren
  • Automatisch EIN, automatisch AUS
  • Netzspannung und Niederspannung verfügbar

Kernfunktionen enthalten:

  • Integrierte manuelle EIN/AUS-Steuerung für die gesamte Beleuchtung
  • Abwesenheitssensoren (nur Manuell EIN): Lichter müssen nur manuell eingeschaltet werden
  • Einstellbare Zeitverzögerung, die Beleuchtung wird nach 15 Minuten automatisch vollständig AUSgeschaltet
  • Zusätzlich: kabellose Mehrfachpositionskits zur Erweiterung des Steuerungsbereichs ohne Neuverkabelung
  • Zusätzlich: mehrere Verdrahtungsoptionen sowohl für Neubauten als auch für Nachrüstprojekte verfügbar.

Erfüllt die zwingenden Bestimmungen

IECC – 2011

C405.2.1 Personenensor-Steuerungen

Personensensor-Steuerungen sollen installiert werden, um die Beleuchtung im Raum zu steuern.

For open offices < 300 sq. ft:

C405.2.1.1 Funktionen der Personensensor-Steuerung

  • Manuell EIN oder Teil-EIN mit maximal 50% Leistung.
  • Vollständiges AUS innerhalb von 20 Minuten nachdem alle Personen den Raum verlassen haben
  • Eine manuelle Steuerung zum Ausschalten der Beleuchtung.

For open offices > 300 sq. ft:

  • The general lighting shall be controlled separately in control zones with floor areas not greater than 600 sq. ft within the open plan office space.
  • In each control zone, the general lighting shall be permitted to automatically turn on within the control zone. In other unoccupied zones, the general lighting shall be permitted to turn on to < 20% full power(or unaffected).
  • Automatically turn off general lighting in all control zones within 20 minutes after all occupants have left the space.
  • In each control zone, the general lighting shall turn off or uniformly reduce lighting power to an unoccupied setpoint of < 20% full power within 20 minutes after all occupants have left.

ASHRAE 90.1 – 2022

For open offices in any sizes:

9.4.1.1 a Lokale Steuerung

Es muss ein oder mehrere manuelle Beleuchtungssteuerungsgeräte geben, die eine EIN- und AUS-Steuerung
der gesamten Beleuchtung im Raum ermöglichen.

9.4.1.1 b Beschränkt auf manuell EIN

Keine der Beleuchtung darf automatisch eingeschaltet werden

9.4.1.1 c Beschränkt auf teilautomatisches EINSCHALTEN

Es darf höchstens 50% der Beleuchtungsleistung für die Allgemeinbeleuchtung automatisch eingeschaltet werden

** HINWEIS: Mindestens eine der Anforderungen 9.4.1.1 b oder 9.4.1.1 c muss implementiert werden.

9.4.1.1 H Automatische Voll-AUS-Steuerung

Die gesamte Beleuchtung im Raum muss innerhalb von 20 Minuten nach dem Verlassen des Raums durch alle Personen automatisch abgeschaltet werden

Additionally, for open offices > 300 sq. ft:

9.4.1.1 g Automatic reduction control

The general lighting power in the space shall be automatically reduced by at least 50% within 15 minutes of all occupants leaving the space.

Title 24 – 2022

For open offices in any sizes:

130.1 (a) Manuelle Bereichssteuerungen.

Jeder durch raumhohe Trennwände begrenzte Bereich muss Beleuchtungssteuerungen vorsehen, die es ermöglichen, die Beleuchtung in diesem Bereich manuell ein- und auszuschalten.

130.1 (c) Ausschalt-Steuerungen.

Additionally, for open offices <250 sq. ft:

130.1 (c) 5. Occupant sensing controls are required for specified offices.

Die Beleuchtung muss mit Personen-anwesenheitssensor-Steuerungen gesteuert werden, um die gesamte Beleuchtung in 20 Minuten oder weniger automatisch AUSzuschalten, nachdem der Steuerungsbereich nicht mehr belegt ist, und zwar entweder als:

  • A. Personen-anwesenheitssensor-Steuerungen (sofern 130.1(b) nicht die Mehrstufige Beleuchtungssteuerung erfordert); oder
  • B. Teil-EIN Personen-anwesenheitssensor-Steuerungen, oder
  • C. Anwesenheitserkennungs-Steuerungen, bei denen die gesamte Beleuchtung nur auf eine manuelle EINGABE reagiert

Additionally, for open offices > 250 sq. ft:

130.1 (c) 6. Full or partial-OFF occupant sensing controls are required for offices greater than 250 square feet.

In office spaces greater than 250 square feet, general lighting shall be controlled with occupant sensing controls that meet all of the following:

  • Lighting shall be controlled separately in control zones not greater than 600 square feet. For luminaires with an embedded occupant sensor that are capable of reducing power independently from other luminaires, each luminaire can be considered its own control zone
  • The occupant sensing controls shall uniformly reduce lighting power in the control zone by at least 80% full power(or off) in 20 minutes or less after the control zone is unoccupied.
  • The occupant sensing controls shall automatically turn off lighting in ALL control zones in 20 minutes or less after the entire office space is unoccupied
  • When occupancy is detected:
    • in each control zone, lighting shall be allowed to automatically turn on to any level up to full power.
    • in other control zones that are unoccupied, lighting shall operate at no more than 20% full power.

Lassen Sie uns von Ihnen hören.

Lassen Sie Rayzeek Ihnen bei der Planung und Bereitstellung einer maßgeschneiderten energiesparenden Beleuchtungslösung helfen.

    German