RZ037-DRY Capteur de présence PIR pour montage au plafond avec relais à contact sec

RZ037-DRY

RZ037-DRY is a ceiling-mounted PIR occupancy sensor with an isolated dry-contact relay output for EMS, HVAC, and building control inputs.

It accepts 12/24VDC or 12/24VAC power and provides COM, NO, and NC relay contacts so a control system can receive occupancy status without the sensor directly switching line-voltage loads.

  • Isolated dry-contact relay output with COM, NO, and NC contacts
  • Relay contacts rated for 30VDC max and 1A max
  • 360-degree PIR occupancy detection from a ceiling position
  • Adjustable time delay, Lux level, and high/low sensitivity
  • Designed for low-voltage control-system wiring, not high-voltage load switching
En savoir plus

Points forts du produit

  • Dry-contact output: Isolated COM, NO, and NC relay contacts let a control system receive occupancy status without switching line-voltage lighting.
  • Low-voltage supply: Accepts 12/24VDC or 12/24VAC input for control-panel and low-voltage system installations.
  • Couverture PIR au plafond : Provides 360-degree passive infrared occupancy sensing from a ceiling-mounted position.
  • Field setup: Onboard buttons adjust time delay, Lux threshold, and high/low sensitivity.

Livraison rapide : 99% en stock

Gamme complète de produits activés par le mouvement

Demande de renseignements pour les commandes en gros ODM/OEM

RZ037 ceiling mounted PIR occupancy sensor front view

Dry-Contact Occupancy Sensing For Control Systems

The RZ037-DRY adapts the RZ037 ceiling PIR sensor format for low-voltage control systems that need an occupancy signal instead of a directly switched lighting load.

Its isolated relay provides Common, Normally Open, and Normally Closed contacts, making it suitable for EMS, HVAC, and building control inputs where the controller decides what action follows occupancy detection.

Commercial conference room ceiling HVAC vents for RZ037-DRY dry contact occupancy control context

Connect Occupancy Sensing To Building Controls

Use the dry-contact output when a control panel, HVAC controller, or energy management input needs to know whether a space is occupied without placing the sensor in the main load circuit.

Installers can choose the NO or NC contact logic according to the receiving system, then tune the time delay, Lux level, and PIR sensitivity from the sensor body after wiring.

Caractéristiques, avantages, spécifications

RZ037-DRY combines ceiling PIR occupancy detection, 12/24V AC/DC power, and isolated COM/NO/NC contacts so installers can verify coverage, relay logic, and setup values before ordering.

RZ037-DRY dry contact wiring diagram and specification image

Caractéristiques et avantages

  • Isolated dry-contact relay: COM, NO, and NC outputs support control-system inputs instead of direct line-voltage load switching.
  • 12/24V AC/DC supply: The sensor can be powered from 12/24VDC or 12/24VAC low-voltage control power.
  • 360-degree PIR detection: Ceiling-mounted passive infrared sensing covers occupancy around the sensor position.
  • Temporisation réglable : Select 15 seconds through 30 minutes to match testing, passageway, restroom, or work-area behavior.
  • Selectable Lux control: Off, 15 Lux, 25 Lux, and 35 Lux settings let installers decide when ambient light should hold the relay off.
  • Sensibilité haute/basse : The sensor can be tuned for the expected movement pattern and room conditions.
  • Clear wire identification: Red and black provide input power, while green, orange, and yellow provide NC, COM, and NO relay wiring.
Caractéristiques

Type de produit

Capteur de présence PIR monté au plafond avec sortie relais à contact sec

Tension d’entrée

12/24VDC or 12/24VAC

Relay contacts

Normally Closed (NC), Common (COM), Normally Open (NO)

Relay rating

COM input 30VDC max; NC/NO output 1A max

Cable wires

Red IN+, Green NC, Orange COM, Yellow NO, Black IN-

Type de capteur

Passive infrared (PIR)

Portée de détection

360 degrees

Diamètre de détection

8-12m when ambient temperature is below 27C

Motion detection speed

0.6-1.5m/s

Hauteur d’installation

2.5-3.5m

Délai

15s, 30s, 1min default, 3min, 5min, 10min, 30min

Niveau du capteur de luminosité

Off, 15Lux, 25Lux default, 35Lux

Sensibilité

Élevée ou faible

Température de fonctionnement

-10 to +40C

Humidité de fonctionnement

<93% RH

FAQ

What makes RZ037-DRY different from the line-voltage RZ037 models?

RZ037-DRY provides an isolated dry-contact relay output for a control system input. It is not specified as a direct line-voltage lighting load switch like the high-voltage RZ037 variants.

What power supply does RZ037-DRY need?

The manual specifies 12/24VDC or 12/24VAC input power. Red is IN+ and black is IN- in the supplied wiring diagram.

Which dry-contact wires are available?

The relay output provides green for Normally Closed, orange for Common, and yellow for Normally Open. Choose NO or NC logic according to the receiving EMS, HVAC, or building control input.

Can this sensor be used with EMS or HVAC systems?

Yes. The product description in the manual identifies EMS and HVAC systems as target integrations, with occupancy communicated through the internal isolated relay dry contact.

What coverage should installers expect?

The manual specifies 360-degree detection with an 8-12m detection diameter when ambient temperature is below 27C, and a recommended installation height of 2.5-3.5m.

Which setup values can be adjusted?

Installers can adjust time delay, light sensor level, and sensitivity. Time delay options range from 15 seconds to 30 minutes, Lux options include Off, 15Lux, 25Lux, and 35Lux, and sensitivity can be set to High or Low.

Why might the sensor not trigger immediately after power is restored?

The manual notes that when power is first turned on or restored, the sensor will not automatically control the load for the first one minute.